VVP10 HART
HART
®
VALVE POSITIONER
INSTALLATION, OPERATION, CONFIGURATION AND MAINTENANCE MANUAL
______________________________________________________________________________________________________________________________
19
3
CONFIGURATION
Configuration of VVP10 HART valve positioner can be done with a HART
®
programmer or with EDDL and FDT/DTM-
based tools. User can use a tablet, Android smartphone, HART
®
375, 475, PC programmer via FDT/DTM tools or a
PALM. Another way to configure the VVP10 HART is through local adjustment using a Vivace magnetic key.
3.1.
LOCAL CONFIGURATION
The equipment local configuration is executed by
using Vivace’s magnetic screwdriver on Z and S
orifices, located at housing superior side, under
identification plate. Orifice Z starts local configuration
and changes the field to be configured. Orifice S is
responsible for changing and saving the new value
on the selected field. Saving after LCD value
changing is automatic.
Figure 3.1 shows orifices Z and S for local
configuration, stamped on device housing, and their
functions on magnetic screwdriver actuation.
Figure 3.1 – Z and S orifices and magnetic screwdriver.
Insert the magnetic screwdriver on
Zero
orifice (Z). icon appears to indicate that device has recognized the
screwdriver action. Keep the magnetic screwdriver inside until “LOCAL ADJST” message is shown on display, then
remove it for 3 seconds. Insert the magnetic screwdriver into Z orifice again, so user can navigate through local adjust
parameters.
Table 3.1 indicates actions executed by magnetic screwdriver when inserted on Z and S orifices.
Table 3.1 – Z and S orifices actions.
Some parameters show the icon to allow user configuration on it by inserting the magnetic screwdriver into
Span
orifice (S). In case the parameter has pre-defined values, those will be rotate on display, while the magnetic
screwdriver remains into
Span
orifice (S).
In the case of a numeric parameter, this field will enter edit mode and the decimal point will begin to blink shifting to
the left. When entering Z orifice, the least significant digit (on the right) will begin to blink, indicating it is ready for
editing. When entering the key in S, user can increment this digit, varying from 0 to 9.
After editing the least significant digit, user must enter the key in Z so that the next digit (on the left) starts blinking,
allowing its edition. User can edit each digit independently, until the most significant digit (5th digit left) is configured.
After the 5th digit is edited, the numeric value signal can be edited with the key in S.
During each step, if the user removes the magnetic key from the local adjustment holes, editing will be completed and
configured value will be saved to the device.
If the configured value is not acceptable by that device parameter (invalid value), it will be returned to the last valid
value before edition. Depending on the parameter, some values can be shown on numerical or alphanumerical fields,
adjusting the best option view to user.
With the magnetic screwdriver out of Z and S orifices, device will leave local adjust mode after some seconds and
monitoring mode will be shown.
Orifice
Action
Z
Select configuration tree function
S
Act on selected function