VVP10 HART
HART
®
VALVE POSITIONER
INSTALLATION, OPERATION, CONFIGURATION AND MAINTENANCE MANUAL
______________________________________________________________________________________________________________________________
23
3.6.
HART CONFIGURATOR PROGRAMMING TREE
The programming tree is a tree-shaped structure with a menu of all available software features, as shown in figure
3.7. To configure the positioner online, make sure it is correctly installed with the correct 4-20 mA current source in
the power supply.
INFORMATION
The main information about the positioner can be accessed here.
Device
-
The main device information is found here, such as: Tag, Description, Address, Manufacturer, Device Type,
Device Profile, HART
®
Revision, Software Version and Order Code.
Sensor
-
Here is the main position sensor information: Position Mode, Magnet Type, Actuator Type and Air
Configuration (open or close).
CONFIGURATION
Here the positioner is configured in relation to the variables of communication, sensor operation and temperature
reading.
Hart
-
In this directory user can configure the parameters of address, current mode, number of preambles and write
protection, all related to HART communication.
Specific
-
In this directory, user can configure positioner’s position, temperature and pressure sensors (when
available), in addition to position and PID tuning adjustments, LCD display variables and characterization curve points.
For a detailed description of the parameters of this menu, refer to section 3.7.
Range
-
In this directory user can configure the Setpoint range in current mode (4-20 mA) and safety fault.
TRIM
In this directory user can adjust the position sensor (calibration of the user's lower and upper points), the input and
output currents (4 mA and 20 mA), temperature and input/output pressures sensors (when available). Figure 3.11
shows the connection of the multimeter with the positioner to the output current trim. See item 3.8 below for more
details.
MAINTENANCE
In this directory user can either restart the device by software or restore the factory default settings of the positioner.
OBSERVE
In this directory, the values of the Input Current, PV%, PV (Position), SV (Setpoint), TV (Temperature) and QV (Output
Current) are monitored.
DIAGNOSIS
In this directory user can configure and view the diagnostics of the equipment.
General Equipment Status
- Informs if there is any problem or alert related to communication or general sensor status
and calculated values.
Sensor Not Detected
No Motion/Air Supply
Current Failure
PID Control Deviation
Reversal Limit
Stroke Limit
Mileage Limit
Deviation Limit
Pressure
Limit Exceeded
Temperature Limit Exceeded
Partial Stroke Test Status (see section 3.9)
Malfunction
Fixed Current
PV Out of Operating Limit
Temperature Out of Operating Limit
Pressure Out of Operating Limit
Saturated Current