THC1 Kits Installation Guide
Overview:
Altronix/Hartmann Controls Trove kits are pre-assembled and consist of Trove enclosure with factory installed Altronix power supply/chargers and
sub-assemblies. Each kit also accommodates one (1) Hartmann Controls PRS_Master boards and up to four (4) PRS_TDM or PRS_IO8 boards.
Configuration Chart:
Altronix
Model Number
120VAC 60Hz Input Current (A)
Power Supply Board Input Fuse Rating
Power Supply Board Battery Fuse Rating
Nominal DC Output Voltage Options
Maximum
Supply Current for
Main and
Aux. Outputs on Power
Supply board and
ACM4 Access Power
Controller’s
outputs (A)
Fail-Safe/Fail-Secure or Dry Form “C” Outputs
Current Per ACM4 Output
(A)
ACM4 Board Input Fuse Rating
ACM4 Board Output Fuse Rating
[DC]
[AUX]
12VDC
Output
Range
(V)
24VDC
Output
Range
(V)
12VDC
Output
Range
(V)
24VDC
Output
Range
(V)
T1HCK3F
3.5
5A/
250V
15A/
32V
eFlow6NB
12 or 24VDC @ 6A
–
–
–
–
10.0-
13.2
20.19-
26.4
10.03-
13.2
20.19-
26.4
T1HCK3F4
3.5
5A/
250V
15A/
32V
eFlow6NB
12VDC @ 5.4A
or
24VDC @ 5.7A
4
2.5 10A/
32V
3A/
32V
10.0-
13.2
20.19-
26.4
10.03-
13.2
20.19-
26.4
Hardware and Accessories:
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws
in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws; level and secure.
Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install
the three fasteners. Place the enclosure’s upper keyholes over the three upper screws.
Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in desired location,
opposite hinge. Slide the tamper switch bracket onto the edge of the enclosure approximately 2” from the
right side
(Fig. 1, pg. 2)
. Connect tamper switch wiring to the Access Control Panel input or the
appropriate UL Listed reporting device. To activate alarm signal open the door of the enclosure.
4. Mount Hartmann Controls boards to backplane,
refer to pages 3-4.
5. Refer to the
eFlow Power Supply/Charger Installation Guide
for eFlow6NB and
Sub-Assembly Installation Guide
for ACM4 for further installation instructions.
Fig. 1
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Nylon or Metal Spacer | 5/16” Pan Head Screw | Lock Nut