Section 2:
Installation
Copyright © 2011 Haskris Company
15
www.haskris.com
Version R1600-X-R407C-XXX Instruction Manual Rev00
6.
After the level of glycol solution in the tank has reached the full level, close fill
valve as shown in Figure 2.10 and install the protective cap back on the ¾”
GHT connection.
•
Fill Piping
1.
Close supply and return side isolation valves as shown in
Figure 2.9 of Section 2.6.2.
2.
Remove protective cap from the supply side flush valve and
connect hose to the ¾” GHT connections (as shown in Figure
2.9).
3.
Remove protective cap from the return side flush valve and
connect hose to the ¾” GHT connection (as shown in Figure
2.9). Place the other end of the hose in a large bucket. This
will be used as a vent when filling the piping with 35% glycol
solution through the supply side flush valve. Open the return
side flush valve.
4.
Open the supply side flush valve and fill the piping with 35%
glycol solution. The use of an external pump may be required
to properly fill the system with glycol solution. See Table 2
below for approximate volume in gallons per 100 feet of
piping.
DO NOT USE THE
CIRCULATING
PUMP IN THE R1600 TO FILL
PIPING.
!!!!