Venting: 

1.

 

The (I) (IS) HRDV model furnace is equipped with a power venter and is complete as received. 

2.

 

No further venting of unit is required for outdoor installation (HRDV). 

3.

 

Venting is required on all indoor installations ISHRDV, and IHRDV units.  
a.

 

Positive pressure flue vent is recommended for installations inside building.  Provide for the ISHRDV and 
IHRDV Series.  For the requirement of positive pressure flue vent, review local codes. 

b.

 

Pitch vent pipe up toward outlet, ¼” per foot for condensate drainage. 

c.

 

Type “B” gas vent is recommended for flue venting above roof lines or external wall penetrations. 

d.

 

Straight vertical runs out through the roof are preferred.  Vertical stack must be a minimum of five feet 

high. 

e.

 

Vertical flue stacks shall be terminated with an approved cap. 

f.

 

The maximum horizontal vent pipe length for these heaters is shown in table II. A total equivalent horizontal 
vent pipe length can be calculated using equivalent straight pipe lengths for tees and elbows reducing the 

maximum horizontal vent pipe length by six feet for each sweep elbow, two and one half feet for 
termination tee, and ten feet for each short radius elbow. 

g.

 

A gradually tapered vent pipe transition is required for (I)ISHRDV-100, (I)ISHRDV-125, and (I)ISHRDV-160 

units when using 4 inch vent pipe. 

h.

 

When possible, locate horizontal vent hoods that do not face the direction of prevailing winds to diminish 
the possibility of back draft situations. 

i.

 

For U.S.A. standards vent systems must conform to the latest edition of  the  National  Fuel  Gas  Code  

(NFPA#54)  and  the  latest edition of NFPA #211, or as follows: 
·  Not less than 7 feet above grade when located adjacent to public walk ways. 
·  AT least 3 feet above any forced air inlet located within 10 feet. 
·  At least 4 feet below, 4 feet horizontally from or 1 foot above any door, window or gravity  air  inlet  into     

   any building. 
·  At least 1 foot above grade, or at least 1 foot above the normally expected snow accumulation level. 
·  Directed such as to not jeopardize people. 

·  At least 4 feet from electric meters, gas meters, regulators and relief equipment. 
·  Sealing or shielding of exposed surfaces with a corrosion  resistant  material  may be  required  to prevent   
   staining or deterioration of building materials, and 
·  Not less than 2 feet from an adjacent building. 

j.

 

In Canada vent systems must conform to the latest edition of the Natural gas and Propane Installation Code 
(CAN/CGA-B149.1 or CAN/CGA-B149.2), or as follows: 
·  A venting system shall not terminate underneath a veranda, porch, or deck, or  above  a  paved  sidewalk   

   or  a paved driveway that is located between two buildings, and that serves both buildings. 
·  The exit terminals of mechanical draft systems shall  not be less than  2.14m  above  grade when located   
    adjacent  to a paved sidewalk or driveway. 
·  A venting system shall not direct flue gases towards brickwork,  siding,  or other  construction,  in such a 

   manner that may cause damage from heat or condensate from the flue gases. 
·  A vent system shall not direct flue gases so as to jeopardize people, overheat combustible structures,  or  
   enter buildings. 

·  A venting system shall not terminate within 1.8m of the following: 
    ·  A window, door or mechanical air supply inlet of any building, including soffit openings. 
    ·  A gas service regulator vent outlet. 
    ·  A combustion air inlet. 

    ·  A property line. 
    ·  A direction facing combustible materials or openings of surrounding buildings 
·  A venting system shall not terminate within 1m of the following: 

    ·  Above a gas meter/regulator assembly within 1m horizontally of the vertical centerline of the regulator. 
    ·  An oil tank or an oil tankfill inlet. 
    ·  The inside corner of an L-shaped structure. 
·  A venting system shall not terminate within .3m of the following: 

    ·  Above grade level or any surface that may support snow, ice, or debris.  

 
 

 
 
 

Summary of Contents for HR SERIES

Page 1: ...on If any part is missing or damaged notify the carrier at once TABLE OF CONTENTS Page IH ISH H RHF IH ISH H RMU and IH ISH H RHV Unit Dimensions 1 2 H RHF and H RHV Unit Dimensions with Optional Intake and Discharge Plenums and Curbs 2 3 H RMU and H RHV Unit Dimensions with Optional Discharge Plenums and Curbs 4 5 Shipping 5 Hoisting Unit 5 Installation 6 Electrical 6 Location 7 8 Gas Supply Pipi...

Page 2: ......

Page 3: ......

Page 4: ......

Page 5: ......

Page 6: ... ISH H RHVA 210 1285 IH ISH H RHFA IH ISH H RMUA IH ISH H RHVA 250 1560 IH ISH H RHFA IH ISH H RMUA IH ISH H RHVA 300 1625 IH ISH H RHFA IH ISH H RMUA IH ISH H RHVA 400 1840 IH ISH H RHFA IH ISH H RMUA IH ISH H RHVA 600 3350 IH ISH H RHFA IH ISH H RMUA IH ISH H RHVA 800 3880 IH ISH H RHFB IH ISH H RMUB IH ISH H RHVB 200 1445 IH ISH H RHFB IH ISH H RMUB IH ISH H RHVB 250 1525 IH ISH H RHFB IH ISH H...

Page 7: ...losion loss of warranty or even death Installation of this appliance must conform to applicable federal state and local codes and regulations and with guidelines established by A G A American Gas Association NFPA National Fire Protection Association N E C National Electrical Code the National Board of Fire Underwriters and CAN CGA B149 Listed are the codes appearing in this text the Associations a...

Page 8: ... in other sections such as offices and shops connected with hangar and in public garages Also the heaters must be so located that they will be protected from damage by aircraft cranes scaffolding etc and must be accessible for servicing and adjustment Standard ANSI NFPA 88 Latest revisions specifies that the heater must be so located that the clearance to combustible materials conform with NFPA No...

Page 9: ...from or 1 foot above any door window or gravity air inlet into any building At least 1 foot above grade or at least 1 foot above the normally expected snow accumulation level Directed such as to not jeopardize people At least 4 feet from electric meters gas meters regulators and relief equipment Sealing or shielding of exposed surfaces with a corrosion resistant material may be required to prevent...

Page 10: ...c pressure drop schedule 40 pipe and fittings TABLE III Input in 1000 s BTU Hr Maximum Distance from Meter Natural Propane 50 feet 100 to125 100 feet 1 60 feet 1 150 to 175 100 feet 1 1 30 feet 1 120 feet 1 1 200 to 250 250 feet 1 1 75 feet 1 1 300 200 feet 1 1 50 feet 1 1 400 to 420 100 feet 1 1 35 feet 1 1 500 80 feet 1 1 300 feet 2 2 50 feet 1 1 600 200 feet 2 2 30 feet 1 1 800 125 feet 2 2 80 ...

Page 11: ...ell Modusnap Valve Model Size 400 Temperature Settings of Controls Modusnap Valve TL and DC TL SET THIS CONTROL TO 110 DEGREES THERE IS NO OTHER SETTING ADJUSTMENT This control is to protect the modusnap valve bulb from exceeding 120 degrees DC SET THIS CONTROL TO 2 TO 3 DEGREES ABOVE MODUSNAP VALVE SETTING MODUSNAP VALVE SET THIS CONTROL 2 TO 3 DEGREES ABOVE ROOM THERMOSTAT SET POINT This is to a...

Page 12: ......

Page 13: ...the discharge air sensor Maintenance 1 Motors should be relubricated according to the manufacturer s lubrication instructions 2 Filters must be cleaned cleanable type or replaced throw away type with like filters as often as necessary so as not to restrict air delivery 3 Twice a year check belts and sheaves for alignment and belt tension 4 When a belt is replaced shorten center distance between sh...

Page 14: ......

Page 15: ...3606 Yost Avenue Hastings Nebraska 6891 1966 Phone 402 463 9821 Fax 402 462 8006 www hastingshvac com E mail sales hastingshvac com ...

Page 16: ... 1 April 2008 WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment WARNING FOR YOUR SAFETY If you smell gas 1 Open windows 2 Don t touch electrical switches 3 Extinguish any open flame 4 Immediately call gas supplier F...

Page 17: ... with products of combustion will cause serious damage c Indoor units must have adequate COMBUSTION AIR If heaters are installed in a closed room provide outside opening of one square inch per 1 000 BTU for combustion air alone d Indoor units must not operate in an area with a negative air pressure condition Provide adequate MAKE UP AIR e Indoor units installed where there is sawdust lint soot dir...

Page 18: ...se of trouble must be corrected IMMEDIATELY to avoid serious damage to the furnace The limit switch is a safety control NOT AN OPERATING CONTROL 14 Special precautions for furnaces used in conjunction with AIR COOLING and MAKE UP AIR SYSTEMS a Type 409 STAINLESS STEEL heat exchangers may be used in all applications but is recommended for make up air systems where inlet air temperature is ABOVE 40º...

Page 19: ...onform with NFPA Nos 52 and 54 and that such material must not attain a temperature over 160º by continued operation of the heater 5 If two furnaces are to be used in a side by side application they must be installed so that the ENDS OPPOSITE the control access doors ADJOIN 6 A 4 inch frame is an integral part of the appliance and may be installed directly on the floor or roof or other combustible...

Page 20: ...conform to the latest edition of the Natural gas and Propane Installation Code CAN CGA B149 1 or CAN CGA B149 2 or as follows A venting system shall not terminate underneath a veranda porch or deck or above a paved sidewalk or a paved driveway that is located between two buildings and that serves both buildings The exit terminals of mechanical draft systems shall not be less than 2 14m above grade...

Page 21: ...supply connection to the appliance 9 The furnace must NOT be operated without a leak limiting orifice installed in the unit pressure regulator vent if applicable 10 The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of PSIG 11 The appliance must be isolated from the gas supply ...

Page 22: ...t burner to a quiet blue flame Flame must surround the end of the flame rod for proper operation of the flame sensing circuit No combustion air adjustment is required on main burners 4 Pressure regulator setting must NOT be changed except under qualified supervision If necessary contact gas company before adjusting 5 With the unit firing a maximum input the gas line pressure should be maintained a...

Page 23: ...rmer all wiring connections improper ground blown fuse in ignition module if applicable faulty high limit switch voltage leaks in igniter lead or cracked flame rod insulator and proper igniter sensor gap approximately 1 8 Correct as necessary If igniter still does not spark replace ignition module 5 Improper pilot Flame either too small or flame lifts If pilot is too small clean pilot line primary...

Page 24: ...nd MV PV terminals If no or inadequate voltage is detected replace module If voltage is satis factory inspect main gas valve 5 Inoperative main gas valve Check all wiring connections between ignition module and main gas valve and correct as necessary If module and wiring inspections are satisfactory replace main gas valve or valve operator Main Burners Shutdown Before Call for Heat Is Satisfied 1 ...

Page 25: ...and 12 3 Insufficient combustion air Make sure air inlets of unit are open Clean unit If condition still exists see item 1 of INSTALLATION PRECAUTIONS Blower Fails to Operate within 2 Minutes after Burners Ignite 1 Faulty blower wiring connections motor or fan Inspect and correct wiring connections as necessary controls Connect line voltage directly to motor If motor operates replace fan control i...

Page 26: ...ly and allow panel to drop Remove panel and disconnect applicable electric wiring Remove retaining tabs at each end of the burner drawer and slide drawer assembly out of the furnace b Remove the screws holding top panel and lift panel off c Remove the screws from bottom flange of the collector box cover and lift cover off d Remove the screws from bottom flange of the collector box Remove the two s...

Page 27: ...ue tubes using a 1 1 2 or 1 3 4 long handled wire brush Clean and replace flue baffles m Remove dirt from bottom pan and clean burners before replacing drawer assembly Cleaning Burners 1 Burners can be removed from drawer assembly by raising front of burner pushing burner forward against the hold down clip until venturi end of burner is free of support Remove burners next to pilot last and replace...

Page 28: ......

Page 29: ......

Page 30: ...must be installed downstream of blower Dimensions Outdoor Model HRDV MODEL NO 100 125 160 210 250 300 400 500 A 500 B 600 A 600 B 800 A 800 B A 30 5 8 30 5 8 41 3 8 41 3 8 41 3 8 52 1 16 65 1 2 52 1 16 52 1 16 65 1 2 AA 1041 8 1041 8 131 B 18 18 28 3 4 28 3 4 39 1 2 39 1 2 527 8 39 1 2 39 1 2 52 7 8 BB 87 3 4 87 3 4 1145 8 C 21 7 8 21 7 8 32 5 8 32 5 8 43 3 8 43 3 8 567 8 43 3 8 43 3 8 56 7 8 CC 6...

Page 31: ...ssional assistance to help you with a solution to that problem Two inbound Watts lines to the home offices enables you to consult with qualified factory service personnel For needed parts appliance data or assistance on a service problem contact the service department of Hastings HVAC Inc Also when ordering replacement parts be sure to specify the following 1 Model and serial number of unit 2 Type...

Reviews: