Model

Voltage

Kilowatts

(kW)

Phase

Amps

Wiring Sizing

AWG*†

Fuse or 

Circuit Breaker* Shipping Weight

FR2-3

208

3.0

1

14.4

12

20

24 lbs. (11 kg)

240

3.0

1

12.5

12

20

24 lbs. (11 kg)

FR2-4

208

4.0

1

19.2

12

30

24 lbs. (11 kg)

240

4.0

1

16.7

12

30

24 lbs. (11 kg)

FR2-6

208

6.0

1

28.8

10

40

27 lbs. (12 kg)

240

6.0

1

25

10

40

27 lbs. (12 kg)

FR2-3B

208

3.0

3 (Bal.)

8.4

14

15

24 lbs. (11 kg)

240

3.0

3 (Bal.)

7.3

14

15

24 lbs. (11 kg)

FR2-4B

208

4.5

3 (Bal.)

11.2

14

15

24 lbs. (11 kg)

240

4.5

3 (Bal.)

9.6

14

15

24 lbs. (11 kg)

FR2-6B

208

6.0

3 (Bal.)

16.7

12

30

27 lbs. (12 kg)

240

6.0

3 (Bal.)

14.5

12

20

27 lbs. (12 kg)

FR2-9B

208

9.0

3 (Bal.)

25

10

40

27 lbs. (12 kg)

240

9.0

3 (Bal.)

21.7

10

30

27 lbs. (12 kg)

Electrical Rating Chart—FR2 Models

*

Wire size is based on THHN wire for branch circuit protection at 0.91 derate factor. Circuit breakers and fused disconnects are

to be mounted remotely and wired by electrical contractor. Sizes are based on the 2002 NEC table 310-16. Conduit size based

on conductors plus ground wire sizing per Table C1 from Appendix C.

Based upon THHN wire rated 90ºC.

NOTE: Shipping Weight includes packaging.

Form No. HHM-0517

6

SPECIFICATIONS

Summary of Contents for FR2 Series

Page 1: ...lla en el seguimiento de las instrucciones contenidas en este manual puede resultar en un serio lesi n o muerte Este manual contiene importante informaci n sobre seguridad concerniente al mantenimient...

Page 2: ...lable in the United States and Canada by calling 800 558 0607 INTRODUCTION Form No HHM 0517 2 CONTENTS Hatco 3CS2 Hydro Heater Sanitizing Sink Heaters and FR2 Hydro Heater Food Rethermalizers Bain Mar...

Page 3: ...trical shock or burn Genuine Hatco Replacement Parts are specified to operate safely in the environments in which they are used Some aftermarket or generic replacement parts do not have the characteri...

Page 4: ...CS2 FR2 Series Hydro Heater Electronic Controller POWER ON OFF I O Switch Drain Handle closed Outlet Inlet Drain Clean out Drain Units are voltage specific Refer to specification label for electrical...

Page 5: ...ctory with an electrical cord and plug installed Plugs are supplied according to the applications ELECTRIC SHOCK HAzARD For units with an electrical cord and plug plug unit into a properly grounded el...

Page 6: ...3 Bal 9 6 14 15 24 lbs 11 kg FR2 6B 208 6 0 3 Bal 16 7 12 30 27 lbs 12 kg 240 6 0 3 Bal 14 5 12 20 27 lbs 12 kg FR2 9B 208 9 0 3 Bal 25 10 40 27 lbs 12 kg 240 9 0 3 Bal 21 7 10 30 27 lbs 12 kg Electri...

Page 7: ...o be incorporated into a hot water bath rethermalizer Hatco does not supply the vessel that contains the water nor the system that determines how food is placed and held in the vessel The Hatco FR2 un...

Page 8: ...n electrical cord and plug require a hardwired connection to on site electrical system Connection must be properly grounded and of correct voltage size and configuration for electrical specifications...

Page 9: ...se or pipe may be connected to the heater drain and run to an open sight drain The heater drain should not be permanently connected to the sanitary drain system The clean out brush must have access to...

Page 10: ...f 190 F 88 C Use appropriate protection when operating unit DO NOT set temperature control higher than 190 F 88 C Units are designed to heat water up to 190 F 88 C Water over 190 F 88 C is very active...

Page 11: ...rd until it is in the horizontal position and allow all water to drain Unscrew and remove the pipe cap s from the clean out drain s and allow all water to drain if applicable 5 Wipe visible deposits f...

Page 12: ...ER ON OFF I O switch to the OFF O position and then to the ON I position Fuses may be blown the circuit breaker may be tripped or the power cord may be unplugged Check for proper fuse sizing and repla...

Page 13: ...nd must conform with all federal state and local codes Do not exceed an incoming water temperature of 140 F 60 C or incoming water pressure of 80 psi 550 kPa 1 Make sure the POWER ON OFF I O switch is...

Page 14: ...h and adapter Use the following procedure to power flush the unit 1 Move the POWER ON OFF I O switch to the OFF O position and allow the unit and water to cool 2 Connect one end of a drain hose onto t...

Page 15: ...ROPERTY RIGHT INFRINGEMENT Without limiting the generality of the foregoing SUCH WARRANTIES DO NOT COVER Coated incandescent light bulbs fluorescent lights heat lamp bulbs coated halogen light bulbs h...

Page 16: ...a 402 341 1414 NEVADA Burney s Commercial Las Vegas 702 736 0006 Hi Tech Commercial Service N Las Vegas 702 649 4616 NEW JERSEY Jay Hill Repair Fairfield 973 575 9145 Service Plus Flanders 973 691 630...

Reviews: