Page 15
BCS3000M-9
APPENDIX C: HIGH TEMPERATURE LIMIT
Hauck P/N 62823.
The high temperature limit has been configured at the factory and should not require any
adjustments. The procedure for changing the limit setpoint and a configuration record are given
below. Detailed information is given in the vendor literature supplied with the control panel.
Figure 1 Front Face of High Temperature Limit.
Changing the limit setpoint
Hold the SETUP key and press the
[
]
key. The lower display will show SLCT and the upper
display will read OPTR. Release the SETUP key and press the
[
]
key until the upper display
reads SETP then press SETUP again to display the current setpoint. Use the
[
]
or
[
]
keys to
change the setpoint.
Hold SETUP and press the
[
]
key then release the SETUP key and press the
[
]
key until the
upper display again reads OPTR; then press SETUP to return to the operating (normal) display.
CONFIGURATION RECORD SHEET
SLCT = CONF
ULOC = 20
LOWER DISPLAY
FACTORY
FINAL
(FUNCTION)
CONFIGURATION
SETTING
INPT
J.F
__________
RUL
999.9
__________
RLL
-199.9
__________
OFFS
0.0
__________
CTRL
HI
__________
SPUL
999.9
__________
SPLL
-199.9
__________
ALA1
P_HI
__________
PHA1
999.9
__________
AHY1
0.1
__________
ALA2
P_LO
__________
PLA2
-199.9
__________
AHY2
0.1
__________
USE2
A1_D
__________
USE3
A2_D
__________
DISP
ENAB
__________
CLOC
20
__________
AHY2
0.1
__________
AHY2
0.1
__________