background image

                                                                                                                                                

Page 4  

        BCS3000M-9 

4. 

Determine the burner fuel control motor type and install a jumper: 

a.  From fuse 5 to ground for a Honeywell M6284 or Barber-Coleman EA57 medium torque 

motor. 

b.  From fuse 5 to fuse 7 for a Barber-Coleman EA71 or EA73 high torque motor. 

5. 

Verify that the 

SELECT R4 

jumper on the printed circuit board is in the correct position for 

the burner application.  Position 

A

 (default) holds the fuel motor at low fire during purge while 

position 

B

 drives the fuel control motor open until purge time is completed. 

6. 

Wire the fuel valves, valve position limit switches and fuel pressure limit switches as shown 
on the external component wiring diagram. 

7. 

Install the exhaust fan flow limit switch in the dryer exhaust duct as shown in Appendix D.  
Wire the normally open contact of the exhaust flow limit to the appropriate terminals in either 
the burner junction box or the BCS control panel. 

8. 

Install a limit switch on the exhaust damper set to close when the damper is greater than 
50% open. 

9. 

Install the stack temperature thermocouple in the dryer exhaust duct to sense exhaust gas 
temperature.  See Appendix E

 

for installation instructions. 

AND / OR 

10.  Install a Hauck Rapid Response material temperature thermocouple in the material 

discharge chute to sense the temperature of the material leaving the dryer.  See Appendix F

 

for recommended installation. 

11.  Connect the thermocouples to the appropriate terminals in the BCS control panel using 

thermocouple cable of the same type as the Material and/or Stack thermocouples. 

 

 

 

 

 

 

 

12.  Install the pilot and main flame scanners on the burner and wire them to the appropriate 

terminals in the burner junction box. Reference burner instructions for scanner installation 
details. 

13.  Refer to the external component wiring diagram for interconnection between the burner 

junction box and the BCS panel terminal strips. 

 

 

 

 

 

 

 

 

IMPORTANT 

Thermocouple cables must be separated from AC power and control wiring to avoid 
interference and nuisance shutdowns.  Observe polarity when making thermocouple 
connections.  Regardless of thermocouple type, the red wire is always negative. 
Shielded cable may be used to provide additional protection from AC power and 
radio frequency (RF) interference. 

Only one end of the cable should be 

grounded.

 Use a ground terminal in the BCS panel for this purpose. 

IMPORTANT 

The flame scanner and control motor position feedback signals should be 
run in a separate cable from the burner junction box to the BCS control 
panel.

 This cable may be run along with thermocouple cables but must be 

separated from all other AC power and control cables. Shielded cable may be 
used to provide additional protection from AC power and radio frequency (RF) 
interference.  

Only one end of the cable shield should be grounded.

  Use one 

of the ground terminals in the BCS control panel for this purpose. 

 

Summary of Contents for BCS-3000M

Page 1: ...el Adjustment of this equipment and its components by unqualified personnel can result in fire explosion severe personal injury or even death BCS 3000M 9 INSTRUCTIONS These instructions are intended to serve as guidelines covering the installation operation and maintenance of Hauck equipment While every attempt has been made to ensure completeness unforeseen or unspecified applications details and...

Page 2: ... DEC the burner position via the MANUAL switch The left AUTO position enables the Temperature Controller to operate the burner The alarm contact of the High Temp Limit instrument is used to shut down the burner if the preset high temperature limit is exceeded An auxiliary temperature limit is also available as an option Refer to Appendix C for entering the desired alarm setpoints WARNING This equi...

Page 3: ...Assy CY7997 CY7997 CY7997 System Schematic CY7986 CY8078 CY8078 Wiring Diagram CY7995 CY7995 CY7995 External Component Wiring CY8000 CY8114 CY8079 BCI Panel Assembly NA CY7813 CY8034 BCI System Schematic NA CY8108 CY8024 D INSTALLATION 1 Locate the tabletop panel on a firm support in an area that is protected from the weather and free from vibration The drop in version is designed to install in an...

Page 4: ...ee Appendix F for recommended installation 11 Connect the thermocouples to the appropriate terminals in the BCS control panel using thermocouple cable of the same type as the Material and or Stack thermocouples 12 Install the pilot and main flame scanners on the burner and wire them to the appropriate terminals in the burner junction box Reference burner instructions for scanner installation detai...

Page 5: ...issive contacts are closed after the air control valve drives open for purge Eco Star and StarJet conversion burners only F FINAL CHECKOUT 1 Ensure sure that all equipment and components have been installed in accordance with the manufacturer s instructions 2 Verify all wiring and tighten connections 3 Confirm all linkage adjustments and insure that control arms and linkage rods are tight 4 Clean ...

Page 6: ... switches have closed a A message will appear b The START pushbutton will flash indicating that the burner is ready to start 9 Press and hold the START pushbutton to begin the burner ignition sequence a The RM7890A flame relay will be energized b Start Relay R3 will be energized and a ten second trial for ignition will begin c When the message appears the START pushbutton may be released d The ign...

Page 7: ...will drive closed f Purge Relay R4 will be energized H TROUBLESHOOTING PROBLEM POSSIBLE CAUSE CORRECTIVE ACTION No power to instruments or indicator lights L1 fuse blown Check for 120Vac between L1 and L2 Replace 10A fuse L1 Purge limits are not made Check purge limits series 120Vac on terminals 19 24F 24E 24D 24C 24B 24A and 24 Low fire limit switch es are not made Check low fire limit switch es ...

Page 8: ...nal 16 For StarJet EcoStar Check the secondary air interlock contact terminal 14 the primary air interlock terminal 15 the primary air or compressed air pressure switch terminal 15A and the secondary air pressure switch terminal 16 Low gas pressure fault Check the low gas pressure limit switch 120Vac on terminal 16A High gas pressure fault Check the high gas pressure limit switch 120Vac on termina...

Page 9: ...ppears replace pilot scanner If signal remains replace main flame scanner Flame relay ALARM led indicator comes on and will not reset Improper grounding or voltage polarity Flame relay failure Verify neutral L2 of 120Vac supply is grounded Verify that control panel is grounded Replace flame relay amplifier and or relay module indication but fuel control motor will not drive Fuse 5 blown Pilot time...

Page 10: ...nable the burner control motor to be driven by the Honeywell Temperature Controller without having to fire the burner 3 Turn the panel power on Enter the calibration mode on the Temperature Controller by pressing the SETUP key until the display reads CALIB POSITION 4 Press the FUNCTION key to display DISABLE POS PROP then press the key to change the upper display DO AUTO 5 Press FUNCTION to begin ...

Page 11: ...eld adjustments other then as noted in this instruction sheet PLEASE CONTACT THE HAUCK SERVICE DEPARTMENT I OPERATOR INTERFACE Figure 1 shows the front face of the UDC3200 instrument This section describes the function of the various displays and keys Examples are given for changing the controller setpoint and operating the burner in MANUAL Detailed information is given in the vendor literature su...

Page 12: ...digit one place to the left To decrease the set point value reverse the above procedure EXAMPLE 2 ADJUSTING THE BURNER FIRING RATE IN THE MANUAL MODE Press the AUTO MANUAL key to place the Controller in the Manual Mode The MAN indicator will come on and the lower display will automatically change to show OUT Press and hold the key to increase Output value To make changes more quickly press the key...

Page 13: ...UNE FUZZY DISABLE __________ ACCUTUNE DISABLE __________ ALGORITHM CONT ALG PID A __________ TIMER DISABLE __________ IN ALG 1 NONE __________ OUT ALG OUT ALG POSITN __________ MOTOR TI 40 __________ INPUT 1 IN 1 TYPE J TC L __________ IN 1 HIGH 550 0 F __________ IN 1 LOW 20 00F __________ RATIO 1 1 000 __________ BIAS IN 1 0 0 __________ FILTER 1 1 __________ BURNOUT 1 UP __________ INPUT 2 IN 2...

Page 14: ... AUTO OUT 0 0 __________ PB OR GAIN PB PCT __________ MIN OR RPM RPM __________ COM COM ADDR 3 __________ COMSTATE DISABLE __________ IRENABLE ENABLE __________ BAUD 19200 __________ TX DELAY 1 __________ ALARMS A1S1 TYPE NONE __________ A1S2 TYPE NONE __________ A2S1 TYPE NONE __________ A2S2 TYPE NONE __________ ALARM HYST 0 1 __________ BLOCK DISABLE __________ DIAGNOST DISABLE __________ A1S1 ...

Page 15: ... display reads SETP then press SETUP again to display the current setpoint Use the or keys to change the setpoint Hold SETUP and press the key then release the SETUP key and press the key until the upper display again reads OPTR then press SETUP to return to the operating normal display CONFIGURATION RECORD SHEET SLCT CONF ULOC 20 LOWER DISPLAY FACTORY FINAL FUNCTION CONFIGURATION SETTING INPT J F...

Page 16: ...o the duct and hold in place 4 Using the second half of the flange tighten the 1 4 20 bolts to hold the pitot in place 5 WARNING Do not fasten both halves of the flange One side is left unbolted for removal and cleaning of Pitot tube 6 For other applications weld the four duct mounting nuts to the inside of the ductwork using the flange as a pattern 7 Use silicone caulk as a gasket 8 Remote mount ...

Page 17: ...st duct to sense exhaust gas temperatures Drawing showing placement of thermocouple in exhaust duct NOTE Thermocouple cables must be separated from AC power and control wiring to avoid interference and nuisance shutdowns Observe polarity when making thermocouple connections Regardless of TC type the red wire is always negative ...

Page 18: ... slow moving area next to the dam The dam must only be wide enough and high enough to create a localized area of build up where the material loses velocity BUT DOES NOT STOP FLOWING The thermocouple must not be located in a stagnant zone or erroneous temperature readings will result Because of the large number of variables involved it is impossible to set down any exact size or location of the dam...

Page 19: ...00 17292 2 Relay 3PDT P B KUP 14A35 or equal 61961 1 Purge timer ATC 407B 100 F3K 40744 1 Timer 10 second solid state Omnetics MMS115A19 1 2B 40747 1 Timer 3 second solid state Omnetics MMS115A1Z3B 55167 5 Fuse 7A 1 4 x 1 1 4 Littlefuse type 313007 48044 5 Fuse 10A 1 4 x 1 1 4 Littlefuse 312010 43508 or 43508R2037 1 Material thermocouple Hauck TC100A J or Material thermocouple Hauck TC100A K 43868...

Page 20: ...Page 20 BCS3000M 9 This page left intentionally blank HAUCK MANUFACTURING CO P O Box 90 Lebanon PA 17042 0090 717 272 3051 www hauckburner com Fax 717 273 9882 ...

Reviews: