16
Art. Nr.: 5090032060
Rev.: 01/2020-01-22
1
Outside of building
Centre the flange over the existing opening.
Align horizontally using the integrated level and mark
the dowel holes (see fig.: 12).
2
Then drill the dowel holes (Ø 10 mm, 80 mm deep)
and clean (see fig.: 13).
• According to DIN 18533 with PMBC (W1-E
to W2.1 E): min. flange outer edge to flange
outer edge, to other components, to building
edges. Distance: min. 150 mm.
Distance to building joints: min. 300 mm.
• Waterproof concrete: Center distance min.
250 mm with multiple arrangement.
3
For assembly, the adhesive and sealant EGO
MS805 (not included in the scope of delivery,
accessories) is to be used, which achieves a
complete adhesion to the substrate. Use with
PMBC thick coating (KMB) according to DIN EN
15814:
The basis for mounting on wall surfaces with
PMBC thick coatings is a professionally executed
building sealing according to DIN 18533-3 and
a fully cured thick coating.
The adhesive and sealant should be applied in the
preformed seal recesses at the rear of the flange (see
fig.: 14).
4
Following this, press the flange onto the wall and
use the pre-installed screws to insert the fastening
dowels and sealing rings until the dowel shaft is inside
the flange base and is flush with the surface of the
wall.
Tighten the screws as shown below (see fig.: 15).
• Tightening torque for concrete:
up to 14 Nm
.
• Tightening torque for masonry:
6 Nm
.
5
Apply a
thorough
coat of GMS „SEGMENTO“ lub-
ricant (included in scope of delivery) to the sealing
lip of the HSI150 S3 system cover and the flange seal
seat.
Twist slightly to insert it into the bayonet of the
plastic flange and screw it in clockwise as far as it
will go using the flexible socket wrench (see fig.: 16).
6
Use the assignment template to determine the dia-
meter of the cables and select the appropriate seg-
ments based on this information (see table 2 under
point 4 "
Description SEGMENTO combination
kit KKS
") (see fig.: 18).
Then clean the cables with cable cleaner.
The drill holes in the wrench thread of the
system cover must correspond to the arrows on
the flange (see fig.: 17).
Legend for fig.: 17
1
Flange arrow
2
Drill holes in the wrench thread
7
Remove the blind plug from the coloured sealing
segment.
Apply a
thorough
coating of GMS „SEGMENTO“
lubricant to the opening(s) of the sealing segment and
cables (see fig.: 19).
Do not install the sealing segment yet!
8
Route the cable through the corresponding opening
in the HSI150 S3 system cover (see fig.: 21).
Then, slide the sealing segment over the required
length of routed cable and allow it to click into place
in the opening of the HSI150 S3 system cover on the
outside of the building (see fig.: 21).
Use the Hauff DSD torque screwdriver to tighten the
Allen screws until the torque control triggers an acoustic
and mechanical signal
(tightening torque 1,2 Nm)
.
9
Install other sealing segments according to work stages
6 - 9 and push black screw-on cover caps onto the
allen screws (see fig.: 22).
Leave the blind plug in the sealing element if it is not
being used (see fig.: 22).
If cables are to be installed at a later date,
remove the corresponding sealing segment and
carry out the installation as described in work
stages 6 - 9.
HSI150 SEGMENTO / SEGMENTO combination kit KKS
EN
Service tel49 7322 1333-0
Subject to change.