Charge Profile
To set the correct profile the charger will need to have the appropriate
firmware loaded. If a Flex battery you will need to have firmware
FXPLUS-
VX.XX or if it’s a flooded battery or a Gel you need to have
LPM3-VX.XX in the charger. (make sure X.XX is the latest available
version if you are updating the charger)
To install firmware follow all steps below. If you have the appropriate
firmware installed already skip to step 8.
1. Insert flash drive in USB port with appropriate firmware
installed.
2. Enter password and go to USB menu.
3. Select Load Control Firmware.
4. Using the down arrow button, select firmware file from the list
on screen and hit Select button.
5. Firmware will automatically load at this point. Wait until it
finishes and splashes the Hawker startup screen before
removing the flash drive.
6. Reenter password.
7. Scroll down to Charge Profile Menu again and select Charge
Profile.
8. Select Ionic, Opportunity, or Gel. Or if the charger is loaded
with the Flex firmware the selectable profiles are Flex Bloc and
Flex Fast.
Ionic Charge Coefficient
This is only accessible through high level password
If you do have access to this setting make sure you understand what you are doing. If adjusted incorrectly it
could eventually damage a battery if not corrected.
This is the amount of overcharge built into the Ionic charge profile to compensate for losses in the battery
during recharge. (factory set to 15%, means total of 115%)
AGV_offset
For AGV applications, enter amount of Amps onboard electronics draw during charging. Allowed range is 0 to
20A. Entering 0 disables
erord
Constant Current Configuration
Caution: This mode is for use by trained service technicians only. For instructions on use see
charger service manual.
erord
Equalize Configuration
Equalize Days
Select day or days of the week to equalize the battery. You may select none, or as many days as you need.
Equalize Time
Equalize Time of Day: Sets the time of day the Equalize charge will start (24hr clock).
Equalize Delay: Sets the delay between the normal charge and the equalization charge from 0 to 24 hrs.