40-1/2"

1029mm

514mm

20-1/4"

13"

330mm

26"

660mm

19-1/4"

489mm

22"

559mm

279mm

11"

38-1/2"

978mm

A

A

SECTION A-A

MOUNTING DETAIL

Ø 5/8"

4X

Ø 16mm

HOLE THRU

46-1/2"

1181mm

83"

2108mm

12-7/8"
327mm

27" MIN

686mm

914mm

36"

2318mm

91-1/4"

FLOOR LINE

2184mm

86"

3-7/8"

98mm

90-1/8"

2289mm

2-1/4" (57mm)

RECESS FOR
WHEELCHAIR

ACCESS

1" IPS

SUPPLY

OPTIONAL

1" IPS

SUPPLY

3" DRAIN PIPE

4X 1/2" (12.7mm)

ANCHOR

BOLT ASSEMBLY

18"

DRAIN SHOWER 
3" INSIDE CAULK
(SUPPLIED)

(NOT SUPPLIED)

APPROVED:

DRAWN:

PART NUMBER

SCALE:

SHEET

OF

REVISION

DRAWING TYPE:

SIZE:   A

BY:

ECN NO.

PA

GE

DATE:

DATE:

ECN:

REVISED PER

CHK'D.:

         Haws Corporation - All Rights Reserved. HAWS   and other trademarks used in these materials are the exclusive property of Haws Corporation.

C

R

MODEL(S)

1455 KLEPPE LANE

SPARKS, NEVADA  89431

(775) 359-4712  FAX (775) 359-7424

E-MAIL:  HAWS@HAWSCO.COM
WEBSITE: WWW.HAWSCO.COM

THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION. CONTINUED PRODUCT IMPROVEMENTS
MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE.

RTM

8/10/01

13

0002080194.D

8605WC

EMERGENCY SHOWER

NA

1

1

MJ

08/07/18

FV

4 OF 

4

INSTALLATION

5334

2018

NG

36"

NOTES:

  1.  WHEN INSTALLING THIS UNIT, LOCAL , STATE, OR FEDERAL CODES SHOULD BE ADHERED TO FOR
       INSTALLATION DIMENSIONS (LOCATIONS), WASTE AND SUPPLY REQUIREMENTS OTHER THAN SHOWN.

  2.  TO COMPLY WITH ANSI Z358.1-2014 FOR EMERGENCY EYEWASH OR EYE/FACE WASH:
       EYEWASH OR EYE/FACE WASH SHALL BE POSITIONED SUCH THAT FLUSHING FLUID PATTERN IS NOT
       LESS THAN 33" (838mm), NO GREATER THAN 53" (1346mm) FROM SURFACE ON WHICH USER STANDS,
       AND 6.0" (153mm) MINIMUM FROM WALL OR NEAREST OBSTRUCTION.

  3   SHOWER SHALL BE POSITIONED SUCH THAT SHOWER HEAD IS NOT LESS THAN 82" (2083mm) OR
       GREATER THAN 96" (2438mm) FROM SURFACE ON WHICH USER STANDS.

  4.  SHOWER SPRAY PATTERN SHALL HAVE A MINIMUM DIAMETER OF 20" (508mm) AT 60" (1524mm) ABOVE
       SURFACE ON WHICH USER STANDS.  CENTER OF SPRAY PATTERN SHALL BE LOCATED AT LEAST 16" (406mm)
       FROM ANY OBSTRUCTION.

  5.   DIMENSIONS MAY VARY ±1/2". 

33"-53"

838mm-1346mm

FLOW PATTERN

Summary of Contents for 8605WC

Page 1: ...pon written authority from HAWS Sparks Nevada HAWS will not be liable for any damages caused by defective materials or poor workmanship except for replacements as provided above Buyer agrees that Haws has made no other warranties either expressed or implied in addition to those above stated except that of title with respect to any of the products or equipment sold hereunder and that HAWS shall not...

Page 2: ... is sufficient 3 a Probable clogging of flow control due to inadequate line flushing Unscrew eye face wash head and remove the four screws to disassemble the head Clean flow control and reassemble head See SP65 Installation Drawing for details 4 Insufficient water flow at the showerhead however eyewash is sufficient 4 Probable clogging of flow control inside showerhead Unscrew showerhead off of el...

Page 3: ...ghts Reserved HAWS and other trademarks used in these materials are the exclusive property of Haws Corporation C R MODEL S 1455 KLEPPE LANE SPARKS NEVADA 89431 775 359 4712 FAX 775 359 7424 E MAIL HAWS HAWSCO COM WEBSITE WWW HAWSCO COM ITEM DESCRIPTION THIS DOCUMENT IS TRUE AND CORRECT AT TIME OF PUBLICATION CONTINUED PRODUCT IMPROVEMENTS MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITH...

Page 4: ...LICATION CONTINUED PRODUCT IMPROVEMENTS MAKE SPECIFICATIONS AND MEASUREMENTS SUBJECT TO CHANGE WITHOUT NOTICE RTM 8 10 01 13 0002080194 D 8605WC EMERGENCY SHOWER NA 1 1 MJ 08 07 18 FV 4 OF 4 INSTALLATION 5334 2018 NG 36 NOTES 1 WHEN INSTALLING THIS UNIT LOCAL STATE OR FEDERAL CODES SHOULD BE ADHERED TO FOR INSTALLATION DIMENSIONS LOCATIONS WASTE AND SUPPLY REQUIREMENTS OTHER THAN SHOWN 2 TO COMPLY...

Reviews: