HAWS
®
P/N 0580001083 Rev.2 11/21
Model 8730
Page 9 of 20
PROGRAMMABLE CONTROLLER
The programable controller executes the following functions:
•
Deactivates the tank heater when the tank level is low.
•
Switches the alarm light from steady to flashing when eyewash/shower is in use.
•
Opens dry contacts for Common alarm when tank level is low.
•
Opens dry contact for In Use alarm when eyewash/shower is in use.
•
Changes interior light from green to white when doors are opened.
The following table lists the inputs and outputs available with the system. System may not contain all
components.
Input
Function
Output
Function
I-01
Horn Silence Button
Q-01
Tank Heater Contactor
I-02
Flow Switch or Proximity Switch
Q-02
Area/ Alarm Light
I-03
Proximity Switch
Q-03
Alarm Horn
I-04
Level Switch
Q-01 (Exp. Mod.)
Customer Contact (Common)
I-05
Door Proximity Switch
Q-02 (Exp. Mod.)
Customer Contact (In Use)
I-06
Tank Temperature Switch
Q-03 (Exp. Mod.)
Interior Light (Green/White)
NOTE: For model specific program, please contact Haws Services at 1-800-766-5612.