HAYWARD POOL PRODUCTS, INC.

Indoor Vent Installation Instructions

Positive Pressure (Horizontal) Venting Kits

for Universal H-Series (Forced-Draft) Heaters

IMPORTANT NOTES:

1. This kit is intended to be used only with Hayward Universal H-Series (forced-draft) gas heater models built after Apr 30, 

2008, serial # 21130804103872001.  These heaters may be identified by inspection of the heater rating plate.  The model 

number should match one of those listed in Table 1, and on models H250FD, H350FD, and H400FD, the serial number 

should indicate a manufacture date of Apr 2008 or later.  If the manufacture date is Apr 2008, the serial number must be 

greater than 03872.  Table 2 may be used to extract the date of heater manufacture based on heater serial number.  If it is 

necessary to install this kit in a heater built before the above listed manufacture date, a separate kit is needed to update 

your  heater.    Install  kit  FDXLRGK1250,  FDXLRGK1350,  or  FDXLRGK1400  (depending  on  your  heater  model)  before 

installing the indoor vent kit.  All models H150FD, H200FD, and H300FD are compatible with this kit.

 

2. This instruction sheet is intended for only the heater service parts kits listed in Table 1.

 

3.  This  kit  enables  indoor  installations  where  the  exhaust  vent  pipe  termination  is  either  horizontal  or  vertical,  and  the 

stainless  steel  vent  pipe  and  vent  terminals  must  be  special-ordered  from  Heatfab.    This  kit  does  not  allow  the  use  of 

galvanized, non-sealed vent pipe.  Please refer to the instructions for kit part numbers UHXNEGVT1150, UHXNEGVT1200, 

UHXNEGVT1250, UHXNEGVT1300, UHXNEGVT1350, and UHXNEGVT1400 for other indoor venting applications.    

1301666501 rev B

Page 1 of 10

TABLE 1

TABLE 2

Serial Number Format

Year (y)

21130ymm1xxxxx001

7=2007                     

8=2008                     

9=2009                     

0=2010

01=Jan                    

02=Feb                        

03=Mar                             

04=Apr                      

05=May                    

06=Jun

07=Jul                             

08=Aug                         

09=Sep                         

10=Oct                              

11=Nov                         

12=Dec

Month (mm)

Note:  "xxxxx" indicates the serial number.

WARNING

Failure  to  comply  with  the  installation  instructions  in  this  instruction  sheet  may  result  in 

equipment  damage,  fire,  asphyxiation,  or  carbon  monoxide  poisoning.    Exposure  to 

products of incomplete combustion (carbon monoxide) can cause cancer, birth defects, or other reproductive harm.

4. Installation of this kit should be conducted only by a qualified technician, specifically trained and experienced in the 

installation of this type of heating equipment.  Some states or provinces require that installers be licensed.  If this is the 

case in the state or province where the heater is located, the contractor must be properly licensed.

 

5.  This kit should be installed in accordance with all local and state codes.  The installation of this kit must conform to 

the latest edition of the National Fuel Gas Code (ANSI Z223.1/NFPA 54), the vent manufacturer's (Heatfab) installation 

instructions,  and  with  the  requirements  of  the  local  authority  having  jurisdiction.    Design  certification  of  this  kit  is  in 

compliance  with ANSI  Z21.56/CSA  4.7.    For  Canadian  installations,  this  kit  is  to  be  installed  in  accordance  with  the 

standard CAN/CGA B149.1 - Installation Codes for Gas Burning Appliances and Equipment and/or local codes.

EN

G

LIS

H

Part Number

Description

For Use With                        

Heater Models

Vent Pipe Limitations

Vent Pipe Material

Vent Termination 

Requirement

UHXPOSHZ1150

H150FD

UHXPOSHZ1200

H200FD

UHXPOSHZ1250

H250FD

UHXPOSHZ1300

H300FD

UHXPOSHZ1350

H350FD

UHXPOSHZ1400

H400FD

Indoor Vent Adapter 

Kit, Positive Pressure, 

Horizontal or Vertical 

Venting Applications

50 ft max with 1 elbow,                              

40 ft max with 2 elbows, or                            

30 ft max with 3 elbows                          

(horizontal or vertical)

Single or Double Wall 

Stainless Steel Sealed 

Vent Pipe

Horizontal or Vertical, 

Termination Immediately 

Outside Wall of 

House/Building

Summary of Contents for UHXPOSHZ1150

Page 1: ...9 2009 0 2010 01 Jan 02 Feb 03 Mar 04 Apr 05 May 06 Jun 07 Jul 08 Aug 09 Sep 10 Oct 11 Nov 12 Dec Month mm Note xxxxx indicates the serial number WARNING Failure to comply with the installation instructions in this instruction sheet may result in equipment damage fire asphyxiation or carbon monoxide poisoning Exposure to products of incomplete combustion carbon monoxide can cause cancer birth defe...

Page 2: ...ach opening shall have a minimum free area of 1 square inch per 4 000 btu hr of total input rating of all equipment in the enclosure See Table 5 1 When communicating with the outdoors through horizontal ducts each opening shall have a minimum free area of 1 square inch per 2 000 btu hr of total input rating of all equipment in the enclosure See Table 5 2 When ducts are used they shall be of the sa...

Page 3: ... 200 200 250 000 250 250 300 000 300 300 350 000 350 350 400 000 400 400 150 000 75 75 200 000 100 100 250 000 125 125 300 000 150 150 350 000 175 175 400 000 200 200 150 000 37 5 37 5 200 000 50 50 250 000 62 5 62 5 300 000 75 75 350 000 87 5 87 5 400 000 100 100 150 000 600 600 200 000 800 800 250 000 1000 1000 300 000 1200 1200 350 000 1400 1400 400 000 1600 1600 1 sq in per 1 000 btu hr paragr...

Page 4: ...witch See Figure 5 If you are refitting a heater with an FDXLRGK1xxx kit you will need to splice into the wire harness red wire which attaches to the water pressure switch The vent pressure switch should be in series with the water pressure switch 13 If installing the kit on models H250FDN H250FDP or H400FDP you must also replace the existing blower air inlet restrictor with the new one included i...

Page 5: ... rev B Page 5 of 10 FIGURE 2 FIGURE 3 FIGURE 4 FIGURE 5 FIGURE 6 Heat Barrier Rain Guard Vent Adapter Flue Cover Vent Pressure Switch Blower Pressure Tap Blower Air Inlet Plate Vent Pressure Switch Tubing ENGLISH ...

Page 6: ... mm Remarque xxxxx indique le numéro de série en fonction du numéro de série du réchauffeur S il est nécessaire d installer ce kit dans un réchauffeur construit avant la date de fabrication mentionnée ci dessus un kit séparé est requis pour mettre à jour le réchauffeur Installer le kit FDXLRGK1250 FDXLRGK1350 ou FDXLRGK1400 selon le modèle du réchauffeur avant d installer le kit d évent d intérieu...

Page 7: ...e 1 pied carré par 4000 BTU par heure d alimentation nominale totale de tous les équipements de l enceinte Voir le tableau 5 1 Lorsqu elle communique avec l extérieur par l intermédiaire de conduits horizontaux chaque ouverture doit avoir une surface libre minimum de 1 pied carré par 2000 BTU par heure d alimentation nominale totale de tous les équipements de l enceinte Voir le tableau 5 2 Lorsque...

Page 8: ...rface libre requise pour l air de ventilation po 2 150 000 150 150 200 000 200 200 250 000 250 250 300 000 300 300 350 000 350 350 400 000 400 400 150 000 75 75 200 000 100 100 250 000 125 125 300 000 150 150 350 000 175 175 400 000 200 200 150 000 37 5 37 5 200 000 50 50 250 000 62 5 62 5 300 000 75 75 350 000 87 5 87 5 400 000 100 100 150 000 600 600 200 000 800 800 250 000 1000 1000 300 000 120...

Page 9: ...ceau de câble du réchauffeur et attacher les 2 fils au pressostat d évent Voir la figure 5 Si on modernise un réchauffeur avec un kit FDXLRGK1xxx il faut faire une épissure dans le fil rouge du faisceau de câble qui est attaché au pressostat d eau Le pressostat d évent doit être placé en série avec le pressostat d eau 13 Si on installe le kit sur les modèles H250FDN H250FDP ou H400FDP il faut auss...

Page 10: ...GURE 3 FIGURE 4 FIGURE 5 FIGURE 6 FRANÇAIS Adaptateur d évent Barrière thermique Protection parapluie Couvercle de conduit Pressostat d évent Raccord de pression de soufflante Plaque d admission d air de soufflante Tubage de pressostat d évent ...

Reviews: