background image

12

Super Chlorinate

24 hours

Adjust Superchlorination period (1 - 96 hours)
Move to previous/next menu item

If external chlorination is enabled.

 For larger pools or when you have an unusually high bather load,

a large amount of rain, a cloudy water condition, or any other condition that requires a large amount

of chlorine to be introduced to the pool, adjust the Superchlorination period to provide adequate

chlorination. Smaller pools require  less hours of Superchlorination.

Group Function

The OnCommand offers the ability to assign one Group function to a particular button.  Instead of the button

controlling one particular function, the button can be programmed to initiate a sequence of commands that are

programmed in the Configuration Menu.  For example, instead of the Lights button turning on and off the pool light

only, the button can be programmed to turn on the pool light, turn on the bug light, turn off the pool cleaner, and turn

on the music all at the same time.  This convenient feature can be assigned to either one of the Aux buttons, the

Lights button or the Valve 3 automated function.

Before assigning and configuring all the desired functions and their control parameters within the group, the group

itself must be configured.  The options for controlling groups are Manual On/Off, Countdown Timer, and Timeclock.

The group will turn on and off based on this selection.

When setting up a Group function in the Configuration Menu, the first menu allows you to select the control

parameter (how the group is activated and de-activated) and the second menu allows you to select which functions

are to be controlled in the group.

A table of functions and their corresponding control parameters are listed below.

Note that all functions in the table may not be offered.  The available functions are dependent on how the OnCommand

is configured.  Also, under some circumstances, functions will be displayed but can’t be changed. Note that the

function whose menu you are in, will not be displayed as an option and will automatically turn on when the group is

activated. For example, if programming a Group function under the Lights menu, the Lights function will not be

offered as an option and the Lights function will automatically turn on with the group.

The available control parameters vary with each function.  All functions offer “Unaffected”, which should be

selected if you do not wish to control that particular function within the group.  All other parameters will depend on

the particular function selected.

15

Filter Config.

+ to view/change

Filter Pump 

1 Speed

Freeze Protect 

Enabled

Lowest Speed

10%

Highest Speed

100%

Push to access pump options

Rotates between 1-speed (default), 2-speed and variable speed options

Toggle between Enabled (default) and Disabled Freeze Protection 

Adjust the lowest speed desired for variable speed operation

Adjust the highest speed desired for variable speed operation

Move to next menu item

Move to previous/next configuration menu

Move to next menu item or previous/next configuration menu

Move to next menu item

Move to next menu item

if “Variable Speed” is selected

if “Variable Speed” is selected

Freeze Temp

38ºF

Freeze Protect

High Speed

Adjust the desired freeze protection temperature (33ºF - 42ºF)

Toggle between high speed (default) and low speed

Move to previous/next configuration menu

Move to next menu item

if “Freeze Protect” is enabled

if “Freeze Protect” is enabled
and “1-speed Filter” is not selected

Filter Pump

For 2-speed pumps:  When a 2-speed pump is configured, one of  the AUX relays must also be

configured to control the low speed motor winding on the pump.  Refer to the appropriate sections in

the Installation manual for specific information regarding the control logic for 2-speed and variable

speed pump operation.

For the Hayward Tristar variable speed pump:  The Filter relay is used to supply input power to the

VSC pump control.  The relay will be on when the filter pump output is on.  When the filter pump

output is off, the relay will be off.  On , off and speed is controlled by commands sent to the pump.

Lowest Speed

This is the lowest speed that the variable speed pump is allowed to run at. It is used as the lower limit

in the Low Speed Settings Menu. Set lowest speed from 10% (default) to 50%.

Highest Speed

This is the highest speed that the variable speed pump is allowed to run at. It is used as the upper limit

in the High Speed Settings Menu.  Also, this is the speed that the pump will run at during the first 3

minutes of operation anytime the pump has been off for more than 30 seconds. Set highest speed from

20% to 100% (default).

Freeze Protection

Freeze protection is used to protect the pool and plumbed equipment against freeze damage.  If freeze

protection is enabled and the AIR temperature sensor falls below the freeze threshold (see below), the

OnCommand will turn on the filter pump to circulate the water. If “Pool and Spa” is selected in the Pool/

Spa sub-menu, the valves will also alternate between the pool and spa every 30 minutes and the filter

pump will turn off while the valves are turning.  The chlorinator will not operate if freeze protection is

the only reason the pump is running.

Freeze Protection Speed

This menu only appears if freeze protection is enabled and the pump is configured for 2-speed or

variable speed pump operation. This is the speed that the pump will run at during freeze protection

operation. Select high (default) or low speed operation.

Freeze Protection Temperature

Select the temperature to be used for freeze protection.  Temperature is adjustable from 33ºF  -  42ºF

(1ºC - 6ºC).  38ºF (3ºC) is default. This threshold will be used for all outputs that have freeze protection

enabled.

        

Pool/Spa

Unaffected, Pool only, Spa only, or Spillover

Pool Filter 

Unaffected, Off, On, High speed, or Low speed

or 

Function 

        Control Parameter

Lights 

Unaffected, Off, or On

Lights

Unaffected, Off, On, 100%, 80%, 60%, 40%, or 20%

Aux1&2 Unaffected, 

Off, 

On

Aux1&2 

Unaffected, Off, On, 100%, 80%, 60%, 40%, or 20%

Valve3

Unaffected, Off, or On

Spa Htr Set

Unaffected, Off, 65º-104ºF

Pool Htr Set

Unaffected, Off, 65º-104ºF

Spa Solar Set

Unaffected, Off, 65º-104ºF

Pool Solar Set

Unaffected, Off, 65º-104ºF 

SuperChlr

Unaffected, Off, On

Spa High

Unaffected, 20% to Highest speed

Spa Low

Unaffected, Lowest speed to 50%

Pool High

Unaffected, 20% to Highest speed

Pool Low

Unaffected, Lowest speed to 50%

(standard relay)

(dimmer relay)

(s

(dimmer relay)

 

 

tandard relay)

Summary of Contents for ONCOM

Page 1: ...Hayward OnCommand Automation Operation Manual ONCOM ONCOM ACT ONCOM RC ONCOM ACT RC www haywardnet com for models ...

Page 2: ...arked Earth Ground is located inside the wiring compartment To reduce the risk of electric shock this terminal must be connected to the grounding means provided in the electric supply service panel with a continuous copper wire equivalent in size to the circuit conductors supplying the equipment A wire connector is provided on this unit to connect a minimum 8AWG 8 4 mm solid copper conductor betwe...

Page 3: ...s Menu 9 Configuration Menu 13 Quick How To Operate the Spa Manually 22 Guide Operate the Spa Automatically 22 Set the Heater Temperature 23 Set the Chlorinator Output 23 Start Stop Superchlorination 23 Program a Timeclock 23 Program a CountdownTimer 23 Enter Exit Service Mode 24 Troubleshooting Service Mode 24 Diagnostic Information Check System Indicator 24 Diagnostic Menu 25 Salt Level 25 Water...

Page 4: ...ge 120 240V pieces of equipment up to 3 automatic valve actuators andaconventionalandsolarheater Bothmanualandautomatic programmed operationareavailable Allofthecontrolfunctionsareprogrammedattheunit sdisplay keypad AlthoughtheOnCommandhasnobuilt inchlorinatorfeature itcancontrolanexternalGoldlineAquaRiteorHaywardSwimpurechlorinator Water Air Solar 120 VAC Power Filter Pump Lights Aux 1 Aux 2 Pool...

Page 5: ... currently off press the FILTER button to turn on the pump Pressing theFILTERbuttonagainwillturnoffthepump However ifthereisaheaterinthesystem anditisoperating and the HeaterCooldown featureisenabled ConfigurationMenu then whenyoupresstheFILTERbuttontoturn offthefilter onlytheheaterwillturnoff theFilterLEDwillflashandthedisplaywillindicate HeaterCooldown Atthispointthefilterpumpwillautomaticallytu...

Page 6: ...eration rightLEDillumi nated PressingthePOOL SPAbuttonagainwillswitchbacktopool only Notethatthefilterpumpwillturnoff whilethepool spavalvesareturning Pool and Spa systems with spa spillover In pool only mode the left LED next to the POOL SPA button is illuminated PressingthePOOL SPAbuttonwillswitchtheOnCommandtospa onlyoperation rightLEDillumi nated Pressing the POOL SPAbutton again will switch t...

Page 7: ...ntheselectedmenu Multiplepushes ofthebuttonwillrotatethroughallmenuitemsandreturntothestartingpoint Onlymenu itemsthatareapplicabletoyourpoolwillappear Example ifyoudon thaveaspa then no spa related menu items will appear 3 Onceamenuitemhasbeenselectedabove thecurrentsetting selectionwillappear flashing on the display Use the and or keys to change this selection Sometimes and willadjustavalueupord...

Page 8: ...us system manual off check system error filter speed settings menu spa heater temperature pool heater temperature spa solar temperature pool solar temperature superchlorinate spa chlorinator setting pool chlorinator setting spa high low speed pool high low speed day and time backlit display light beeper teach wireless remote wireless channel timers menu pool filter pump spa lights aux1 aux2 valve3...

Page 9: ...ntional heater will only operate when solar heat is NOT available Pool Heater Off Adjust the desired pool temperature Off 65 F 66 F 103 F 104 F Off Move to previous next menu item The pool heater setting will only appear if the system has been setup for pool only or pool and spa operation and the heater control is enabled The heater will turn on whenever the pool spa valves are in the pool only or...

Page 10: ...re then the chlorinator will not operate during this time Pool Chlorinator 60 Adjust the desired chlorinator output for pool 0 1 2 3 9 10 15 20 95 100 Move to previous next menu item This setting will appear only if the system has been setup for external chlorinator and pool only or pool and spa It will determine the chlorinator output when the system is operating in pool only or spa spillover mod...

Page 11: ...er than 7 days then the time may have to be reset Display Light On for 60 sec Toggle between Always On and On for 60 sec Move to previous next menu item This function controls the backlight on the display If the 60 seconds option is selected then the backlight will automatically turn off 60 seconds after the last key is pressed and will stay off until next time a key is pressed Note that the Displ...

Page 12: ...next menu item This setting changes the channel to be used by the wireless base station and remote s If the channel is changed and confirmed all of the wireless remotes will have to be retaught This menu will only appear if a wireless base station is connected to the OnCommand Timers Menu TheTimersMenuallowsyoutosetalltimeclockandcountdowntimerswhichcontroltheautomaticoperationof your pool spa sys...

Page 13: ...ime period These include manual operation spa operation or heating operation Refer to page 9 for general notes regarding timeclock programming This menu is only available if the system has been setup for pool and spa Only one timeclock is available for Spa operation During the programmed spa time the OnCommand will turn on the filter pump and move the pool spa valves into the spa only position The...

Page 14: ...anually turn off the relay at an earlier time by pressing the AUX1 button This menu will appear only if Valve3 is configured for timeclock The valve will rotate on and off at the designated times There is no manual override If the Valve3 relay is on during the programmed off time it may be because of freeze protection Set Day and Time Wednesday 10 37P Adjust time setting Move between start and sto...

Page 15: ...howthegroupisactivatedandde activated andthesecondmenuallowsyoutoselectwhichfunctions are to be controlled in the group Atable of functions and their corresponding control parameters are listed below Notethatallfunctionsinthetablemaynotbeoffered TheavailablefunctionsaredependentonhowtheOnCommand is configured Also under some circumstances functions will be displayed but can t be changed Note that ...

Page 16: ...runningagroupcommand Thisallows the pump s to be set to a higher or lower speed than normal while the group is activated When the group stops thespeedwillreturntoitsnormalsetting Changing the speed setting while the group is running will make the group release the alternate speed setting and revert back to the normal speed setting Any changes that are made at that point will affect the normal spee...

Page 17: ...ons It is programmed in increments of 5 minutes from Manual On Off 0 minutes to 21 00 21 hours The filter is forced on during this time period Spa Spillover When spa spillover is Enabled and Pool and Spa the homeowner will be able to rotate through Pool Only both suction and return valves switched to pool Spa Only both suction and return valves switched to spa and Spillover suction valve switched ...

Page 18: ...ill be off On off and speed is controlled by commands sent to the pump Lowest Speed This is the lowest speed that the variable speed pump is allowed to run at It is used as the lower limit in the Low Speed Settings Menu Set lowest speed from 10 default to 50 Highest Speed This is the highest speed that the variable speed pump is allowed to run at It is used as the upper limit in the High Speed Set...

Page 19: ...setting will be used Heater Cooldown This feature ensures that the heater cools down before water circulation is stopped When enabled the OnCommand will continue to run the filter pump for 5 minutes after the heater turns off During this period the filter pump LED will flash and also a Heater Cooldown X XX remaining message will scroll on the display When the filter pump is running and the heater ...

Page 20: ...l turn on when the water temperature is less than the desired temperature settingAND the solar sensor is hotter than the water The desired temperature is in the Settings Menu If applicable the homeowner will be prompted to enter separate pool and spa desired temperature settings Depending on the position of the pool spa suction valve the proper temperature setting will be used Solar Extend If Enab...

Page 21: ...e function of each option is shown below Manual On Off default the lights relay will alternate between turning on and off when the LIGHTS button is pressed There is no automatic control logic Countdown Timer the lights relay will turn on when the LIGHTS button is pressed The lights relay will turn off automatically after a programmed time see Timers Menu in Operation Manual The LIGHTS button can a...

Page 22: ...elected in the Settings Menu for normal filter operation If an alternate speed is desired when the Lights output is on push or and select from Lowest to Highest in 5 increments NOTE The configuration parameters for the Aux2 output are the same as shown below for Aux1 Aux1 Pump Spd Settings Menu Select between Settings Menu default and the desired pump speed only if filter pump is set to variable a...

Page 23: ...e level is saved for the next time the aux1 output is turned from off to on Aux1 Interlock If Enabled this feature will override the function Manual On Off Countdown Timer Timeclock selected above and turn the aux1 off when filter pump is off first 3 minutes of filter pump operation allows the pump to prime and get water flowing when the pool spa suction return valves are in any position other tha...

Page 24: ...3 Lights the valve operates whenever the Lights relay is on Valve3 Aux1 the valve operates whenever the Aux1 relay is on Valve3 Aux2 the valve operates whenever the Aux2 relay is on Valve3 Interlock If Enabled this feature will override the function timeclock or in floor cleaner selected above and turn the valve off when the filter pump is off first 3 minutes of filter pump operation allows the pu...

Page 25: ...onfig to Default Press Are you sure to proceed Config reset Confirmed Initiate reset of all configuration parameters Reset all configuration parameters Move to previous next configuration menu config not reset Move to previous next menu config not reset Move to previous next configuration menu Use this function to erase all previous system configuration and reset all configuration parameters back ...

Page 26: ...etting If the valves are in the spa only position then the chlorinator will operate according to the spa setting The actual amount of chlorine introduced into the pool spa is determined by this output setting the amount of time the filter pump is running the water temperature and the amount of salt in the water Also see Start Stop Superchlorination below Start Stop Superchlorination for external c...

Page 27: ...ormationregardingsystemoperation Whilebothofthefeaturesareprimarilyintendedfortheuseoftheprofessionalservicetechnician theirfunctionis fullyexplainedbelow Service Mode ThemainunitkeypadhasaSERVICEbuttonthatisusedprimarilyduringservicingofthepoolequipment Ifyouwanttocompletelydisabletheautomaticoperationandoperatethesystemmanually youcanputthesystem intoServiceorService Timedmodebypressingthe Servi...

Page 28: ...lorination is used and requires a Aqua Rite or Swimpure chlorine generator For the chlorinator to be operating several other things must be happening the filter pump must be running the flow switch must be detecting flow the chlorinator setting must be set greater than 0 the water temperature at the cell must be between 50ºF and 140ºF and the salt level must be within the operating range If any of...

Page 29: ...em Move to previous next menu item Move to previous next menu item Available displays depend on configuration If you call the Hayward Goldline Technical Service Dept for assistance they may ask for the software revisions of both the main unit and each of the display keypads or other devices that are attached to the system Note that it is possible that different display keypads have different softw...

Page 30: ...27 ...

Page 31: ...process of installation 2 Damageresultingfromimproperinstallationincludinginstallationonpoolslargerthantheproductrating 3 Problemsresultingfromfailuretoinstall operateormaintaintheproduct s inaccordancewiththerecommen dationscontainedintheownersmanual s 4 Problemsresultingfromfailuretomaintainpoolwaterchemistryinaccordancewiththerecommendationsinthe ownersmanual s 5 Problemsresultingfromtampering ...

Page 32: ...092442A Copyright 2009 Hayward 620 Division St Elizabeth NJ 07207 ...

Reviews: