Internal calculation channels
196
A4354-2.2
HBM: public
PMX
Default
Inversion hold: no
Re-triggerable: yes
Hold delay: 0.0 ms
Exception handling
If the input is marked as invalid (Invalid Bit), then the output is
also marked as invalid.
The hold function is still implemented and output
.
13.2.2.7 Mean values (arithmetic, RMS)
Function
Provides the mean value of a signal over time. The period
is determined by trigger events.
The output is not updated continuously, it is rather updated
at trigger events only.
The trigger event is determined by either
1.When reaching a given number of acquired samples
2.The control input becomes greater than the threshold
3.The control input becomes smaller than the threshold
4.Rising edge at the digital input
5.Falling edge at the digital input
Inputs
in0: The signal to be averaged
control: The control input that is compared to the threshold
input. Only relevant with trigger events 2, 3.
threshold: The threshold input. Only relevant with trigger
events 2, 3. trigger input: The digital trigger input. Only
relevant with trigger events 4, 5
Outputs
mean: Either the arithmetic or the quadratic mean count:
The number of samples that have been averaged
Summary of Contents for PX401
Page 1: ...Operating Manual English PMX...
Page 104: ...Electrical connections PMX 104 A4354 2 2 HBM public PMX...
Page 141: ...Startup PMX A4354 2 2 HBM public 141 Network settings...
Page 239: ...Internal calculation channels PMX A4354 2 2 HBM public 239...
Page 241: ...Internal calculation channels PMX A4354 2 2 HBM public 241...
Page 246: ...Internal calculation channels 246 A4354 2 2 HBM public PMX...
Page 264: ...Internal calculation channels 264 A4354 2 2 HBM public PMX...
Page 272: ...Parameter sets measurement programs 272 A4354 2 2 HBM public PMX...
Page 295: ...Communication with a control system PMX A4354 2 2 HBM public 295...
Page 297: ...Communication with a control system PMX A4354 2 2 HBM public 297...
Page 300: ...Communication with a control system 300 A4354 2 2 HBM public PMX...
Page 376: ...CODESYS V3 Soft PLC WGX001 only 376 A4354 2 2 HBM public PMX...
Page 378: ...CODESYS V3 Soft PLC WGX001 only 378 A4354 2 2 HBM public PMX...
Page 381: ...CODESYS V3 Soft PLC WGX001 only PMX A4354 2 2 HBM public 381...
Page 392: ...CODESYS V3 Soft PLC WGX001 only 392 A4354 2 2 HBM public PMX Dialog Updating the PMX device...
Page 489: ...Object directory PMX A4354 2 2 HBM public 489...
Page 523: ...Diagnosis and maintenance PMX A4354 2 2 HBM public 523 Network settings...