Supervisormode
WTX110
A4774-1.0
HBM: public
137
Meaning of parameter P1
A correction factor of 1 means that the difference between the actual weight
and target weight (either too much or not enough material added) will be
included in the next cut-off point at a rate of 100%. With a correction factor of
0.5, only 50% of the difference is included in the calculation.
10.2.9
Re-dosing
(Re-Dosing
)
If the previously measured actual value is below the lower tolerance limit,
re-dosing is carried out. When optimization is active (parameter P1 > 0), the
result of a re-dosing operation does not change the cut-off points.
Re-dosing occurs with fine flow.
Menu
Key
Function/Secondary selection
Re-dosing
Off
Re-dosing turned off
1
Re-dose if fine flow cut-off point < current
measured value < lower tolerance limit
When to re-dose?
At the start of the batching process
2
Re-dose if previously measured actual weight
< lower tolerance limit
When to re-dose
After checkweighing
3
Re-dose if
fine flow cut-off point < current measured
value < lower tolerance limit
When to re-dose?
At the start of the batching process
OR
Re-dose if previously measured actual weight
< lower tolerance limit
When to re-dose?
After checkweighing