NoMax 900 Functions
18) OPEN TEMP -
The temperature setting threshold for opening the capacitor
bank. The minimum value is 5 degrees. The maximum value is 125 degrees
(The NoMAX
®
900 prevents the OPEN TEMP setting from being closer than 5
degrees to the CLOSE TEMP setting). The control will issue an open command
to the capacitor bank based upon the Winter/Summer schedule as follows:
Winter Schedule
(defined by OPEN
TEMP greater than
CLOSE TEMP setting)
– The capacitor bank
will Open when the
temperature rises
above the
OPEN TEMP setting.
Summer Schedule
(defined by CLOSE
TEMP greater than
OPEN TEMP setting) –
The capacitor bank
will Open when
temperature drops
below the OPEN
TEMP setting.
19) Close Temp -
The
temperature setting
threshold for closing the capacitor bank. The minimum value is 5 degrees.
The maximum value is 125 degrees (The NoMAX
®
900T prevents the CLOSE
TEMP setting from being closer than 5 degrees to the OPEN TEMP setting).
The control will issue a close command to the capacitor bank based upon the
Winter / Summer schedule as follows:
Winter Schedule (defined by OPEN TEMP greater than CLOSE TEMP setting) –
The capacitor bank will Close when the temperature drops below the
CLOSE TEMP setting.
Summer Schedule (defined by CLOSE TEMP greater than OPEN TEMP
setting) – The capacitor bank will Close when the temperature rises above
the CLOSE TEMP setting.