10
DISPLAY MESSAGES
The following describes the messages the user can expect to see on the
Liquid Crystal Display.
• “Total Ops xxxxxx”
The total number of Close operations since installation
• “24Hr Auto Ops xx”
The number of Automatic Close operations today
• “Close Inh. xx:xx”
The remaining time Close Inhibit is active
• “Auto In xx:xx”
The remaining time a Manual Open or Manual Close
maintenance operation is active before the control
returns to automatic operation
• “Opening In xx:xx”
The remaining time until an AUTOMATIC Open Operation occurs
• “Closing In xx:xx”
The remaining time until an AUTOMATIC Close Operation occurs
• “Bank Switching!”
Indicates an IMMEDIATE operation is in progress
• “Bank Volts x.x”
The Delta Volts measurement
• “Line Volts xxx.x”
The Line Volts measurement
• “Fahrxxx”
The Temperature measurement (positive) (NoMax
®
900 only)
• “Fahrenheit -xxx”
The Temperature measurement (negative) (NoMax
®
900 only)
• “Time xx:xx:xx”
The present control clock time
• “Date xx/xx/xx”
The present control clock date
• “Sunday”
(or other day)
The present control clock day
Note:
All messages which include an equality sign “=” indicates the user is
accessing a set point.
• “Seconds = xxx”
The OPERATION TIME DELAY setting
• “Max. Ops./24 Hr. = xx”
The MAX OPS/DAY setting
• “Open V = xxx.x”
The OPEN VOLTS setting
• “Close V = xxx.x”
The CLOSE VOLTS setting
• “Close Temp. = xxx”
The CLOSE TEMP setting (NoMax
®
900 only)
• “Open Temp. = xxx”
The OPEN TEMP setting (NoMax
®
900 only)
• “Mode = Time”
The CONTROL MODE is Time only
• “Mode = Time/Temp”
The CONTROL MODE is Time with Temperature Override
(NoMax
®
900 only)
• “Mode = Time/Volt”
The CONTROL MODE is Time with Voltage Override
(NoMax
®
900 and 950)
• “Mode = Voltage”
The CONTROL MODE is Voltage Only
• “Mode = Temp”
The CONTROL MODE is Temperature Only
(NoMax
®
900 only)
• “Mode = Temp/Volt”
The CONTROL MODE is Temperature with
Voltage Override (NoMax
®
900 and 950)
• “Time = xx:xx:xx”
The control clock time setting
• “Year = xxxx”
The control clock year setting
• “Month = xx”
The control clock month setting
• “Day = xx”
The control clock day setting
• “Close = xx:xx”
The CLOSE TIME setting
• “Open = xx:xx”
The OPEN TIME setting
• “DST = xxxxxxxx”
Daylight Savings Time Enabled/Disabled
Gridco, Inc. v. Varentec, Inc. IPR2017-01135