6 Using the heating system – TIME menu
94
HDG Compact 99 - 200 - Version 1 - en
©
HDG Bavaria GmbH 07/2008
S
ETTING
UNDERPRESSURE
CONTROL
VALUES
In this menu, the settings for fan speed with the HDG cyclone dust
extractor and the underpressure value for the underpressure control
can be defined.
✎
See “Procedure” in this section.
6.8 TIME menu
In this menu you can view and set all time parameters relating to ig-
nition, de-ashing, cleaning and delivery systems. All target values can
be modified. The actual values displayed indicate the current status.
P
ROCEDURE
1.
Press the
F3
key under the standard display screen.
✓
You are in the
Time
menu.
2.
Scroll with the
F1
or
F2
key to the previous or next submenu.
✓
The first resettable parameter is shown in black.
3.
Enter the desired value using the numerical keypad.
4.
Confirm each change with the
Enter
key.
✓
The desired parameter is set.
5.
Scroll with the
Up
or
Down
key to the next submenu.
✓
The next resettable parameter is shown in black.
6.
Repeat steps 3 to 5 for additional parameters.
7.
Press the
F6
key under the
END
command to exit the submenu.
✓
The standard display is restored.
PID pressure control fan
6-07
MAX : 100%
P_Min
:
-10pa
KP:
20
MIN :
20%
P_Max
:
-50pa
TN:
40
ACT : 90%
P_Set:
-20pa
TV:
0
Fact.: 73%
P_Ist :
-25pa
KP_:
30.0
END
The standard setting is 100% for
MAX
and 20% for
MIN
.