5 Commissioning the system – Procedure
95
F
ILLING
THE
FUEL
BUNKER
1.
Before filling the fuel bunker, check the rotational direction, the
intermediate base, the leaf springs and the dosing plate of the de-
livery system.
2.
Fill the fuel bunker.
✎
See the chapter entitled “6 Using the heating system”, section
“6.8 Filling the fuel bunker”.
✓
The fuel bunker is filled.
C
HECKING
AND
ADAPTING
THE
BASIC
PARAMETER
SETTINGS
1.
Using the
Mode
button, switch to
OFF
mode.
2.
Press the
Enter
button.
✓
The mode has been changed.
✓
The
OFF
symbol will be illuminated on the control unit.
3.
Simultaneously press the
Plus
and
Enter
buttons.
✓
The display changes to the service level.
4.
Check the basic settings for the following parameter groups:
1 - General
2 - Boiler
3 - Ignition
4 - Control
5 - Return
6 - Cleaning
7 - Delivery system
and the basic settings of the additional hydraulic system-dependent
parameter groups
8-Hydraulic system
to
21-Heating
pump, Combi
.
The fuel bunker may only be filled if the actuators and sensors have
been tested.
Warning!
Damage to delivery system during filling
If the heating system is not switched on during filling of the fuel
bunker, the overload protection of the delivery system could be
triggered when the heating system is switched on after the filling.
When filling the fuel bunker for the first time, activate the delivery
system by switching in manual operation.
Enter
Enter
Summary of Contents for Compact 25
Page 1: ...hdg bavaria com HDG Compact 25 80 Operation Manual ...
Page 2: ......
Page 186: ...12 Index 186 HDG Compact 25 35 Version 2 de HDG Bavaria GmbH Oktober 2007 ...
Page 187: ......