5 Commissioning the system – Procedure
44
A
DJUSTING
THE
AIR
DAMPER
1.
Open the ash door (3).
2.
Release the four retaining screws (1 + 5) with a flat-bladed
screwdriver.
3.
Adjust the upper and lower air damper (4 + 2) on the upright grate
flap.
4.
Retighten the retaining screws (1 + 5).
5.
Close the boiler in the reverse order.
✓
The air damper is adjusted.
G
RATE
LIFTER
The position of the grate lifter can be changed in order to correct the
gas quantity during degassing and thus avoid pulsating (sudden
igniting due to lack of oxygen) or insufficient flue gas temperatures.
This is required in the case of larger deviations from the
recommended fuel or deviations from the required temperatures in
order to ensure safe operation of the log wood boiler.
Figure 5/2 - Adjusting the air damper
1
2
3
5
4
With the log wood boiler HDG Euro 30/40/45/50, the grate lifting
bar is delivered separately. The flat grate elements are in the lowest
position at the time of delivery.