background image

                                                                                                                                  User Manual 

                                              SB-DN-1ip     

                                                                                             
 

 

 

HDL typical gateway – User Manual                                                                                                                       
15 

 

5.  Or  you  can  just  click  the  Apply  button;  this  pop  up  window  will  exit  automatically  if  it 

communicates  with  remote  HDL-BUS  system  successfully,  now  you  can  get  start  to 

program the HDL-BUS system. 

 

6. Get into the SB-DN-1IP, you can check the Access Log and connection status. 

 

 

  “Interval(1-255)m ” 

It is the parameter that decides how long the SB-DN-1IP will register its info to the HDL 

server again, e.g., if we set it as 5 minutes, that means every 5 minutes the SB-DN-1IP 

will  register  itself  to  the  HDL  server  (so  that  HDL  server  knows  where  this  SB-DN-1IP 

locates  even  if  the  public  IP  of  the  router  is  changed  or  private  IP  of  the  SB-DN-1IP  is 

Summary of Contents for MBUS01IP.431

Page 1: ...on com MBUS01IP 431 4th generation This manual describes both old and new version of the gateway SB DN 01IP HDL MBUS01IP 431 The used snapshots come from previous version of HBST In the current version of HBST2 the aspect is slightly different but the functions are the same ...

Page 2: ......

Page 3: ...1 3 Mounting 2 1 4 Technical data 3 2 installations 4 2 1 Wiring 4 2 2 connector Info 4 3 Software configurations 5 3 1 Basic settings 5 3 1 1 Change the ID 5 3 1 2 Remark 5 3 1 3 DHCP Auto IP 6 3 2 Communication modes 6 3 2 1 Local Network mode 8 3 2 2 P2P mode 9 3 2 3 Remote Server mode 12 3 3 Site license 16 4 NOTES 18 ...

Page 4: ...en HDL system and Ethernet 1 2 Functionalities Bidirectional data exchange between HDL and Ethernet Support local network remote control and P2P the default is Local network About 4 devices can connect to this device remotely at once such as ILife ipad iphone android HDL bus pro software and so on Smart data exchange minimize the data traffic Site license for ILife only for 4th generation Auto IP ...

Page 5: ...n 40mA DC24V Installation mode standard 35mm DIN Rail Mount Dimension 72x90x66 mm HMI 128x64 raster graphic LCD RJ 45 UDP IP network interface Working environment Working relative humidity 0 45 Working temperature 20 90 40C Storage temperature 20 55 Storage relative humidity 10 93 40C Working Voltage DC12 30V Protection IP20 Approval Approved by CE ...

Page 6: ...ical gateway User Manual 4 2 installations 2 1 Wiring a LED indicator b Programming button c Ethernet RJ45 UDP IP interface d HDL interface 2 2 connector Info Connector Information BusPro DC24V Red COM Black DATA White DATA Yellow ...

Page 7: ...conds until it turns to a red color 3 On the software click ton Address management and select Modify address when device button is pressed option it will show a window like below 4 click on Indicate initial address then it will show the current subnet device ID of this module to modify the address fill in the new address and click the Modify initial address Click the Add button the device will be ...

Page 8: ...r that the module will reboot its self for about two seconds and it will be obtain a new IP address from the DHCP server 3 2 Communication modes If the firmware of SB DN 1IP is HDL_V04 02N_2013 05 30 or newer it supports three modes i e Local Network mode P2P mode and Remote Server mode Tips when the firmware upgrade finished better to power off this module for several seconds and power on this mo...

Page 9: ...User Manual SB DN 1ip HDL typical gateway User Manual 7 numbers can be set arbitrarily ...

Page 10: ...it always is a gateway between HDL BUS and local Ethernet This mode does not have remote function Configuration steps 1 Change the default IP and IP MAC to avoid possible conflict Default IP 192 168 10 250 Default IP MAC H D L 85 85 85 2 Select Local Network all other tables will not be available and click Apply ...

Page 11: ...end user to control the HDL BUS system in their home from e g their IPad because the IPad will have different public IP when end user is in office bus subway metro homeI PS For Installation Company this mode is more secure than Remote Server mode since no server saves your password and the SB DN 1IP only transfers the data to the installation company so even somebody knows the password it is usele...

Page 12: ...ou are going to fill in the Router R2 when setting up port forwarding Some routers support Internal port and External port mapping some do not the example below is this kind there is only one port or you can take it as External port equals Internal port to simplify we suggest to use the port 6000 for all ports 3 Configure port forwarding in Router R1 Map UDP port 6000 to the IP of SB DN 1IP ...

Page 13: ... the functionality port forwarding here in the example it is literally virtual machine 4 Configure port forwarding in Router R2 Map UDP port 6000 to the IP of PC laptop that runs HDL BUS Pro Setup Tool 5 Run HDL BUS Pro Setup Tool on the PC laptop with the IP set in the Router R2 in this doc it is 192 168 1 100 ...

Page 14: ...r R1 the Port is the one set in Router 1 the UDP 6000 7 Click Apply this pop up window will disappear when you connect to the remote SB DN 1IP successfully then you can search for devices and configure them as usual 3 2 3 Remote Server mode This mode is suitable for both travelling programmer and end user to configure and control HDL BUS system via Internet Since a server is getting involved in th...

Page 15: ...ode will keep updating itself to the server programmer and end user can always get info of the remote SB DN 1IP from the server and later access the HDL BUS system directly Schematic diagram Configuration steps 1 Change the default IP and IP MAC to avoid possible conflict 2 Set your Project Name Group Name User PWD and click Apply NOTE ...

Page 16: ...ion companies can fill in their own servers and ports 3 Exit HDL BUS Pro Setup Tool and find another Internet access that has a different public IP for your PC laptop run the HDL BUS Pro Setup Tool again and select Communication mode C III 4 Fill the Group Name and sever IP Click the search button on the pop up window HDL server will feedback all projects in the same group An installation company ...

Page 17: ...system 6 Get into the SB DN 1IP you can check the Access Log and connection status Interval 1 255 m It is the parameter that decides how long the SB DN 1IP will register its info to the HDL server again e g if we set it as 5 minutes that means every 5 minutes the SB DN 1IP will register itself to the HDL server so that HDL server knows where this SB DN 1IP locates even if the public IP of the rout...

Page 18: ... at the same time 3 3 Site license Site license is to used to register the 1ip module MBUS01IP 431 on ILife so all devices IPAD IPHONE ANDROID can use one registration to control HDL bus on ILife instead of registering each device one by one this feature is used mostly in Home showrooms and so on where there are many devices IPAD IPHONE ANDROID to control HDL bus through Ilife its quite costly to ...

Page 19: ...D IPHONE or ANDROID connected to the same WIFI as 1ip module 2 On Ilife click on the gear button at the right top and select site license 3 Fill in the subnet ID and device ID of the IP module and click on machine code and it will read the ID of the module and you can use that code for registration ...

Page 20: ...User Manual SB DN 1ip HDL typical gateway User Manual 18 4 NOTES ...

Reviews: