background image

1

Heat & Glo  •  PVK-80 Power Vent Instructions •  655-900  Rev. O  •  12/09

PVK-80 Power Vent

- Installation Instructions -

PVK-80 POWERVENT

6.

  CLEARANCES BETWEEN THE VENT PIPE AND 

COMBUSTIBLE MATERIALS MUST BE MAIN-
TAINED AT 3 INCH TOP, 1- NCH SIDES, AND 1 
INCH BOTTOM.

7. 

CAUTION:

  Failure to install, operate, and main-

tain the power venting system  in accordance with 
manufacturer's instructions will result in conditions 
which may produce bodily injury and/or property 
damage.

INSTALLATION OF PVK-80 POWER VENT

Note: 

Some  fi replace models may have unique venting 

and/or wiring requirements when used with the PVK-80. In 
those cases, PVK-80 instructions those manuals supersede 
these instructions. 

1.  Location of venting system terminations must be made 

in accordance with national, provincial, and/or local 
codes. The minimum clearance requirements must be 
followed on models using the PVK-80 Power Vent.

A. The exit termination of mechanical draft systems 

shall not be less than 7 feet above grade when 
located adjacent to public walkways and at least 
10 feet from lot line or adjacent buildings.

B. A mechanical drafting venting system shall termi-

nate at least 3 feet above any forced air inlet located 
within 10 feet.

C. The venting system of direct vent appliances shall 

terminate at least 12 inches below, 12 inches 
horizontally from, or 12 inches above any building 
opening through which fl ue gases could enter.

D. The vent termination point shall not be installed 

closer than 2 feet from an inside corner of an L-
shaped structure.

E.  The vent termination should not be mounted directly 

above or within 3 feet horizontally from an oil tank 
vent or gas meter.

F.  The bottom of the vent termination shall be located 

at least 2 feet above the fi nished graded and 2 feet 
above any combustible projection.

Note:

 The PVK-80 Power Vent must terminate in a 

HORIZONTAL

 position. See Figure 1.

2.  Install vent system components per planned vent 

run.  Route the vent pipe from the fi replace to the 
Power Vent using the minimum number of elbows 
possible. Refer to Tables 2 and 3 for vent specifi ca-
tions per size of vent pipe used.

Note:

 Most direct vent fi replaces can use either 4 in./ 6-5/8 in. 

or 5 in. / 8 in. direct vent pipe components when using the PVK-
80 and conforming to the parameters in Tables 2 and 3.  

IMPORTANT:

  Failure to read and follow these instruc-

tions may create a possible hazard and will void the 
fi replace warranty.

THESE INSTRUCTIONS MUST REMAIN WITH THE 
EQUIPMENT.

INTRODUCTION

Models PVK-80 Power Vent can be used on direct 
vent gas fi replaces manufactured by Hearth & Home 
Technologies.

Any gas fi replace fi tted with the PVK-80 Power Vent 
must utilize DSI (direct spark ignition) or IPI (intermit-
tent pilot ignition) fi replace gas controls. Fireplaces 
equipped with millivolt type gas controls 

CANNOT

 use 

this Power Vent.

Tables 2 and 3 list the type and size of vent pipe, 
maximum number of 90° elbows, maximum total vent 
pipe run, and maximum vertical drop allowed when 
using this Power Vent.

The PVK-80 Power Vent operates on 120VAC, 60Hz 
electrical service which is supplied at the fi replace 
junction box.

INSTALLATION PRECAUTIONS

1.  This device must be installed by a qualifi ed installer 

in accordance with these instructions.

2.  Safety inspection of the venting system should 

be performed before and after installation of this 
power vent. Consult local code offi cials and follow 
applicable installation codes.

3.

  DO NOT INSTALL DAMAGED EQUIPMENT OR 

VENT COMPONENTS.

4.  Disconnect electrical power supply before making 

wiring connections.

5. 

VENTING OF MORE THAN ONE APPLIANCE IN 
A COMMON VENT SYSTEM IS PROHIBITED.

Summary of Contents for PVK-80

Page 1: ... at least 2 feet above the finished graded and 2 feet above any combustible projection Note The PVK 80 Power Vent must terminate in a HORIZONTAL position See Figure 1 2 Install vent system components per planned vent run Route the vent pipe from the fireplace to the Power Vent using the minimum number of elbows possible Refer to Tables 2 and 3 for vent specifica tions per size of vent pipe used Note ...

Page 2: ... 4 3 A vent pipe adaptor must be installed on the fireplace vent collars if a smaller vent pipe than the fireplace starting collars is to be used in the vent system Adaptors are also used to connect the last smaller vent system component to the Power Vent cap SEE TABLE 1 FOR ADAPTOR DESCRIPTIONS 4 After determining the location of the vent system termination point see Step 1 cut a 10 in X 10 in for ...

Page 3: ...e Fasten the other end of each brace to the outside wall See Figure 4 WIRING THE POWER VENT Note Electrical wiring must be done in accordance with national provincial and or local electric codes Note Some fireplace models may have unique wiring requirements when used with the PVK 80 In those cases PVK 80 instructions those manuals supersede these instructions CAUTION Before performing any maintenan...

Page 4: ...5 006 Hardware Bag 655 900A 6 Plug one end of the black wire harness into one of the HOT terminals on the junction box Plug the other female end into the back of the rocker switch where the brown wires were removed in Step 6 7 Plug the white wire from the terminal block har ness into one of the NEUTRAL terminals of the junction box 8 Plug the black wire from the terminal block har ness into the ba...

Page 5: ...tion Inspection If the burner flames are short active and jumping remove the lever screw and slightly close the ex haust control Check the burner flames and adjust the lever again as necessary until the flames are stable strong and steady If the burner flames are tall lifting floating and ghost like the exhaust control is closed too far and MUST be opened When the burner flames have been optimized secur...

Page 6: ...h the cable loosened from the power vent as sembly remove the sheetmetal screws used to secure the power vent assembly in place Firmly support the assembly to prevent the unit from falling after the sheetmetal screws have been removed See Figure 10 E Remove the sheetmetal screws from the 10 1 2 in diameter pipe and remove the inner ring from inside the collar See Figure 11 IMPORTANT Take special n...

Page 7: ...wires back through the hole on the collar and tighten the nut on the right angle connector Reconnect the brown and red wire to the vacuum switch and connect the black and white wires to the fan motor CAUTION Make sure the cable is NOT in the path of the hot exhaust air This can cause the wire insulation to melt and the Power Vent to malfunction G Reattach the end cap to the cap assembly with four ...

Page 8: ...6 90 12 DIRECT VENT WITH 5 in 8 in DIAMETER DVP PIPE MAX ELBOWS 45 90 MAX TOTAL VENT RUN FT MAX VERT DROP FT 10 90 12 ADAPTOR KITS PART NUMBER PART DESCRIPTION SL 2DVP Adapts from 4 in 6 5 8 in SL D series starting collars to 5 in 8 in DVP vent pipe DVP 2SL Adapts from 5 in 8 in DVP series starting collars to 4 in 6 5 8 SL D series vent pipe Table 1 Note Some fireplace models may have unique wiring...

Page 9: ... TERMINAL BLOCK BLK WHT BRN RED 120 V MOTOR VACUUM SWITCH BLK WHT BRN RED TO REMOTE OR WALL SWITCH This connection is 120 VAC use appropriate wire and switches VALVE GREEN ORANGE WHT ORG GROUND TO FIREPLACE CHASSIS INTERMITTENT PILOT IGNITOR IGNITION MODULE 3 VAC BRN BRN TRANSFORMER 3 VAC PIGGYBACK SWITCH Figure 18 IPI Wiring Diagram With Pvk 80 Installed System 4 Note Remove battery pack from the...

Page 10: ...h See Detail A This switch must be manually turned ON and OFF whenever the fireplace is operated with the WSK 300 wall panel By turning the Power Vent ON the suction created by the Power Vent closes the vacuum switch which completes the circuit on the cable assembly BRN Wire enabling the ignition sequence of the WSK300 HNG to operate the fireplace A1 A2 A3 HI LOW JUNCTION BOX 110V MINIMUM 14 3 AWG...

Page 11: ...CONNECTION BLACK PLUG ADP IPI MODULE IPI PILOT 3V DC BLACK RED BROWN BROWN RED GREEN YELLOW H G WHITE HTL REAR VIEW FRONT VIEW FIREBOX BACK LIGHT 1 BACK LIGHT 2 R Y G G Y R PVK 80 POWERVENT BLACK BROWN RED WHITE WHITE BLACK BROWN RED BROWN BROWN RED BLACK GREEN NOTE 1 BROWN AND RED WIRES FROM PVK 80 ARE FOR THE VACUUM SWITCH NOTE 2 BLACK WHITE AND GREEN WIRES RUN PVK 80 MOTOR NOTE 3 GREEN WIRE FRO...

Reviews: