20
07/22
7027-804H
D. Full Reline With Outside Air - Vertical
NOTE:
Check clearances carefully for this type of
installation to ensure adequate room for outside air
venting.
NOTE:
In Canada only a full reline is allowed per
ULC
S628, ORD ULC C1482-M1990
.
Outside Air
Termination
at
Chimney Top
(Vertical)
305mm min.
below
305mm min.
above
NOTE; Use non-combustible
materials around exhaust vent pipe
and seal all edges with
non-flammable insulation such as
mineral wool or ceramic.
Do not use high temperature
caulking materials to seal any edge
to prevent furture serviceability.
Figure 20.1
NOTE:
In Canada this fireplace insert must be installed
with a continuous chimney liner extending from the
fireplace insert to the top of the chimney. The chimney
liner must conform to the Class 3 requirements of
CAN/
ULC-S635, Standard for Lining Systems for Existing
Masonry or Factory-Built Chimneys and Vents, or
CAN/ULC-S640, Standard for Lining Systems for New
Masonry Chimneys
.
Check building codes prior to installation.
• Installation MUST comply with local, regional, state
and national codes and regulations.
•
Consult local building, fire officials or authorities
having jurisdiction about restrictions, installation
inspection, and permits.
CAUTION