Hearthstone Quality Home Heating Products, Inc
CHAMPLAIN DV Model 8301
IV.
H
ORIZONTAL
T
ERMINATION
V
ENTING
C
ONFIGURATIONS
-A minimum of 24" rise is required (with or w/o
offsets)
-40' maximum system height (without offsets)
-Maximum rise to run = 1 to 5
-The termination must meet the requirements
outlined in
Figure 8 & 9.
Use a vinyl siding Stand off
when installing against vinyl siding.
-Horizontal sections require a 1/4" rise every 12" of
horizontal run.
-For each 90° elbow after the second, remove 5'
from horizontal run.
-Use with snorkel termination 45" maximum
horizontal run.
Figure 12: Approved DV Venting Alternate Configurations for Vertical Termination
Page 15 of 30