background image

OWNER’S MANUAL                                                                                  MODEL:  8745 TUCSON Vent-Free HEATER

 

 

 

-12- 

 
GAS SUPPLY & CONNECTIONS 

Gas Supply 
NOTICE:  A qualified technician must connect the 
heater to the gas supply and leak test the unit 
before it is approved for use.  Consult all local 
codes.

 

 

WARNING:  

The unit must be installed and 

connected in accordance with local codes, or in the 
absence of local codes, with the most current edition 
of the National Fuel Gas Code ANSI Z223.1/NFPA 
54. 
We recommend using new black iron or steel pipe 
only.  Internally tinned copper tubing can be used in 
some areas when permitted by local codes.  Only use 
pipe of ½" or greater diameter to allow full gas 
volume to heater.  Excessive pressure loss will occur 
if the pipe is too small. 
The supply line must include a manual shut-off valve 
and union so that the unit can be disconnected for 
servicing Also a sediment trap must be installed 
upstream of the heater. The sediment trap is installed 
to prevent moisture and contaminants from passing 
through the pipe to the heater controls and burners. 
Failure to install a sediment trap could prevent the 
heater from operating reliably. 
The gas supply line connection is made to the 
Tucson’s gas control valve just inside the  left front 
leg of the unit using a 

d

" male NPT fitting. The 

supply line should be ½" diameter or appropriately 
sized to  provide a sufficient gas supply to meet the 
maximum demand of  

the unit without undue loss of pressure.  We 
recommend a flexible line to avoid undue mechanical 
load on the valve and to ease thread alignment, but 
also refer to local code.

  

 
CAUTION: Check Gas Type!  

The gas supply must 

be the same as stated on the heater’s rating 
plate(located on the back of the unit).  If the gas 
supply is different,

 DO NOT INSTALL 

the heater.  

Contact your dealer for the correct model. 
 

Gas Pressure Adjustment

 

The supply line pressure is tested, to ensure it meets 
the minimum pressure, as listed in the Specifications 
sections of this manual, for the type of fuel in use 
(NG or LP).  The Tucson must be isolated from the 
gas supply piping system by closing its individual 
manual shutoff valve during any pressure testing of 
the gas supply piping system at test pressures equal to 
or less  than ½" psig.  During tests in excess of  ½" 
psig. (14" w.c.), the heater must be disconnected from 
the gas supply system.  Test by connecting a 
manometer to the supply line.  Adjust the incoming 
pressure, if necessary, to meet the  required supply 
line pressure.  Once connected to the gas supply, the 
gas inlet  pressure and manifold gas pressure must be 
tested. The gas inlet tap (6) and manifold pressure tap 
(7) is located on the control valve (

see Figure 5

).  

Connect a manometer to  the test points on the gas 
control valve, refer to 

#’s 6 & 7

 of 

Figure 5

 for 

locations.

 

 

 

Figure 5

 

Summary of Contents for TUCSON 8745

Page 1: ...erformed by a qualified installer service agency or the gas supplier This is an un vented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion...

Page 2: ...___ __________________________________ ____ _________________ _______________ __________________________________ ____ _________________ _______________ __________________________________ ____ ________...

Page 3: ...he heat output along with the flame height to suit personal needs Heat output can be reduced during the Fall and Spring when the need for heat is reduced and increased during Winter months when the ne...

Page 4: ...ill be operating The installation must conform with local codes or in the absences of local codes the current National Fuel Gas Code ANSI Z223 1 NFPA 54 DO NOT INSTALL THIS HEATER IN A BEDROOM OR BATH...

Page 5: ...tric spark generator as described in the How To Turn the Unit On Off section of this manual Never attempt to light the pilot or main burners by hand with a match or lighter After repeated attempts if...

Page 6: ...stibles Minimum alcove height 22 above stove top HEARTH REQUIREMENTS FLOOR PROTECTION The Tucson can be installed on wood flooring or a non combustible surface For installation of the Tucson on carpet...

Page 7: ...s to be installed meets the following criteria it is considered to be an unconfined space The room in which the heater is to be installed has an air volume of at least 50 cubic feet cubic feet length...

Page 8: ...f the number from III is smaller than the number calculated in II the space should be considered an unconfined space If the number from III is larger than II the space should be considered a confined...

Page 9: ...d space needs to have two permanent openings one commencing within 12 inches 30 cm of the top and one commencing within 12 inches 30 cm of the bottom of the enclosure The openings shall communicate fr...

Page 10: ...the top three stones and grill Use the protective wrapping material to temporarily protect the stones from chipping or damage while the unit is inspected and installed With the top stones and grill r...

Page 11: ...ly behind or too close to the unit otherwise heat from the unit will immediately satisfy the thermostat and turn the unit off Violet Black Yellow On Off T stat Figure 4 Wiring diagram Thermostat Wirin...

Page 12: ...line should be diameter or appropriately sized to provide a sufficient gas supply to meet the maximum demand of the unit without undue loss of pressure We recommend a flexible line to avoid undue mec...

Page 13: ...use however they will break if subjected to rough or improper handling Broken or cracked logs should be replaced When removing and replacing the log set from the unit during routine cleaning or servic...

Page 14: ...m the firebox The log set assembly will be in four pieces along with the charcoal embers as shown in Figure 6 First remove the Top Log 6 by pulling it up off the Middle Log 2 and out of the firebox Ne...

Page 15: ...o its lowest setting or OFF position If the gas control knob is not in the OFF position turn the knob fully clockwise to OFF Locate the variable output and turn it fully clockwise to the highest setti...

Page 16: ...en turned to the ON position the main burners are lit by selecting ON of the On Off T stat switch or if T STAT was selected by moving the thermostat to a high setting so that it calls for heat i e tur...

Page 17: ...ly the thermocouple as well located next to the pilot but not so large as to create excessive noise or consume excessive gas However it can be adjusted by means of the pilot light adjustment screw loc...

Page 18: ...accumulation of dust lint and other debris To clean the firebox set the thermostat to the OFF position and turn off the gas at the gas control valve When the unit is cool u nfasten the front door and...

Page 19: ...x 6 1741 352 top center stone 8e x 3e 7211 554 rear log 7211 559 middle log 7211 556 front log 7211 557 top log 7211 558 charcoal ember 2 oz 5320 070 ember screen 5710 119 light shield 5710 120 back l...

Page 20: ...TER 20 Natural Gas LP Input rating Btu hr 20 000 20 000 Minimum input rating Btu hr 13 500 16 000 Orifice size DMS 44 55 Man pressure HI setting in w c kPa 3 5 10 0 Man Pressure Lo setting in w c kPa...

Page 21: ...oltage between valve body and solder connection on the rear of the valve where the blue wire connects It should be no less than 7mV C1 Ensure that the thermocouple connection at the gas valve is tight...

Page 22: ...input underrated C Valve leak if flashback occurs with burner valve in off position D Improper gas pipe size A Incorrect air to fuel ratio A1 Primary air incorrect A2 Burner ports plugged B Pilot not...

Page 23: ...d orifices against breakage cracking or burn through Ceramic logs and embers against breakage cracking or burn through This warranty expires on the fifth 5th anniversary of the Purchase Date LIMITED T...

Page 24: ...RRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE SHALL APPLY TO THE SUBJECT STOVE SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS SO THE ABOVE LIMITATION MAY...

Page 25: ...ts related to shipping Stove parts to and from HearthStone or a Dealer as the case may be Shipping cost for the Stove Within the first 1st year after the Purchase Date if the Original Purchaser is ins...

Reviews: