Page 38
4/20/11
Heat & Glo • NorthStar EPA Fireplace • 480-1081E
Do not apply combustible finishing materials over any part
of the front of this fireplace.
• The metal fireplace face may only be covered with
noncombustible materials such as ceramic tile, brick,
or stone.
• Do not cover or block any cooling air slots.
The decorative fascia must be removable for future service-
ability of the Automatic Combustion Control.
WARNING
!
Fire Risk!
Comply with all minimum clearances specified.
• A minimum 1 in. (13mm) air clearance must be
maintained at the back and 1 in. (25mm) to the sides of
the fireplace assembly.
• Chimney sections at any level require a 2 in. (51mm)
minimum air space clearance between the framing and
chimney section.
WARNING! Fire Risk!
D. Electrical Access and Wiring Diagram
NOTICE: The manual override switch, rheostat speed con-
trol and cover plate are supplied. You will need to supply:
14-3 wire with ground; 14-2 wire with ground; standard wall
mount junction box; wire nuts.
1. Remove junction box cover plate on the bottom right side
of the fireplace.
2. Thread the 14-3 with ground wire through the opening
with the strain relief on the cover plate.
3. Match colors to wire harness, (red to red, white to white,
etc) and secure with wire nuts.
NOTICE: Wiring for fans must be done before framed
enclosure is completed. If using a Heat Zone kit, it also
must be installed before enclosure is complete.
Figure 6.4 Fan Wiring Diagram
14-2 w/ground
Standard wall mount with
Junction Box
14-3 w/ground
WIRE NUT
WHITE
GREEN
BLACK
BLACK
RED
WHITE
Match colors to wire
harness (red to red,
white to white, etc) and
secure with a wire nut
Incoming Power
(110V)
Power to the Fireplace
Snap Disc
bypass switch
• Maintain clearances.
• Use only non-combustible material below standoffs,
material such as cement board is acceptable.
• Framing or finishing material used on the front of, or
in front of, the appliance closer than the minimums
listed, must be constructed entirely of noncombustible
materials (i.e., steel studs, concrete board, etc.).
WARNING! Risk of Fire! You must comply with all minimum air space clearances to combustibles. DO NOT pack re-
quired air spaces with insulation or other materials.