Page 60
4/20/11
Heat & Glo • NorthStar EPA Fireplace • 480-1081E
INSTALLATION
1. Remove the knockout or cover plate from the top of the
fireplace and discard it. See Figure 11.2.
2. Cut a 3 in. (76mm) hole in the insulation board as per the
dimensions shown in Figure 11.2
Adapter
Mounting
Plate
Starter Pipe
Knockout
Cut a 3 in. (76mm) ho
le
in insulation board
3-13/16 in.
(97mm)
3-1/8 in. (79mm)
CL
Run Length
Cut Pipe
20 - 40 ft (6-12m)
2 in. (51mm)*
*A minimum of 2 in. (51mm) pipe must be used to
cover the raw insulation to prevent it tfrom blow-
ing out through the Return Air grille.
10 - 20 ft (3 - 6m)
8 in. (203mm)
3 - 10 ft (1 - 3m)
No cut needed**
**
Use full 16 in. (406mm) as supplied
3. Determine the necessary length of starter pipe from the
following table and cut as required. See Figure 11.3.
4. The starter pipe is shipped flat. After cutting to the required
length, manually roll the pipe together and snap lock into
place.
NOTE: It is important the pipe length be adhered
to or it will affect the performance of your fireplace.
Figure 11.2
Figure 11.3
5. Slide the starter pipe into the fireplace, matching the holes
in the plate to the holes in the fireplace.
6. Place the Adapter on the Mounting Plate lining up holes.
Using the 4 sheet metal screws included in the kit, secure
the Adapter and Mounting Plate into fireplace. After secur-
ing to the fireplace, tape down the Adapter edges to the top
of the fireplace with aluminum tape to prevent leakage.
7. Determine the location for the air register and fan housing
assembly. Cut a 7-5/8 in. x 13-5/8 in. (143 x 346mm) hole
between framing members (wall studs or floor joists). The
brackets can be rotated 180° and mounted to the back side
of the 2 x 4 if necessary. See Figure 11.6 on page 61.
NOTICE: The fan and electrical connections must be
accessible for servicing per local code requirements.
NOTE: If the fan housing is installed in a 2 x 4 wall, the
front of the housing will protrude approximately 1/4 in.
(6mm) from the finished wall. see Figure 11.5 on page
61.
8. Attach enough 6 in. (152mm) B-Vent as required for
your installation to the fan housing.
A maximum of (4) 90°
elbows is recommended.
Securely
twist lock the B-Vent
to the Adapter.
Also screw the B-Vent to the outlet box on the fan housing.
See Figure 11.6 on page 61. Support duct at intervals of no
greater than 4 ft (1 m) as required by local code.
Figure 11.4
Warning Fire Risk!
Comply with all minimum clearances specified.
• A minimum 1 in. (13mm) air clearance must be
maintained at the back and 1 in. (25mm) to the sides
of the fireplace assembly.