NOTES:
• The CAK4A termination cap must be a minimum of 4 ft
(1219 mm) above the ground and kept free of debris.
• If the CAK4A is installed in a chase, the CAK4A side
termination cap must be at least 3 ft (914 mm) below
the chimney top.
• Seal around the cap and flex with caulk to stop air from
getting into the chase (see Figures 6.4).
Wire Ties
Seal
Seal
4" Duct - Use UL181
Class 0 or Class 1
ducting.
Figure 6.4 Installing Flex Pipe
WARNING! Risk of Fire!
• The flex pipe must never be compressed or deformed!
• Restricting the airflow inside the flex pipe may increase
flue pipe temperatures causing a chase fire.
27
Heat & Glo • NORTHSTAR • 480-2360 Installation Manual • Rev H • 8/20/14