37
Heat & Glo • SL-750TRS-IPI-E, SL-550TRS-IPI-E, SL-350TRS-IPI • 2120-901 Rev. U • 11/13
Clearances to Combustibles:
Refer to Section 5 for clearances to the appliance, man-
tel, mantel legs and wall projection.
Refer to Section 8 for pipe clearances to combustibles.
Termination Cap
For installation of termination cap see minimum vent
heights for various pitched roofs. See Section 6 of appli-
ance owner’s manual.
Flue Damper
Fully lock the solid fuel
fi
replace’s
fl
ue damper in the open
position, OR completely remove it.
Venting Components
The LINK-DV30B is approved for use with the coaxial/co-
linear venting application. The LINK-DV30B kit includes:
• Two 30 feet sections of
fl
exible vent pipe (3 inches Ø).
One section is used to draw combustion air and the other
section is used to expel exhaust gases.
• One vertical termination cap.
WARNING! Risk of Fire!
Coaxial to colinear venting
con
fi
guration may only be used in existing non-combus-
tible chimney. Installation in any other venting application
could cause
fi
re.
Prior to installing the gas appliance:
• Have the chimney and adjacent structure inspected
and cleaned by quali
fi
ed professionals. Hearth & Home
Technologies recommends that NFI or CSIA certi
fi
ed
professionals, or technicians under the direction of certi-
fi
ed professionals, conduct a minimum of a NFPA 211
Level 2 inspection of the chimney.
• Replace component parts of the chimney and
fi
replace
as speci
fi
ed by the professionals.
• Ensure all joints are properly engaged and the chimney
is properly secured.
EXHAUST VENT PIPE
INLET AIR VENT PIPE
Figure 7.18 Coaxial/Colinear Appliance Adapter (DV-46DVA-GCL)
Coaxial to Colinear Venting
The coaxial to colinear adapter (DV-46DVA-GCL) is ap-
proved for installations into solid fuel masonry or factory
built
fi
replaces that have been installed in accordance
with the National, Provincial, State and local building
codes. The DV-46DVA-GCL must be recessed into exist-
ing masonry
fi
replace. See Table 1 and Figure 7.19.
OUTSIDE FACE OF
FIREPLACE
TOP OF FIREPLACE
OPENING
SHADED AREA DEFINED AS
“INSIDE EXISTING MASONRY FIREPLACE”
3 IN. MIN.
5 IN. MIN.
EXHAUST VENT PIPE
Figure 7.19 Existing Fireplace DV-46DVA-GCL Clearance
Requirements
Table 1
CLEARANCE TO COMBUSTIBLES REQUIREMENTS
DV-46DVA-GCL 3
IN.
Exhaust Vent Pipe
5 IN.
CAUTION! DO NOT use any
fl
ue restrictor when vent-
ing with the DV-46DVA-GCL adapter and LINK-DV30B
kit.
This may result in poor
fl
ame appearance, sooting,
pilot malfunction, or overheating.