Heat & Glo • SL-36-Ultimate • 2141-900 Rev. i • 5/11
30
A. Recommendation for Wire
This appliance requires 110-120 VAC be wired to the
junction box either for use of optional accessories or for
proper operation of the appliance.
10
Electrical Information
Note:
This appliance must be electrically wired and grounded
in accordance with local codes or, in the absence of local
codes, with
National Electric Code ANSI/NFPA 70-latest
edition
or the
Canadian Electric Code, CSA C221.1
.
B. Connecting to the Appliance
Wire 110V to electrical junction box.
Do NOT wire 110V to valve.
Do NOT wire 110V to wall switch.
• Incorrect wiring will damage millivolt valves.
• Incorrect wiring will override IPI safety lockout
and may cause explosion.
C. Intellifi re Ignition System Wiring
This appliance requires a 110 VAC supply to the appliance
junction box for operation. A wiring diagram is shown in
Figure 10.1.
This appliance is equipped with an Intellifi re control valve
which operates on a 3 volt system.
This appliance is supplied with a battery pack and a 3 volt
AC transformer, which requires the installation of the sup-
plied junction box. It is highly recommended that the junc-
tion box be installed at this time to avoid reconstruction.
The battery pack requires two D cell batteries (not includ-
ed). Batteries cannot be placed in the battery pack while
using the 3 volt AC transformer. Conversely, the trans-
former must be unplugged if the battery pack is used.
CAUTION
Battery polarity must be correct or module damage will
occur.
WARNING
Figure 10.1 Intellifi re Pilot Ignition (IPI) Wiring Diagram
Note
1: Ignition module, valve, pilot
and wall switch operate on 3 volts.
Note
2: Plug WSK-MLT wall switch
kit into the REM/AUX outlet on the
junction box.
IPI
VALVE
ORANGE
WIRES WITH LABEL “FOR USE WITH REMOTE OR WALL SWITCH ONLY”
(LOCATED UNDER FIREPLACE)
GREEN
RED
RED
GROUND
PIGTAIL
GREEN
AUX
CONNECTION
FRONT VIEW
REAR VIEW
G Y R
BLACK
BLACK
AC
FAN
CONNECTION
ORANGE
BATTERIES
1
2
3
4
5
6
7
8
R Y G
ORANGE
IPI
MODULE
FLAME
SOLENOID
FLAME HIGH/LOW
BLACK
RED
BLACK
RED
RED
BLACK
RED
(MALE/FEMALE)
RED
(FEMALE/MALE)
ADAPTER WIRES
BROWN
BROWN
GROUND
BLACK
BROWN
BROWN
RED
GREEN
YELLOW (HNG)
WHITE (HTL)
BATTERY
IPI PILOT
3V DC
FLAME ON
YELLOW
YELLOW
FAN THERMOSTAT
FACTORY
CONNECTED
TOGETHER
FIREBOX LIGHTS
CONTINUOUS
110VAC
SUPPLY
BLACK
WHITE
GROUND
HOT
FA
N
TRANS
REM/AUX
NEUTRAL
• A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when
it is installed in locations such as in bathrooms or near
sinks.