background image

Heat & Glo  •  SL-36-Ultimate  •  2141-900  Rev. i  •  5/11

46

Intellifi re Ignition System - (continued)

Symptom

Possible Cause

Corrective Action

3. (Continued)  Pilot lights 

but continues to spark, 

and main burner will not 

ignite. (If the pilot contin-

ues to spark after the pilot 

fl ame has been lit, fl ame 

rectifi cation has not oc-

curred.)

c. Module is not grounded.

Verify that module is securely grounded to metal chassis 

of appliance. Verify that wire harness is fi rmly connected to 

module.

d. Damaged pilot assembly or dirty sensor 

rod.

Verify that ceramic insulator around the sensor rod is not 

cracked, damaged, or loose. Verify connection from sensor 

rod to white sensor wire. Clean sensor rod with emery cloth 

to remove any contaminants that may have accumulated 

on sensor rod. Verify continuity with a multimeter with 

ohms set at lowest range. 

e.  Faulty module.

Turn ON/OFF rocker switch or wall switch to OFF posi-

tion. Remove ignitor wire “I” from module. Place ON/OFF 

Rocker switch or wall switch in ON position. Hold ground 

wire about 3/16 inch away from “I” terminal on module. If 

there is no spark at “I” terminal module must be replaced. 

If there is a spark at “I” terminal, module is fi ne. Inspect 

pilot assembly for shorted sparker wire or cracked insulator 

around electrode.

4. Pilot sparks, but Pilot 

will not light.

a.  Correct gas supply.

Verify that incoming gas line ball valve is “open”. Verify that 

inlet pressure reading is within acceptable limits, inlet pres-

sure must not exceed 14 in. W.C. 

b.  Ignitor gap is too large.

Verify that spark gap from ignitor to pilot hood is .17 in. or 

1/8 in.

c.  Module is not grounded.

Verify module is securely grounded to metal chassis of 

appliance.

d.  Module voltage output / Valve/Pilot 

solenoid ohms readings.

Verify battery voltage is at least 2.7 volts. Replace batteries 

if voltage is below 2.7.

Summary of Contents for SL-36-Ultimate

Page 1: ...n the rating plate Installation and service of this appliance should be performed by qualified personnel Hearth Home Technologies suggests NFI certified or factory trained professionals or technicians supervised by an NFI certified professional Leave this manual with party responsible for use and operation DO NOT DISCARD Important operating and maintenance instructions included Read understand and fo...

Page 2: ...del Number Not Not for for use use with with solid solid fuel fuel Ne Ne doit doit pas pas entre entre utilise utilise avec avec un un combustible combustible solide solide This This appliance appliance must must be be installed installed in in accordance accordance with with local local codes codes if if any any if if not not follow follow ANSI ANSI Z223 1 Z223 1 in in the the USA USA or or CAN C...

Page 3: ... 20 D Installing Non combustible Facing Material 21 8 Installing Vent Pipe A Assembly of Vent Sections 22 B Disassembly of Vent Sections 24 C Installing Heat Shield and Horizontal Termination Cap 25 D Installing Roof Flashing and Vertical Termination Cap 26 9 Gas Information A Fuel Conversions 28 B Gas Pressures 28 C Gas Connection 28 10 Electrical Information A Recommendation for Wire 30 B Connec...

Page 4: ...ompressed paper plant fibers plastics or other material that can ig nite and burn whether flame proofed or not or whether plastered or unplastered shall be considered combustible materials G Electrical Codes NOTICE This appliance must be electrically wired and grounded in accordance with local codes or in the absence of local codes with National Electric Code ANSI NFPA 70 latest edition or the Canad...

Page 5: ...ng appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OB STRUCTIONS Inspection The state or local gas inspector of the side wall horizon tally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector ob serves carbon monoxide detectors and signage installed in accordanc...

Page 6: ...g The vent system components and trim doors are shipped in separate packages The gas logs may be packaged separately and must be field installed Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starting the instal lation Follow these instructions carefully during the installation to ensure maximum safety and benefit Check...

Page 7: ...acture lines or spider webbing on the surface of the material Cracks that are less than 1 32 in wide and less than 3 in long If cosmetically unacceptable such cracks may be repaired with the SRV PACK service kit See Service Parts List Cracks that are unacceptable Cracks greater than 1 32 in wide and 3 in long are at risk of growing Cracks that penetrate entirely through the firebrick material Insp...

Page 8: ...ccess Locate appliance away from traffic areas A Selecting Appliance Location When selecting a location for your appliance it is important to consider the required clearances to walls see figure 3 1 Figure 3 1 Appliance Locations Note For actual appliance dimensions refer to Sec tion 16 In addition to these framing dimensions also reference the following sections Clearances and Mantel Projections Se...

Page 9: ... in regions where cold air infiltration may be an issue the inside surfaces may be sheetrocked and taped for maximum air tightness To further prevent drafts the wall shield and ceiling firestops should be caulked with caulk with a minimum of 300ºF continuous exposure rating to seal gaps Gas line holes and other openings should be caulked with caulk with a minimum of 300ºF continuous exposure rat C C...

Page 10: ...3 Clearances to mantels or other combustibles above appliance Figure 3 4 Clearances to Mantel Legs or Wall Projections Acceptable on both sides of opening 17 1 2 in Min 1 in Max 18 in Min 12 in Min 12 in Max COMBUSTIBLE TRIM NON COMBUSTIBLE FACING AND FINISHING MATERIAL Note Dimensions shown in inches ...

Page 11: ...12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 6 0 Over 16 12 to 18 12 7 0 Over 18 12 to 20 12 7 5 Over 20 12 to 21 12 8 0 Figure 4 2 Minimum height from roof to lowest discharge opening Figure 4 2 specifies minimum vent heights for various pitched roofs 3 foot minimum in snow regions HORIZONTAL OVERHANG VERTICAL WALL GAS DIRECT VENT TERMINATION CAP 12 X ROOF PITCH IS X...

Page 12: ... Electrical Service V K V K V L C V N 6 inches non vinyl sidewalls 12 inches vinyl sidewalls O 18 inches non vinyl soffit and overhang 42 inches vinyl soffit and overhang P 8 ft QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMAX 2 termination caps x QACTUAL Covered Alcove Applications Spaces open on...

Page 13: ... 1 Figure 5 1 5 Vent Information and Diagrams A Vent Table Key The abbreviations listed in this vent table key are used in the vent diagrams C Measuring Standards Vertical and horizontal measurements listed in the vent diagrams were made using the following standards 1 Pipe measurements are shown using the effective length of pipe see Figure 5 2 2 Measurements are made from the appliance outer wra...

Page 14: ...aximum V1 H1 30 ft 9 1 m Maximum Fire Risk Explosion Risk Do NOT pack insulation or other combustibles between ceiling firestops ALWAYS maintain specified clearances around venting and firestop systems Install wall shield and ceiling firestops as specified Failure to keep insulation or other material away from vent pipe may cause fire WARNING V1 Minimum H1 H2 Maximum 1 1 2 ft 457 mm 3 ft 924 mm 2 1 2 ft...

Page 15: ...6 in 3 ft 2 ft 6 in 6 ft 3 ft 6 in 9 ft 4 ft 10 ft 4 ft 6 in 12 ft 5 ft 6 in 15 ft 6 ft 6 in 18 ft 7 ft 6 in 21 ft HT 21 ft Max VT 40 ft Max VT HT 30 ft Max Note A section of vertical pipe 18 inches minimum MUST be installed prior to attaching a 90 elbow If the horizontal component is less than 5 feet then the total vent run can be extended to 40 feet ...

Page 16: ...izontal component is less than 5 feet then the total vent run can be extended to 40 feet VT Min HT Max 1 ft 6 in 3 ft 2 ft 6 in 6 ft 3 ft 6 in 9 ft 4 ft 10 ft 4 ft 6 in 12 ft 5 ft 6 in 15 ft 6 ft 6 in 18 ft 7 ft 6 in 21 ft HT 21 ft Max VT 40 ft Max VT HT 30 ft Max Note A section of vertical pipe 18 inches minimum MUST be installed prior to attaching a 90 elbow ...

Page 17: ...T Max 1 ft 6 in 3 ft 2 ft 6 in 6 ft 3 ft 6 in 9 ft 4 ft 10 ft 4 ft 6 in 12 ft 5 ft 6 in 15 ft 6 ft 6 in 18 ft 7 ft 6 in 21 ft HT 21 ft Max VT 40 ft Max VT HT 30 ft Max Note A section of vertical pipe 18 inches minimum MUST be installed prior to attaching a 90 elbow If the horizontal component is less than 5 feet then the total vent run can be extended to 40 feet ...

Page 18: ... shield is necessary If your local inspector requires the wall shield firestop on both sides then both wall shield firestops must have a heat shield attached to them Fire Risk Explosion Risk Maintain vent clearance to combustibles as specified Do not pack air space with insulation or other materials Failure to keep insulation or other materials away from vent pipe may cause fire Figure 6 1 Pipe Cleara...

Page 19: ...ield Note An additional ceiling firestop is not required if attic shield is used Frame opening for attic shield Attic shield may be installed above or below ceiling see Figure 6 4 Secure with three fasteners on each side Fold tabs at top of attic shield in toward vent pipe Tabs must keep vent pipe centered within shield Field construct additional shield height if insulation is deeper than height of...

Page 20: ...l away from the appliance may cause fire Fire Risk Prevent contact with sagging loose insulation Do NOT install against combustible materials such as exposed insulation plastic and insulation backer WARNING WARNING A Removing Non combustible Facing Mate rial Assembly The non combustible assembly is located on the back side of appliance CAUTION Handle with care Non combustible material may be damage...

Page 21: ...re 7 2 Attaching Non combustible Facing Material D Installing Non combustible Facing Material Center and attach two top boards to the framing members See Figure 7 2 Use fasteners from fastener packet in manual bag in shaded areas Use regular sheetrock screws in non shaded areas Use a wet or dry towel or soft brush to remove dust or dirt from facing material Apply a non combustible adhesive to atta...

Page 22: ...pletely locked into place It is acceptable to use screws no longer than 1 inch to hold outer pipe sections together If predrilling holes do NOT penetrate inner pipe For 90 and 45 elbows that are changing the vent direction from horizontal to vertical one screw minimum should be put in the outer flue at the horizontal elbow joint to prevent the elbow from rotating Use screws no longer than 1 inch If...

Page 23: ...p section is too long the inner and outer flues of the slip section can be cut to the desired length Assembling Minimum Installations MI Sections MI sections are non unitized so that they can be cut to a certain length Cut these sections to length from the non expanded end see Figure 8 6 They can then be attached by first connecting the expanded end of the MI inner flue with the inner pipe from the a...

Page 24: ...120 apart may be used to do this see Figure 8 9 Horizontal Sections Horizontal sections of vent must be supported every 5 feet with a vent support or plumber s strap Figure 8 9 Securing Vertical Pipe Sections Figure 8 12 Align and Disassemble Vent Sections Figure 8 11 Rotate Seams for Disassembly Figure 8 10 Securing Horizontal Pipe Sections Improper support may allow vent to sag or separate Fire ...

Page 25: ...odes Figure 8 13 Venting through the Wall Burn Risk Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap Fire Hazard Impaired performance of appliance Telescoping flue section of termination cap MUST be used when connecting pipe section to termination cap Maintain a 1 1 2 inch minimum overlap on telescoping flue section of termination cap INTE...

Page 26: ... the pilot holes in the outer collar of the cap into the outer flue of the pipe see Figure 8 15 Roof Pitch H Min Ft Flat to 6 12 1 0 Over 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5 0 Over 14 12 to 16 12 6 0 Over 16 12 to 18 12 7 0 Over 18 12 to 20 12 7 5 Over 20 12 to 21 12 8 0 3 foot mi...

Page 27: ...llar around the exposed pipe section and align brackets Insert a bolt provided through the brackets and tighten nut to complete storm collar assem bly see Figure 8 18 Slide the assembled storm collar down the pipe section until it rests on the roof flashing Caulk around the top of the storm collar see Figure 8 15 Assembling and Installing Storm Collar CAUTION Sharp Edges Wear protective gloves and ...

Page 28: ...ondition Low pressure may cause explosion Verify minimum pressures when other household gas appliances are operating Install regulator upstream of valve if line pressure is greater than 1 2 psig 9 Gas Information Note Gas line may be run from either side of the appliance provided the hole in the outer wrap does NOT exceed 2 1 2 inches in diameter and does not penetrate the firebox Note A listed and...

Page 29: ...with local authorities Ensure that gas line does not come in contact with outer wrap of appliance Follow local codes Incoming gas line should be piped into the valve compartment and connected to the 1 2 inch connection on the manual shutoff valve CHECK FOR GAS LEAKS Explosion Risk Fire Risk Asphyxiation Risk Check all fittings and connections Do not use open flame After the gas line installation is ...

Page 30: ... time to avoid reconstruction The battery pack requires two D cell batteries not includ ed Batteries cannot be placed in the battery pack while using the 3 volt AC transformer Conversely the trans former must be unplugged if the battery pack is used CAUTION Battery polarity must be correct or module damage will occur WARNING Figure 10 1 Intellifire Pilot Ignition IPI Wiring Diagram Note 1 Ignition ...

Page 31: ...xiliary function provides 110 120 VAC source for added features the fireplace may have installed Electrical ratings for the control box are 110 VAC 60 Hz and is required for operation of this device Installation precautions This remote is tested and safe when installed in accordance with this installation manual It is your responsibility to read all instructions before starting installation and to ...

Page 32: ...nce a location is chosen and the electrical box is installed proceed as follows Install the provided control wire from the fireplace to the switch location Use caution not to stress the wire around tight or sharp corners Do not run the control wire adjacent to existing or future phone data cable or electrical lines The wire should not come into contact with any part of the fireplace exterior with th...

Page 33: ... tap Use a soap solution to carefully check the pressure tap for leaks Up and Down Arrows Push to adjust set point temperature under automatic control AUX Auxiliary Button Button Press Turns on auxiliary power Button Press Turns off auxiliary power Can be operated independently of all functions Child Proof Mode To Enter Child Proof Mode Press the UpArrow Button twice and DownArrow Button once The ...

Page 34: ... and reattach the cover plate to the outer shell If the box is being wired from the INSIDE of the appliance Remove the screw attaching the junction box receptacle to the outer shell rotate the junction box inward to disengage it from the outer shell See Figure 10 6 Pull the electrical wires from outside the appliance through this opening into the valve compartment Feed the necessary length of wire...

Page 35: ...grilles Modifying or covering grilles could cause temperature rise and fire hazard Finishing materials must not interfere with Air flow through grilles or louvers Operation of louvers or doors Access for service 17 1 2 in Min 1 in Max 18 in Min 12 in Min 12 in Max COMBUSTIBLE TRIM NON COMBUSTIBLE FACING AND FINISHING MATERIAL Risk of Fire Non combustible clearances MUST be maintained 18 1 4 in 463 m...

Page 36: ...structions in manual Do NOT place embers directly over burner ports Replace ember material annually Improperly placed embers interferes with proper burner operation Placing the Ember Material Ember material is shipped with this gas appliance To place the ember material Embers CANNOT be placed directly over ports Care should be taken not to cover the lighting trail of ports from back to front When ...

Page 37: ...g CAUTION Logs are fragile Figure 12 1 1 6 5 4 3 2 Carefully remove the grate from the foam sup ports and then remove the foam supports from around the burner Figure 12 2 Place grate on the base of the firebox surround ing the burner The grate should be centered on the burner and pushed back until it contacts the burner Figure 12 3 2141 930 ...

Page 38: ...that the bottom of the log conforms with the contour of the burner The outside of the log should rest on the grate The front of the log will rest against the right andiron LOG 1 SRV2062 701 Place log 1 on the back of burner Rest log on back of the grate The notches located on the bot tom of the log should rest over the back corners of burner Figure 12 4 Figure 12 5 Figure 12 6 1 1 2 2 1 3 ...

Page 39: ...notch on the bottom of log 6 should rest on the wedge shape on the end of log 3 LOG 5 SRV330 704 Place the Y end of log 5 against the corre sponding bump on log 3 The other end of the log should rest in the second smooth cut out area on top of log 1 LOG 4 SRV330 706 Nest log 4 in the cut out area on the right side of log 1 The thinnest arm of log 4 rests on top of log 2 2 3 4 1 2 3 4 5 1 2 3 4 5 6...

Page 40: ...into the top latches Rotate the bottom of the glass door toward the firebox with slight upward pressure Latch the bottom spring latches securely onto the bottom glass door tabs G Burner Removal Only for Servicing Loosen the shutter adjustment wing nut and move the shutter to the closed position see Figure 12 10 Figure 12 10 Wing nut Remove the air baffle by removing the two screws at taching it to t...

Page 41: ...he air shutter To adjust loosen the wing nut Care should be taken when adjusting the air shutter so as not to cause the appliance to soot If sooting occurs the air shutter will need to be opened by sliding the handle to the left When finished tighten wing nut Replace the burner by first tipping the front of the burner up to get the burner neck started into the shutter sleeve see Figure 12 14 Once th...

Page 42: ...ement should be done by qualified technician Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to the owner s information manual provided with this appliance For assistance or additional information consult a qualified installer service agency or the gas supplier Do NOT use this appliance if any part has been under water Immediately call a q...

Page 43: ...O IF YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electric switch do not use any phone in your building DO NOT CONNECT LINE VOLT AGE 110 120 VAC OR 220 240 VAC TO THE CONTROL VALVE Improper installation adjustment al teration service or maintenance can cause injury or property damage Re fer to the owner s information manual provided with this appliance This appliance needs fres...

Page 44: ...rom remote control if absent or if appliance will not be used for an extended period of time Property damage possible from elevated temperatures CAUTION Fire Hazard Keep combustible materials gasoline and other flammable vapors and liquids clear of appliance Do NOT store flammable materials in the appliance s vicinity Do NOT use gasoline lantern fuel kerosene charcoal lighter fluid or similar liquids...

Page 45: ...ged into module Check voltage of transformer under load at spade connection on module with ON OFF switch in ON position Acceptable readings of a good transformer are between 3 2 and 2 8 volts AC b A shorted or loose connection in wir ing configuration or wiring harness Remove and reinstall the wiring harness that plugs into module Verify there is a tight fit Verify pilot assembly wiring to module Re...

Page 46: ... set at lowest range e Faulty module Turn ON OFF rocker switch or wall switch to OFF posi tion Remove ignitor wire I from module Place ON OFF Rocker switch or wall switch in ON position Hold ground wire about 3 16 inch away from I terminal on module If there is no spark at I terminal module must be replaced If there is a spark at I terminal module is fine Inspect pilot assembly for shorted sparker ...

Page 47: ... glass assembly with care Note Clean glass after initial 3 4 hours operation Longer operation without cleaning glass may cause a permanent white film on glass CAUTION When cleaning glass door Avoid striking scratching or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white film Do NOT clean glass when hot Turn off appliance after 3 4 hours of operation and ALLO...

Page 48: ...rebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for plugged ports corrosion or deterioration Replace burner if necessary 3 Replace ember materials with new dime size and shape pieces Do not block ports or obstruct lighting paths 4 Check for smooth lighting and ignition carryover to all port...

Page 49: ... Use for reference only For framing dimensions and clearances refer to Section 3 Figure 16 1 Appliance Dimensions Location Inches Millimeters L 37 1 4 945 M 8 3 8 212 N 30 1 2 776 O 36 1 8 916 P 41 1043 Q 17 7 8 455 R 33 1 2 852 S 52 1321 T 2 1 4 56 U 5 126 V 34 1 2 876 Location Inches Millimeters A 17 1 4 437 B 1 24 C 31 3 8 798 D 16 1 4 413 E 9 3 8 238 F 8 202 G 20 1 2 521 H 59 1 2 1511 I 2 1 8 ...

Page 50: ...mm 8 in 203 mm 6 in 152 mm 10 in 254 mm 1 1 2 in 38 mm 5 in 127 mm 12 in 305 mm UP DVP HVS Vent Support DVP WS Wall Shield Firestop DVP FS Ceiling Firestop DVP45 45 Elbow DVP Pipe see chart Effective Height Length 4 7 8 in 276 mm 13 mm Assembled Height 24 in 610 mm Diameter 10 in 254 mm DVP AS2 Pipe Effective Length Inches Millimeters DVP4 4 102 DVP6 6 152 DVP12 12 305 DVP24 24 610 DVP36 36 914 DV...

Page 51: ...eld is designed to be used on a wall 4 in to 7 1 4 in 102 mm to 184 mm thick If wall thickness is less than 4 in 102 mm the existing heat shields must be field trimmed If wall thickness is greater than 7 1 4 in 184 mm a DVP HSM B will be required Heat Shield B Vent Components Diagrams continued Figure 16 3 DVP vent components Term Cap Minimum Effective Length Maximum Effective Length Trap1 4 1 8 i...

Page 52: ...in 625 mm 13 1 4 in 367 mm RF12M Roof Flashing Multi pak BEK Trap Cap Brick Extension 13 3 4 in 349 mm 5 in 127 mm 13 3 4 in 349 mm Cap Shield DRC RADIUS 13 7 8 in 352 mm 9 1 2 in 241 mm 14 in 356 mm COOL ADD Cap Shield 11 5 8 in 295 mm 5 3 4 in 146 mm 7 1 8 in 181 mm 12 1 8 in 308 mm DVP TRAPFL DVP HSM B Extended Heat Shield 7 1 4 in 184 mm 5 1 4 in 133 mm 12 1 2 in 318 mm DVP TVHW VerticalTermin...

Page 53: ...l purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier The warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupancy date The warran...

Page 54: ... FKDQJHV LQ FRORU RI LQWHULRU DQG H WHULRU VXUIDFH ILQLVKHV PD RFFXU 7KLV LV QRW D IODZ DQG LV QRW FRYHUHG XQGHU ZDUUDQW DPDJH WR SULQWHG SODWHG RU HQDPHOHG VXUIDFHV FDXVHG E ILQJHUSULQWV DFFLGHQWV PLVXVH VFUDWFKHV PHOWHG LWHPV RU RWKHU H WHUQDO VRXUFHV DQG UHVLGXHV OHIW RQ WKH SODWHG VXUIDFHV IURP WKH XVH RI DEUDVLYH FOHDQHUV RU SROLVKHV 5HSDLU RU UHSODFHPHQW RI SDUWV WKDW DUH VXEMHFW WR QRUPDO Z...

Page 55: ...______________________________________________________________________ ________________________________________________________________________________ ________________________________________________________________________________ DO NOT DISCARD THIS MANUAL CAUTION Leave this manual with party responsible for use and operation Important operating and maintenance instructions included Read unders...

Reviews: