33
Heat & Glo • SL-5F-IFT, SL-7F-IFT Installation Manual • 2638-980 Rev. H • 6/22
Top Vent
• Remove top seal cap and insulation if equipped.
See Section 6, “Appliance Preparation.” Attach the
DV-46DVA-GCL adapter to the appliance starting collar
with 3-1/2 in. self-tapping screws. See Figure 4.29.
Rear Vent
• Remove the rear seal cap and insulation if equipped.
Connect the DVP-2SL adapter to the vertically positioned
elbow. Follow installation instructions included with DVP-
2SL kit. Secure DV-46DVA-GCL adapter to DVP-2SL
with 3-1/2 in. self-tapping screws. See Figure 4.29.
WARNING!
Risk of Fire, Explosion or Asphyxiation!
Do NOT connect this gas appliance to a chimney flue
serving a separate solid fuel or gas burning appliance.
• Could impair safe operation of this appliance or other
appliances connected to the flue.
• Vent this appliance directly outside.
• Use separate vent system for this appliance.
Connecting the LINK-DV30B to the DV-46DVA-GCL
adapter
• Insert the two sections of flexible vent pipe down the
existing chimney.
• Attach one 3 ft
section of stainless steel flex pipe to the
exhaust collar on top of the DV-46DVA-GCL adapter with
three screws.
• Attach one section of flexible vent pipe to the 3 ft s
tainless
steel flex pipe with three self-tapping screws.
• Attach one section of flexible vent pipe to the inlet collar
on top of the DV-46DVA-GCL adapter with three self-
tapping screws.
• To minimize cold air drafts, seal around the flex vents
at the damper inside the chimney with non-combustible
unfaced fiberglass or rock wool insulation.
The DV-46DVA-GCL adapter must be recessed into existing
masonry fireplace. This measurement is taken from the top
of the fireplace opening. See Table 1 and Figure 4.28.
Figure 4.29
EXISTING CHIMNEY
HEARTH
FLOOR
EXISTING CHIMNEY
EXHAUST AIR
VENT PIPE
INLET AIR
VENT PIPE
To minimize cold air
drafts, seal with
non-combustible
insulation.
TERMINATION CAP
DIRECT VENT FIREPLACE
V
COAXIAL/COLINEAR
APPLIANCE CONNECTOR
The first 3 feet of
exhaust flue must
be stainless flex
pipe (768-380A).
TERMINATION CAP
EXISTING CHIMNEY
EXISTING CHIMNEY
EXHAUST AIR
VENT PIPE
V
FLOOR
HEARTH
H
To minimize cold air
drafts, seal with
non-combustible
insulation.
DIRECT VENT FIREPLACE
DVP-2SL
COAXIAL/COLINEAR
APPLIANCE CONNECTOR
INLET AIR VENT PIPE
The first 3 feet of
exhaust flue must be
stainless flex pipe
(768-380A).
TOP VENT
REAR VENT
V
Minimum
10 ft
3.05 m
Maximum
40 ft
12.2 m
V
H
Minimum
10 ft
3.05 m
0 ft
0 mm
Maximum
40 ft
12.2 m
2 ft
610 mm
NOTICE:
To achieve optimum perfor-
mance of appliance, minimize or avoid
bends in exhaust vent pipe.
CAUTION! DO NOT
use any flue restric
-
tor when venting with the DV-46DVA-GCL
adapter and LINK-DV30B kit.
This could
result in poor flame appearance, sooting,
pilot malfunction, or overheating.
Connecting the DV-46DVA-GCL Adapter to Appliance