Heat & Glo • RHW-415 & RHW-485 • 33221 Rev K • 08/05
12
E. Construct the Chase
A chase is a vertical boxlike structure built to enclose the
fi replace and/or its vent system. Vertical chimneys that run
on the outside of a building may be, but are not required to
be, installed inside a chase.
Construction of the chase may vary with the type of build-
ing. These instructions are not substitutes for the require-
ments of local building codes. Local building codes MUST
be checked.
Chases should be constructed in the manner of all outside
walls of the home to prevent cold air drafting problems. The
chase should not break the outside building envelope in any
manner.
Building codes require false ceiling and ceiling fi restops at
each fl oor of the chase or every 10 ft (3.05 m) of clear space
to control spread of fi re.
Walls, ceiling, base plate and cantilever fl oor at the fi rst level
of the chase should be insulated. See Figure 3.5. Vapor and
air infi ltration barriers should be installed in the chase as per
regional codes for the rest of the home. Additionally, Hearth
& Home Technologies recommends that the inside surfaces
be sheet rocked and taped for maximum air tightness.
Ceiling
Firestop
Metal Chase Top
Round Termination Cap
False Ceiling
Insulation in the
outside walls
of the chase
Attic
Insulation
Shield
Chimney
Ceiling
Firestop
Tabs
False Ceiling
False Ceiling
Insulation
Insulation
Figure 3.5
Chase Assembly
F. Chimney Requirements
When planning your fi replace location, the chimney con-
struction and necessary clearances must be considered.
The fi replace system and chimney components have been
tested to provide fl exibility in construction. Vertical distances
are measured from the base of the fi replace as shown in
Figure 5.2.
1
2
3
All outside walls MUST be insulated.
Figure 3.6
Chase Constructions
1. Fireplace and chimney enclosed in an exterior chase.
2. Chimney offset through exterior wall and enclosed in
chase.
3. Chase constructed on roof.
Gas line holes and other openings should be caulked with
high temperature caulk or stuffed with unfaced fi berglass in-
sulation. If the fi replace is being installed on a cement slab,
we recommend that in cold climates, a sheet of plywood or
other raised platform be placed underneath to prevent con-
ducting cold up into the room.
Three examples of chase applications are shown in Fig-
ure 3.6.
• Minimum overall straight height
16.5 ft
(5.03 m)
• Minimum height with offset/return
16.5 ft
(5.03 m)
• Maximum height
90 ft
(27.43 m)
• Maximum chimney length between an offset
and return
20 ft
(6.1 m)
• Maximum distance between chimney
stabilizers
35 ft
(10.67 m)
• Double offset/return minimum height
20 ft
(6.1 m)
• Maximum unsupported chimney length
between the offset and return
6 ft
(1.83 m)
• Maximum unsupported chimney height above
the fi replace
35 ft
(10.67 m)
• Maximum unsupported chimney above roof
6 ft
(1.83 m)
Note:
A maximum of two pairs of offsets and returns may
be used.