background image

9

3

Installing the Appliance

Step 1.  Locating the Appliance

Space and clearance requirements for locating the appli-

ance within a room (see Figure 2).

Minimum Clearances

 from the Appliance to Combustible Materials

Inches

mm

Sides .................................. 9 ..................... 229
Floor ................................... 0 ....................... 0
Rear .................................... 3 ...................... 76
Ceiling* .............................. 45 .................... 1143

The distance from the unit to combustible construction is to

be measured from the unit outer wrap surface to the com-

bustible construction, 

NOT

 from the screw heads that se-

cure the unit together.
For minimum clearances of direct vent termination (see Fig-

ures 19 and 20).

Minimum Clearances

 from the Vent Pipe to Combustible Materials

Inches

mm

Vertical Sections

. ............. 1 ................ 25

Horizontal Sections

Top ..................................... 3 ................ 75
Bottom ............................... 1 ................ 25
Sides ................................. 1 ................ 25

At Wall Firestops

Top .................................. 2 1/2 ............ 63.7
Bottom .............................. 1/2 ............... 13
Sides ................................. 1 ................ 25

* The clearance to the ceiling is measured from the top

of the unit, excluding the standoffs (see Figure 25).

   Figure 2.    Appliance Dimensions, Locations

                     and Space Requirements

Constructing the Chase

A chase is a vertical box-like structure built to enclose the

gas fireplace and/or its vent system. Vertical vents that run

on the outside of a building may be, but are not required to

be, installed inside a chase.

CAUTION:

 TREATMENT OF FIRESTOP SPACERS AND

CONSTRUCTION OF THE CHASE MAY VARY WITH THE

TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT

SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL

BUILDING CODES. THEREFORE, YOUR LOCAL BUILD-

ING CODES 

MUST

 BE CHECKED TO DETERMINE THE

REQUIREMENTS FOR THESE STEPS.

Factory-built fireplace chases should be constructed  in the

manner of all outside walls of the home to prevent cold air

drafting problems. The chase should not break the outside

building envelope in any manner.

This means that the walls, ceiling, base plate and cantilever

floor of the chase should be insulated. Vapor and air infiltra-

tion barriers should be installed in the chase as per regional

codes for the rest of the home. Additionally, Heat-N-Glo rec-

ommends that the inside surfaces be sheetrocked and taped

for maximum air tightness.

To further prevent drafts, the firestops should be caulked to

seal gaps. Gas line holes and other openings should be

caulked or stuffed with insulation. If the unit is being in-

stalled on a cement slab, we recommend that a layer of

plywood be placed underneath to prevent conducting cold

up into the room. Be sure to include spark arrestors for

woodburning units if they are required.

THE CHASE SHOULD BE CONSTRUCTED SO THAT ALL

CLEARANCES TO THE FIREPLACE ARE MAINTAINED

AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.

Clearance Requirements

The top, back, and sides of the appliance are defined by stand-

offs. The minimum clearance to a perpendicular wall extending

past the face of the appliance is four inches (102 mm).

ALCOVE INSTALLATION

CORNER INSTALLATION

1 MIN.

3 MIN.

4 MIN.

CEILING

(45 MIN. - TOP OF UNIT)

48 MIN.

9 MIN.

3 MIN.

48 MIN.

Summary of Contents for Bay-stove

Page 1: ...PPLIANCE FOR FUTURE REFERENCE 1 This appliance may be installed in an af termarket permanentlylocated manufac tured mobile home wherenotprohibited by local codes 2 Thisapplianceisonlyfor usewiththetype of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used Please contact your Heat N Glo dealer with any questions or concerns Fo...

Page 2: ...NDERSTAND all instructions carefully before starting the installation FAILURE TO FOLLOW these installation instructions may result in a possible fire hazard and will void the warranty Prior to the first firing of the fireplace READ the Using Your Fireplace section of the Owners Guide DO NOT USE this appliance if any part has been under water Immediately CALL a qualified service technician to inspe...

Page 3: ... 11 A Vent System Approvals 11 B Installing Vent Components 16 C Vent Termination 19 Step 3 The Gas Control System 22 Step 4 The Gas Supply Line 22 Step 5 Gas Pressure Requirements 22 Step 6 Wiring the Appliance 23 Step 7 Finishing 24 Step 8 Positioning Logs Ember Material and Glass Doors 25 Glass Door Removal 25 Placing the Ember Material 25 Glass Specifications 25 Positioning the Logs 26 Step 9 ...

Page 4: ...y SGS ICS Appliance Certification The Heat N Glo appliance model discussed in this Installers Guide has been tested to certification standards and listed by the applicable laboratories Certification MODEL BAY STOVE LABORATORY Underwriters Laboratories TYPE Direct Vent Gas Fireplace Heater STANDARD ANSI Z21 88 CSA2 33 UL307B NOTE ALL MODELS ARE UL LISTED TO UL307B THE STANDARD FOR GAS BURNING HEATI...

Page 5: ... Follow these instructions carefully during the installation to ensure maximum safety and benefit Failure to follow these instructions will void the own er s warranty and may present a fire hazard The Heat N Glo Warranty will be voided by and Heat N Glo disclaims any responsibility for the following actions Installation of any damaged gas appliance or vent sys tem component Modification of the gas...

Page 6: ...CESS FOR GAS CONNECTION VENT COLLARS TOP GRILLE GLASS DOOR LABELS BEHIND LOWER GRILLE BASE 34 3 8 873mm 9 1 2 242mm 9 7 8 251mm 17 1 4 448mm 30 762mm 17 1 2 445mm 9 9 16 243mm 11 1 2 292mm VENT COLLARS 6 5 8 168mm 25 1 4 640mm 19 1 8 486mm ...

Page 7: ...ES FOR THE REQUIREMENTS OF LOCAL BUILDING CODES THEREFORE YOUR LOCAL BUILD ING CODES MUST BE CHECKED TO DETERMINE THE REQUIREMENTS FOR THESE STEPS Factory built fireplace chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems The chase should not break the outside building envelope in any manner This means that the walls ceiling base plate...

Page 8: ... 4 inch inner pipe 6 5 8 inch outer pipe SL 17 24D 17 24 432 610mm 11 3 4 298mm SL 12D 6 1 2 165mm 6 5 8 168mm 5 4 3 146mm SL 06D SL 09D SL 12 17D SL 24D SL 36D SL 48D 8 3 4 222mm 12 17 305 432mm 23 3 4 603mm 35 3 4 908mm 47 3 4 1213mm 6 5 8 168mm 9 5 8 244mm 6 3 8 162mm 6 3 8 162mm 6 1 2 165mm SL 90D 9 5 8 244mm ...

Page 9: ...S OR COMPONENTS MAY BE USED Termination Kits SLK 01D SLK 991DA Detailed installation instructions are included with each vent termination kit and should be used in conjunction with this Installers Guide Identifying Vent Components The vent systems installed on this gas appliance may in clude one two three or four 90 elbow assemblies The relationships of vertical rise to horizontal run in vent con ...

Page 10: ... MIN 24 MAX 914MM 7 2M Figure 6 Venting with One 90 Elbow V FT H FT 3 MIN 914mm 2 MAX 610mm 6 MIN 1 8m 4 MAX 1 2m 9 MIN 2 7m 6 MAX 1 8m 20 MAX 6 2m 20 MAX 6 2m Rise to Run up to 9 FT Vertical Ratio 3 2 Rise to Run above 9 FT Vertical Ratio 1 1 VENTING WITH ONE 1 90 ELBOW H V V CAP ...

Page 11: ...s VENTING WITH TWO 2 90 ELBOWS V H H H1 FT M FT M FT M 4 MIN 1 2m 2 MAX 610mm 2 MAX 610m 20 MAX 6 2m 20 MAX 6 2m 20 MAX 6 2m Rise to Run up to 9 FT Vertical Ratio 2 1 Rise to Run above 9 FT Vertical Ratio 1 1 V V1 20 MAX 6 2m H1 V1 H V H V ...

Page 12: ...elbows V H H H1 FT M FT M FT M 4 MIN 1 22m 2 MAX 6m 2 MAX 6m 20 MAX 6 2m 20 MAX 6 2m Rise to Run up to 9 FT Vertical Ratio 2 1 Rise to Run above 9 FT Vertical Ratio 1 1 VENTING WITH THREE 3 90 ELBOWS V V1 20 MAX 6 2m H H1 V1 V V H H1 V1 ...

Page 13: ...h four 90 elbows Rise to Run up to 9 FT Vertical Ratio 2 1 Rise to Run above 9 FT Vertical Ratio 1 1 V V1 V2 20 MAXIMUM 6 2M H H1 H2 20 MAXIMUM 6 2M VENTING WITH FOUR 4 90O ELBOWS V 5 FT 1 6M MINIMUM V2 H1 V H V1 H2 V1 H1 H V ...

Page 14: ...omponents into place by sliding the con centric pipe sections with four 4 equally spaced interior beads into the appliance collar or previously installed com ponent end with four 4 equally spaced indented sections When the internal beads of each 6 5 8 inch 168mm outer pipe line up rotate the pipe section clockwise about one quarter 1 4 turn Theventpipeisnowlockedtogether Figure 10 Attaching the Fi...

Page 15: ...vent passes To install firestops for horizontal runs that pass through either interior or exterior walls Cut a 10 X 10 254mm X 254mm hole through the wall NOTE The center of the hole is one 1 inch 25 4mm above the center of the horizontal vent pipe Position the firestops on both sides of the hole previ ously cut and secure the firestops with nails or screws The heat shields of the firestops MUST B...

Page 16: ...using the centerpoint previously marked Frame the hole with framing lumber the same size as the ceiling joists Figure 16 Ceiling Firestop Ceiling Side If the area above the ceiling is NOT an attic position and secure the ceiling firestop on the ceiling side of the previously cut and framed hole Figure 15 Hole New Framing Members If the area above the ceiling IS an attic position and secure the fir...

Page 17: ...INTING UP For roundcap termination kits Use the exterior pipelock hole on the round flange of the wall firestop to secure the vent pipe in place Figure 18 Round Termination Cap WARNING THE BOTTOM OF THE VENT TERMINATION CAP MUST BE A MINIMUM OF 12 INCHES 305 MM ABOVE GROUND LEVEL GRADE THE TOP OF THE CAP MUST BE A MIN IMUM OF 18 INCHES 457MM BELOW COMBUS TIBLE MATERIAL SUCH AS A DECK THE SIDE OF T...

Page 18: ...door that may be opened C 9 U S A 12 Canada clearance to permanently closed window D 18 vertical clearance to ventilated soffit located above the termi nal within a horizontal distance of 2 feet 60 cm from the cen ter line of the terminal E 18 clearance to unventilated soffit F 9 clearance to outside corner G 6 clearance to inside corner H 3 ft Canada not to be installed above a gas meter regulato...

Page 19: ...E FOLLOWING DIAGRAM FOR MINIMUM HEIGHTS PROVIDED THE TERMI NATION CAP IS AT LEAST TWO 2 FEET FROM A VERTICALWALLAND 2 FEET BELOWA HORIZON TAL OVERHANG NOTE This also pertains to vertical vent systems in stalled on the outside of the building Roof Pitch H min ft flat to 6 12 1 0 6 12 to 7 12 1 25 over 7 12 to 8 12 1 5 over 8 12 to 9 12 2 0 over 9 12 to 10 12 2 5 over 10 12 to 11 12 3 25 over 11 12 ...

Page 20: ...r Heat N Glo gas appliances are shown in the table below Pressure Natural Gas Propane Minimum 5 0 inches 11 0 inches Inlet Pressure w c w c Maximum Inlet 14 0 inches 14 0 inches Gas Pressure w c w c Manifold 3 5 inches 10 0 inches Pressure w c w c A one eighth 1 8 inch 3 mm N P T plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the ...

Page 21: ...ISCONNECT REMOTE CONTROLS IF AB SENT FOR EXTENDED TIME PERIODS THIS WILL PRE VENT ACCIDENTAL FIREPLACE OPERATION Figure 23 Standing Pilot Ignition Wiring Diagram For Standing Pilot Ignition Wiring Appliance Requirements This appliance DOES NOT require 110 120 VAC to operate WARNING DO NOT CONNECT 110 120 VAC TO THE GAS CONTROL VALVE OR WALL SWITCH OR THE APPLIANCE WILL MALFUNC TION AND THE VALVE W...

Page 22: ...ny finishing material on the Vent Cap Figure 25 Combustible above Appliance Figure 24 Fan Wiring Diagram FAN TEMPERATURE SENSOR SWITCH SPEED CONTROL RHEOSTAT JUNCTION BOX NOTE IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE 105 C RATED WIRE O JUNCTION BOX VARIABLE SPEED CONTROL TEMPERATURE SENSOR SWITCH WHT GRN BLK BLK 110 120 VAC BLOWER BL...

Page 23: ... foreign mate rial from the orifice or tubing When the appliance is put back in service check burner flame patterns with Figure 26 Step 8 Positioning Logs Ember Material and Glass Doors Placing the Ember Material Ember material is shipped with this gas appliance The bag labeled Golden Embers GE 93 is flame colorant material The bag labeled Glowing Ember 050 721 is standard glowing ember material T...

Page 24: ... edge of Log 1 3 Grasp Log 3 with the bark side up and the burned sections facing towards the left Place the rear of the twig against the long tab at the rear of the log grate and rest it on the right edge of Log 2 4 Place Log 4 on top of the base log 1 so that the burned sections line up with each other Keep this log as far back on the large log as possible 5 Place the burned tip of log 5 on top ...

Page 25: ...ake a few minutes for the lines to purge themselves of this air Once the purging is complete the appliance will light and will operate normally Subsequent lightings of the appliance will not require this purging of air from the gas supply lines unless the gas valve has been turned to the OFF position in which case the air would have to be purged NOTE The appliance should be run 3 to 4 hours on the...

Page 26: ...vice technician Task Brush or vacuum the control compartment logs and burner areas surrounding the logs Checking Flame Patterns Flame Height Frequency Periodically By Qualified service technician Home owner Task Make a visual check of your appliance s flame patterns Make sure the flames are steady not lifting or floating See Figure 28 The thermopile thermocouple tips should be covered with flame s...

Reviews: