PATIO CAMPFIRE INSTALLATION INSTRUCTIONS

2. Enclosures for LP Gas Supply Systems

If you build an enclosure for an LP gas cylinder, follow these recommended specifications and you must follow local codes.

a.

Enclosures for LP gas supply cylinders must be ventilated by openings at the level of the cylinder valve and at floor level. The
effectiveness of the opening(s) for purposes of ventilation must be determined with the LP gas supply cylinder(s) in place.
This must be accomplished by one of the following:

1)

One side of the enclosure must be completely open or,

2)

For an enclosure having four sides, a top and bottom:

At least two ventilation openings at cylinder valve level shall be provided in the side wall, equally sized, spaced at
180 degrees (3.14 rad), and unobstructed. Each opening must have a total free area of not less than 1/2 square inch
per pound (3.2 sq. cm/kg) of stored fuel capacity and not less than a total free area of 10 square inches (64.5 sq. cm).

Ventilation opening(s) must be provided at floor level and shall have a total free area of not less than 1/2 square inch
per pound (3.2 sq. cm/kg) of stored fuel capacity and not less than a total free area of 10 square inches (64.5 sq. cm).
If ventilation openings at floor level are in a side wall, there must be a least two openings. The bottom of the
openings must be at floor level and the upper edge can’t be more than 5 in. (127 mm) above the floor. The openings
must be equally sized, spaced at 180 deg (3.14 rad) and unobstructed.

Every opening must have minimum dimensions to permit the entrance of a 1/8 inch (3.2 mm) diameter rod.

b.

Cylinder valves must be readily accessible for hand operation. A door on the enclosure to gain access to the cylinder valves
is acceptable, provided it is non-locking and can be opened without the use of tools.

c.

There must be a minimum clearance of 2 in. (50.8 mm) between the lower surface of the floor of the LP gas supply cylinder
enclosure and the ground.

d.

The design of the enclosure must be such that:

1)

The LP gas supply cylinder(s) can be connected, disconnected and the connections inspected and tested outside the
cylinder enclosure.

2)

Those connections which could be disturbed when installing the cylinder(s) in the enclosure can be leak tested inside
the enclosure.

3)

Be certain to mount or set the LP gas cylinder on a flat stable surface and retain it to prevent it from tipping.

e.

Purge the gas supply line of any trapped air prior to the first firing of the appliance!

WARNING!

Due to the initial purging and subsequent lightings, NEVER allow the gas valve to remain in the “OPEN” position
without first placing a burning match on the top of the burner.

Summary of Contents for PATIO CAMPFIRE

Page 1: ...r s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier IMPORTANT Read al...

Page 2: ...nclosed area WARNING This log set must NOT be installed in an unvented appliance WARNING This appliance is not for use with solid fuel Rock Ring The following clearances to combustibles must be mainta...

Page 3: ...ng it into service It is recommended that cylinders that have not been used for extended periods of time also be purged before use Clothing or other flammable materials should not be placed on or near...

Page 4: ...CAMPFIRE INSTALLATION INSTRUCTIONS C COMPONENTS AND INSTALLATION The burner assembly and log assembly are packaged individually and shipped in one carton See illustrations below Burner Assemblies Log...

Page 5: ...d completely off clockwise 2 Ensure the tank valve has the proper external mating threads tank valve marked USE WITH TYPE 1 3 Inspect the hose shipped with the appliance for any damage Do not use if t...

Page 6: ...penings at floor level are in a side wall there must be a least two openings The bottom of the openings must be at floor level and the upper edge can t be more than 5 in 127 mm above the floor The ope...

Page 7: ...oken components b Position the log base over the burner making sure to align the dimple in the log base over the locating button on the burner top see burner assemblies page 4 c Position the logs by p...

Page 8: ...r s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to turn the gas control knob or valve Never use tools If the valve will not turn by hand don t try...

Page 9: ...likely to occur when using LP gas The soot should be cleaned off the surface of the logs periodically to prevent excessive buildup To clean the logs be sure the fire is out the gas supply is turned o...

Page 10: ...10 4004 001 Rev C 08 04 PATIO CAMPFIRE INSTALLATION INSTRUCTIONS G REPLACEMENT PARTS Log Assembly Log 1 Log 2 Log 3 Log 4 Log Base...

Page 11: ...2 Burner Assembly 35323 1 Y 3 Burner Weldment 35324 1 N 3 Burner Neck Gasket 17196 1 N 4 SMS 8x1 2 S Grip BO 12460 2 Y 5 Burner Neck Assembly 34465 1 Y Natural Gas Flex Tube Assembly 35326 1 Y LP Gas...

Page 12: ...d before Hearth Home Technologies has been afforded a reasonable opportunity to inspect the Product This warranty is limited to the replacement or repair of defective components or workmanship and Hea...

Reviews: