28
Heat-Timer Corp.
Weekday
Cycle
Set Point
Saturday
• No Vari-Boost as the Day #1 is not programmed
• Day Cutoff, Day Heat Adjustment, and Day Space
Target are maintained from 8 AM until before 4 PM
• Early Shutdown starts before 4 PM and ends at 4 PM
• Night Cutoff, Night Heat Adjustment, and Night Space
Target are maintained from 4 PM until before 6 AM
Monday morning
• No Boost will take effect
• Day Cutoff and Set Point are maintained from 8 AM until
before 4 PM
• No Early Shutdown will take effect
• Night Cutoff and Set Point less Setback are maintained
from 4 PM until before 6 AM Monday morning
Sunday
• Night Cutoff, Night Heat Adjustment, and Night Space
Target are maintained all Sunday until before 6 PM
• Night Cutoff and Set Point less Setback are maintained
all Sunday until before 6 AM Monday morning
♦
If no space sensors with space average are available the Vari-Boost will end at the Day #1 time setting. However, if space sensors with
space average are available and Space Lock was enabled, the Vari-Boost can extend up to 1 hour past the Day #1 setting.
ALERT
When working with MPCQ Platinum Internet communication with Space Lock enabled, the Boost can extend to
an additional hour past the Day #1 setting if Day Space Target was not reached within the Boost period.
Copy Schedule
SELECT:
Settings/Schedules/Copy Schedule
• To reduce the need for setting each weekday time schedule, this feature has been
made to allow the copying of the Monday schedule settings to the reset of the week.
------ SCHEDULES ------
Copy Mon Schedules
To All Other Days
(Select to Execute)
-- DATE & TIME --
Date WED 01/05/08
Time
6:56 Am
Set Date and Time
SELECT:
Settings/Schedules/Set Date & Time
• The Date and Time will need to be set n the startup process of the MPCQ Platinum.
• Selecting Date will allow you to set the year followed by the month then finally the day.
• Adjust the time by selecting Time from the menu and then scrolling through the hours followed by the minutes.
• Pay attention to the AM/PM when adjusting the hours.
• Internet controls will receive their date and time based on their Internet configured building time zone automatically.
ALERT
Remember that the battery is the only backup for the Date and Time. If no power is supplied to the MPCQ Platinum
and there was no battery or battery had no power, date and time values will be lost and will need to be re-entered.
Vacation Schedule Setting
(Available with RINet (Internet Communication Controls Only)
• The vacation Space Target and settings can only be set on the Internet
ICMS website.
• The MPCQ Platinum offers a Vacation Schedule which provide the
user with an adjustable lower space target that can be maintained
between two specified date/time periods. See Vacation Schedule on