16
PREPARATION
RETURN
SOLAR PANEL
CIRCULATOR
GAUGE
FOR SOLAR SENSOR
DRY WELL
LINE
EXHAUST VENT
INTAKE AIR
AIR VENT
BALL
VALVE
BACKFLOW
LINE
VALVE MANUFACTURER.
DRAIN VALVE
TEMP/PRESSURE
EXPANSION
PREVENTER
SOLAR
(see note 4)
DRAIN
COLD WATER
MIXING VALVE SHOWN.
CLOSED LOOP
RELIEF VALVE
VENT
OUTLET
MANUAL
FOR OTHER VALVES, CONSULT
PANEL
TANK
COLD IN
AUXILIARY
HOT WATER
VALVE
HOT OUT
CONNECTION
AUXILIARY
CONNECTION
TANK
RE-CIRCULATED
CONDENSATE
SUPPLY
GAS
EXPANSION
INLET
TEMP/PRESSURE
SOLAR PANEL
SPARCO AQUAMIX
EXPANSION
CONDENSATE
AUXILIARY
TEMP/PRESSURE
FOR OTHER VALVES, CONSULT
CONNECTION
LINE
VALVE MANUFACTURER.
MANUFACTURER FOR PROPER SIZING
BALL
INTAKE AIR
TANK
COLD IN
SOLAR
PANEL
RELIEF VALVE
AIR
RE-CIRCULATED
GAS
(see note 4)
CIRCULATOR
HOT WATER
HOT OUT
COLD WATER
INLET
AIR VENT
AUXILIARY
CONNECTION
SOLAR PANEL
RETURN
SOLAR PANEL
SUPPLY
GAUGE
TEMP/PRESSURE
HANDLER *
VALVE
VENT
EXHAUST VENT
MANUAL
OUTLET
CLOSED LOOP
PREVENTER
VALVE
BACKFLOW
DRAIN VALVE
DRY WELL
FOR SOLAR SENSOR
TANK
EXPANSION
( see note 4)
CIRCULATOR
DRAIN
LINE
SPARCO AQUAMIX
MIXING VALVE SHOWN.
*
C
HECK WITH AIR HANDLER
PHOENIX SOLAR PIPING WITH AIR HANDLER
PHOENIX SOLAR PIPING
NOTES:
1. Minimum pipe size should match connection size on Phoenix. If you require greater flow, upsize the pipe accordingly.
2. A Thermal Expansion tank suitable for potable water must be sized and installed within this piping system between the check
valve and the cold water inlet of the Phoenix.
3. Gas Line must be rated to the maximum input capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
NOTES:
1. Minimum pipe size should match connection size on Phoenix. If you require greater flow, upsize the pipe accordingly.
2. A Thermal Expansion tank suitable for potable water must be sized and installed within this piping system between the check
valve and the cold water inlet of the Phoenix.
3. Gas Line must be rated to the maximum input capacity of the unit. Unit must have 10 feet of pipe after gas regulator.
4. All circulators shall have an integral flow check.
LP-201-A
7/16/07
LP-179-R
7/16/07