ORIFICE INSTALLATION 

 

 

All burners are equipped with an orifice set at the minimum firing rate (except for OEM 

packaged units).  Drilling the orifice increases the firing rate.  To drill the orifice, first open the 

union and then unscrew the orifice from inside the union.  Determine the proper orifice size for 

the desired firing rate and drill the orifice (see Chart 5).  Replace the orifice in the union and 

tighten the union so that it is gas tight.  Once installed, a higher or lower firing rate can be 

achieved by raising or lowering the manifold pressure by +/- 0.3”.  Pressure changes can only be 

made when the burner is running.  The typical working manifold pressure for natural gas is

 3.5” 

W.C. (2.3” W.C. for LP).  The maximum inlet pressure at the gas valve is 11” W.C.; the 

minimum is 

5” W.C. (for the purpose of input adjustment). 

Note: The manifold pressure may vary for OEM packaged units. 

 

Chart 5: Burner Orifice Sizing For Natural Gas And LP* 

Orifice Size 

(inches) 

Drill 

Size 

Manifold Pressure at 3.5” 

W.C. for Nat Gas (BTU) 

Manifold Pressure at 2.3” 

W.C. for L.P. (BTU) 

Approximate 

Head Setting 

Approximate 

Air Setting 

5/32 

0.156 

50,000 

50,000 

21 

3/16 

0.188 

80,000 

80,000 

18 

7/32 

0.219 

90,000 

90,000 

12 

15/64 

0.234 

122,000 

122,000 

18 

14 

9/32 

0.281 

146,000 

146,000 

14 

11 

19/64 

0.297 

160,000 

160,000 

10 

10 

27/64 

0.422 

200,000 

200,000 

15 

1/2 

no 

orifice 

250,000 

250,000 

20 

* Assumes 0” to –0.02” Draft over fire 

 

 

 

INSTALLING THE CHIMNEY LINER, DRAFT DIVERTER AND 

VENT PIPE 

 

Some utilities require new chimney liners for all gas installations.  Use a corrosion resistant 

chimney liner (approved for gas service) of the same size as the vent pipe.  Use an CSA or U.L. 

listed draft diverter only if you can maintain draft over fire.  Otherwise, it is better to use a double 

swing draft regulator, listed by CSA or U.L.  When the burner is used as a conversion burner, 

draft over fire should be maintained as –0.02” W.C. by adjusting the regulator when the burner is 

fired.  The installer should follow the barometric draft regulator manufacturer’s instructions for 

complete details for installations and adjustments.  The vent pipe should extend only to (but not 

beyond) the inside wall of the chimney. 

Summary of Contents for SU-2A

Page 1: ...all the fire department A qualified installer service agency or the gas supplier must perform installation and service All installations must be made in accordance with all state and local codes which may differ from instructions in this manual The installer should inform and demonstrate to the user the correct operation and maintenance of the appliance The installer shall also inform the user of ...

Page 2: ...O2 or CO2 by the dial located on top of the burner housing which allows the air to flow more or flow less within the burner Two electrodes act as a sparker and a flame rod See Fig 1 Flame rectification by this flame rod monitors the continued presence of the burner flame With three trials for ignition consistency with Fenwal control trouble free safe operation is achieved Warning Should overheatin...

Page 3: ...oper operation of the burner AIR FOR COMBUSTION If the boiler or furnace room is unusually tight or if the house has a ventilation fan it is recommended that the combustion air be supplied to the furnace room through intakes from the outside of the building The intakes must terminate facing down in order to avoid obstruction from rain snow leaves etc Openings must have one square inch of free area...

Page 4: ...s such as tree limbs other buildings etc which may cause a down draft The chimney should be lined as required by the local Gas Company or local codes Some utilities require new chimney liners for all gas installations Use a corrosion resistant chimney liner approved for gas service of the same size as the vent pipe Fig 2 Chimney and Fresh Air Dimensions ...

Page 5: ...stalled is a conversion burner use a prefabricated chamber or build a firing chamber that can withstand 2000o F See Chart 2 on page 3 Measure the boiler or furnace mounting plate to determine the flame tube insertion required Deduct from the total length and tighten the flange on the flame tube with the deducted insertion depth The deduction will prevent the tip of the flame tube from burning off ...

Page 6: ...e blast tube into the boiler to the proper depth and tighten the two setscrews using a 4 mm allen key Seal off any free openings with either high temperature cement or high temperature silicone Picture 2 BODY FLANGE picture to the left First install the gasket and boiler flange to the boiler For heat exchangers with a diamond stud pattern one allen screw on the flange should be on the top slightly...

Page 7: ...tate codes 3 A gas union 4 A drip pipe Caution The gas valve should not be subjected to more than PSIG Therefore the burner should be isolated during high pressure gas leak tests The appliance and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of psig The appliance must be isolated from the...

Page 8: ...t 3 5 W C for Nat Gas BTU Manifold Pressure at 2 3 W C for L P BTU Approximate Head Setting Approximate Air Setting 5 32 0 156 50 000 50 000 21 0 3 16 0 188 80 000 80 000 18 2 7 32 0 219 90 000 90 000 12 6 15 64 0 234 122 000 122 000 18 14 9 32 0 281 146 000 146 000 14 11 19 64 0 297 160 000 160 000 10 10 27 64 0 422 200 000 200 000 3 15 1 2 no orifice 250 000 250 000 1 20 Assumes 0 to 0 02 Draft ...

Page 9: ... carrying lines do not power this Sometimes T T terminals are jumped with a wire nut for burners not set for post purge 3 Burner motor starts and pre purge begins 4 Burner housing pressurizes and proves air flow contacts closed Note if the contacts are closed before the motor starts blower motor runs continuously Diagnostic light flashes once every 3 seconds 5 At the end of pre purge ignition spar...

Page 10: ...e spark is energized for 4 seconds At the same time the 24 Volt transformer powers the gas valve allowing the fuel to flow 5 Within 4 seconds the flame should be established and proved The spark will shut off and the control will hold power to the gas valve until the limits open and the burner stops firing 6 If the flame is not established the blower motor continuously runs 7 To restart power shou...

Page 11: ...ms install manometers before and after the gas valve Keep the observation port of the boiler or furnace open Follow the instructions on the nameplate of the burner to turn it on Follow the sequence of operations for the control see pages 9 and 10 Use a combustion analyzer and record the readings below BURNER OPERATION Record the Readings at Steady State Draft over fire at steady state should be 0 ...

Page 12: ... compensate for backpressure in the combustion area up to 0 3 W C Caution If this is the case the flange and the combustion chamber should be completely sealed This pressure firing decreases as the firing rate increases See Graph 1 Note the burner should be adjusted while it is firing Graph 1 Chamber Pressure versus Firing Rate BTU 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 50 000 100 000 150 000 200...

Page 13: ...Polarity reversed Check power feed for broken polarity Bad earth grounding Fix the ground wire Gas pressure is too low Check the gas pressure and adjust to proper pressure 3 Pulsation at start First check the burner head location with respect to the end of the flame tube Adjust as necessary Gas pressure is too high Use manometer and readjust the pressures Blocked Flue Check draft and clear flue of...

Page 14: ...Blower motor D82132 20 Plastic Cover Plate 11850001 8 Shielding Plate Housing 21 Screw Long Special 11750702 9 Outside Air Boot 11859107 22 Airflow Switch Honeywell Tridelta 6041A 9A Silencer 11879302 23 Ignition Electrode 115 34708 10 Air Regulation Plate 11851001 24 Flame Rod 115 34707 11 Air Damper 11852201 25 Retention head 119 39701 12 Air Regulation Adjustment screw 11848501 26 Union 1139101...

Page 15: ...e user should do periodic visual checks of the burner and the flame 3 Laundry lint or dog and or cat hairs should not go inside the blower If they are seen they should be removed after disconnecting the power to the burner and cover parts should be installed before starting the burner 4 Keep the area around the conversion burner clear and free from combustible materials gasoline and other flammabl...

Page 16: ...16 ...

Reviews: