background image

 

Figure 5 

         

Combustion Air Opening

ID

Fan

Rectangular to 

Round adapter

Condensate 

Drain

AHU 

Cabinet

4 ft. Min.

12 in. Min

Field Starkap or equal 

listed Vent cap

 

 

 

Venting Indoor Installations 

 

Duct furnace module must be connected to a properly designed venting system to convey flue gases 
outside of the heated space. 
Category 1 Vent systems must be sized and installed in accordance with the National 
Fuel Gas Code, ANSI Z223.1 (NFPA 54) Chapter 13 in the United States or CAN/CGA-B149 Natural and propane 
gas installation code, Section 8 and Annex C, in Canada. A vent connector adaptor is available that transitions the 
induced draft fan outlet (rectangular) to round vent pipe. This adaptor must be installed on the outlet of the ID fan to 
provide a connection point for the vent pipe.  Vent pipe connector is sized based on furnace input as listed in Table 1. 

 

Vertically Vented Duct Furnaces 

– Category I     

 

Proper venting of the heating units is the responsibility of the installer. Venting materials are provided by others. 
UL Listed Type B Vent or single wall metal pipe may be used. 

If used, single wall vent pipe shall have seams and joints 

sealed with pressure sensitive aluminum tape or silicone rubber sealant, rated for 480 

o

F (249 

o

C) or higher. Joints should be 

secured with at least two corrosion resistant fasteners. 

  

 

Table 1-Vent Connector Sizing 

 

 

Models                 

 

            Input Rating (Btuh) 

Input Rating (W) 

    Vent Pipe Dia. 

 

HM(D,G) 050-175; HHG050-160                    50,000 

– 175,000 

   14653 

– 51287   

      5 in. (126 mm) 

HMG200-400, HMD200; HHG200-360 

  200,000 

– 400,000 

   58614 

– 117228 

      6 in. (152 mm) 

HM(A,B)150-400; HHA150-400    

  150,000 

– 400,000 

   43960 

– 117228 

      6 in. (152 mm) 

HM(A,B,G)500-600; HHA500; HHG440 

  440,000 

– 600,000 

  131881 

– 175842 

      7 in. (178mm) 

 

1.  Maximize the height of the vertical run of vent pipe. A minimum of five (5) feet (1.5m) of vertical pipe is required. 

The top of the vent pipe must extend at least 18 in. ( 457 mm) above the highest point on the roof. (Use Listed 
Type B vent for external runs).  

2.  An approved weatherproof vent cap must be installed to the vent termination. 
3.  Horizontal runs should be pitched upward 

¼” per foot (21mm/m) and should be supported at 3 foot (1m) 

maximum intervals. It is best to keep horizontal runs less than 75% of vertical height to avoid possible need to 
upsize vent pipe. 

4.  Design vent pipe runs to minimize the use of elbows. Each 90o elbow is equivalent to 5 feet (1.5m) to 7 feet 

(2.13m) of straight vent pipe run depending on pipe diameter. 

5.  Vent pipe should not be run through unheated spaces. If such runs cannot be avoided, insulate vent pipe to 

prevent condensation inside vent pipe. Insulation should be a minimum of 

½” (12.7mm) thick, foil faced material 

suitable for temperatures up to 500 

o

F (260 

o

C). 

6.  Dampers must not be used in vent piping runs. Spillage of flue gases into the occupied space could result. 
7.  Vent connectors serving Category 1 heaters must not be connected into any portion of a mechanical draft 

system operating under positive pressure. 

Caution! 

Flue gases must be directed 

away from combustion air 

inlets, to avoid recirculation 

into combustion air supply. 

 

Summary of Contents for HH SERIES

Page 1: ...or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any ph...

Page 2: ...rt up 11 Manifold Pressure Adjustment 11 Gas Valves 12 Burner Flames 13 Shutdown 13 Normal Operation 13 Safety and Ignition Controls 14 Annual Maintenance Inspection 14 15 Installation Requirements Al...

Page 3: ...ent and maintenance of the furnace installed Provide at least 36 0 9m clearance for removal of access panel 11 Filters and filter rack components rated 250 oF 121 oC or less must be located a minimum...

Page 4: ...ces with vertical or horizontal top mounted burner trays to remove condensate from inside the heat exchanger Condensate drain lines must be connected if heater is located downstream of cooling section...

Page 5: ...enance Gas Supply Piping and Connections 1 Installation of piping must conform with local building codes and ordinances or in the absence of local codes with ANSI Z223 1 the National Fuel Gas Code In...

Page 6: ...Outdoor Horizontal Venting Combustion Air Opening AHU Cabinet Rain Hood Optional Flue Gas flow unobtructed Comb Blwr Mesh Screen AHU Cabinet Combustion Air Inlet Cover Mesh Screen Rain Hood Optional O...

Page 7: ...50 160 50 000 175 000 14653 51287 5 in 126 mm HMG200 400 HMD200 HHG200 360 200 000 400 000 58614 117228 6 in 152 mm HM A B 150 400 HHA150 400 150 000 400 000 43960 117228 6 in 152 mm HM A B G 500 600...

Page 8: ...not exceed 50 ft 15 25m Equivalent length of 5 or 6 inch 90o elbows is 5 ft 1 5 m and for a 7 inch 90o elbow is 7 feet 2 13 m 45o Elbows are half of the equivalent length of 90o The vent system must...

Page 9: ...pplied to systems for operation in separated combustion systems The furnace must be mounted with the burner section in a reasonably airtight vestibule compartment as these systems provide combustion a...

Page 10: ...lent length of vent pipe and air supply is 50 ft Individual runs should be approximately same length Figure 9 Horizontal Venting Separated Combustion Exterior Wall 18 in 0 45m Above grade or expected...

Page 11: ...es 10 Turn power on at disconnect switch 11 Set thermostat or controller to its highest position to initiate call for heat and maintain operation of unit 12 Draft inducer will run for a 15 to 30 secon...

Page 12: ...ure 10B White Rodgers 36H Gas Valve Figure 10C Honeywell V8944 Gas Valve 1 8 NPT Inlet Pressure Tap 2nd Stage Hi Fire Manifold Pressure Adjustment 3 32 Allen Key 1st Stage Lo Fire Manifold Pressure Ad...

Page 13: ...hanger tubes with stiff brush Poor flame characteristics can also be caused by undersized combustion air openings or flue gas recirculation into combustion air supply Increase air opening size or re d...

Page 14: ...itions the unit is equipped with a fixed temperature high limit switch mounted on the vestibule panel This switch will shut off gas to the heater through the ignition control module before the air tem...

Page 15: ...s valve to ensure that the gas valve seat is not leaking 6 Check wiring connections to be sure they are secure and inspect wiring for any deterioration 7 Label all wires prior to disconnection when se...

Page 16: ...16 Page left blank Heatco Inc 50 Heatco Court Cartersville Ga 30120...

Reviews: