25
Beacon II Troubleshooting Guide (continued)
Diagnostics
Part Number
Valve
100
BTUH
100
BTUH
100
BTUH
100
BTUH
29320003
ESVB-1
0.68
8160
0.64
7680
0.48
5760
0.42
5040
29320004
ESVB-4
3.27
39240
3.07
36840
2.31
27720
2.05
24600
29320007 - 08 ESVB-10
8.02
96240
7.54
90480
5.65
67800
5.01
60120
29320013
ESVB-15
15.14
181680
14.25
171000
10.69
128280
9.47
113640
29320014
ESVB-20
22.18
266160
20.87
250440
15.65
187800
13.86
166320
PROBLEM
Step ACTION ITEM
IF OK
IF NOT OK
1.
Check wiring connection to the board
• Correct field wiring to the board
2.
Low Pressure Safety (LPS) Tripped:
• Check for correct refrigerant type
• Change setpoint to match refrigerant
• Check refrigerant charge
• Add more refrigerant to proper charge
• Check LPS setting
• Correct LPS setting
• Check LPS wiring
• Correct LSP wiring
• Check EEV operation (stuck?)
• Clean or replace EEV
• Check coil for icing
• Defrost coil (see E6, step 2)
• Check for correct superheat reading
• Check/replace sensor or transducer
• Check for correct nozzle selection
• Replace distributor nozzle
• Check for clogged EEV inlet screen
• Replace EEV
• Check line sizing
• Correct line sizing
• Check LPS time delay relay setting
• Reset to 1 minute
• Check operation of LPS
• Replace Low Pressure Safety Switch
3.
High Pressure Safety (HPS) Tripped:
• Check for system overcharge
• Reclaim/recover excess charge
• Check for non-condensables
• Remove all non-condensables
• Check condenser fan motor and blade
• Repair or replace motor and/or blade
• Check for dirty condenser coil
• Clean condenser coil
• Check head pressure controls
• Adjust or replace faulty controls
• Check fan cycling controls
• Adjust or replace faulty controls
• Check liquid line sizing
• Correct line sizing
• Check for liquid line restrictions
• Repair line or remove restrictions
• Check operation of HPS
• Replace HPS if necessary
E7 Compressor
4.
Oil Pressure Safety (OPS) Tripped:
Shutdown
• Check oil level in compressor
• Add oil to crankcase to minimum level
• Check oil sump screen pickup
• Clean or replace pickup screen
• Check oil pump pressure
• Replace compressor oil pump
• Check for proper piping practices
Go to
• Correct piping to minimize oil logging
• Check for low superheat (see E6)
next step • Correct per steps in E6
• Check operation of auxiliary relay (R6)
• Replace auxiliary relay
• Check OPS sensor
• Replace faulty OPS sensor
• Check operation of OPS
• Replace faulty OPS
5.
Compressor Module Tripped (when supplied):
• Check module
• Replace faulty module
• Check superheat at compressor inlet
• Reduce superheat (TXV adjust, etc.)
• Check compressor for overheating
• Correct overheating problem
• Check suction pressure (too low?)
• Consider crankcase pressure regulator
or other measures
6.
Phase Loss Monitor (PLM) Tripped:
• Check presence of all phase legs
• Correct power phase problem
• Check power supply
• Correct power supply problems
• Check operation of PLM
• Replace faulty PLM
7.
Demand Cooling (when supplied):
• Check auxiliary relay
• Replace auxiliary relay
• Check demand cooling device
• Replace faulty demand cooling device
8.
Check compressor relay on board
• Replace board if relay is faulty
Summary of Contents for BEACON II H-IM-79E