6
Each Beacon II board power is supplied by a transformer in the evaporator on which
it is mounted. Do not run any 24 VAC wires between Beacon II boards on the evaporators.
Configuration
CU
M
S
S
S
M
= Master Evaporator
S
= Slave Evaporator
CU
= Condensing Unit
If there are multiple evaporators on a system, the
program for each SLAVE evaporator must be changed to
identify it as a SLAVE. To do so, press the “
PROGRAM
REVIEW
” button repeatedly until “
SLA
” appears then
use the “
SELECT
” knob to select “
YES
” then press
“
ENTER
”. All Beacon II boards are shipped with the
factory default as a MASTER evaporator. Place all
boards in the “
SERVICE
” mode while you program the
setpoints to avoid errors and alarms which may cause
troubles at startup.
VERY IMPORTANT:
This must be done for each slave
board.
Multiple Evaporator Configuration (Master/slave)
Up to 4 evaporators can be connected as a
master/slave configuration.
DO NOT remove the room
sensor from any of the Beacon II boards
.
This also applies when connected to the optional Smart
Controller.
PROGRAM
REVIEW
SELECT