Refrigeration Load Estimate Form
(for rooms below 32ºF) Bulletin Below32-05
Estimate for:
Basis for Estimate
Room Dimensions: Width
ft. x Length
ft. x Height
ft.
Volume: (L)
x (W)
x (H) = cu. ft.
Ambient Temp ºF. (Corrected for sun load) — Room Temp. ºF. = ºF. T.D.
Product Load
(a) lbs./day of to be reduced from entering temp. of ºF.
to freezing point of ºF. (Table 7) = ºF. Initial temp. drop
and then reduced from freezing point to storage Temp. of ºF. = (Table 7) ºF. Final temp. drop.
(b) gallons of ice cream @ overrun
Miscellaneous
Motors (including all blower motors) HP Ground Temp. (Table 21)
Lights (assume 1 watt/sq.ft.) Watts
No. of People
2. Air Change Load
Volume: cu. ft. x Factor (Table 5) x Factor (Table 6)
=
3. Additional Loads
Electrical Motors: HP x 75000 BTU/HP/24 hr.
=
Electrical Lights: Watts x 82
=
People Load: People x BTU/24 hrs. (Table 12)
=
Glass Door Load: Doors x 31200 BTU/Door/24 hr.
=
4. Product Load: (Table 7) (Product Load Figured @ 24 hr. Pulldown*)
(a) lbs./day x Spec. Heat above freezing x ºF. Intial Temp. Drop
=
lbs./day x Latent Heat Fusion
=
lbs./day x Spec. Heat below freezing x ºF. Intial Temp. Drop
=
(b) gallons of ice cream/day x BTU/gal (Table 19)
=
*For product pulldown time other than 24 hrs. figure 24 hr. load x (24/Pulldown Time)
Divide by No. of Operating Hrs. (18) to obtain BTUH Cooling Requirement
Equipment Selection
Condensing Unit
Unit Cooler
System Capacity
Qty. Model No.
Qty. Model No.
BTU/hr.
Total Refrigeration Load (1+2+3+4+5) BTU/24 hrs.
Add 10% Safety Factor
Total with Safety/Factor BTU/24 hrs.
1. Transmission Loads
Ceiling: (L)
x (W)
x Heat Load
(Table 1)
=
North Wall: (L)
x (W)
x Heat Load
(Table 1)
=
South Wall: (L)
x (W)
x Heat Load
(Table 1)
=
East Wall: (L)
x (W)
x Heat Load
(Table 1)
=
West Wall: (L)
x (W)
x Heat Load
(Table 1)
=
Floor: (L)
x (W)
x Heat Load
(Table 1)
=
Estimate by:
Date:
Insulation
Inches
Ceiling
Walls
Floor
Type
Note: Tables can be found in
Engineering Manual, H-ENG-2
2175 West Park Place Blvd. • Stone Mountain, GA 30087 • 770.465.5600 • Fax: 770.465.5990 • www.heatcraftrpd.com
(H)
(H)
(H)
Example: -20ºF Ice Cream Hardening Freezer
12 14 8
14 12 8 1344
85 -20 105
4 Foamed In place Ure
4 Foamed In place Ure
4 Foamed In place Ure
— —
—
— —
— —
100 100%
0.2 60
168
0
14 12 76 12768
14 8 76 8512
14 8 76 8512
12 8 76 7296
12 8 76 7296
14 12 58 9744
1344 12 3.49 56287
0.2 15000
168 13776
0 —
—
10 —
— — —
— — —
— — —
100 425
X 2.4 (10 hr. Pull down)* 102000
241191
24119
265310
14739
(W)
(W)