background image

11

Line Insulation 

 

After the final leak test, refrigerant lines exposed to high 

ambient conditions should be insulated to reduce heat pickup 

and prevent the formation of flash gas in the liquid lines. 

Suction lines should be insulated with 3/4" wall Armstrong 

“Armaflex” or equal. Liquid lines should be insulated with 1/2 

inch wall insulation or better. The insulation located in outdoor 

environments should be protected from UV exposure to prevent 

deterioration of insulating value.

Leak Testing 

 

After all lines are connected, the entire system must be 

leak tested. The complete system should be pressurized 

to not more than 150 psig with refrigerant and dry nitrogen (or 

dry CO

2

). The use of an electronic type leak detector is highly 

recommended because of its greater sensitivity to small leaks. 

As a further check it is recommended that this pressure be 

held for a minimum of 12 hours and then rechecked. For a 

satisfactory installation, the system must be leak tight. 

Evacuation and Leak Detection 

 

Due to the smaller molecule size of HFCʼs, they will tend to 

leak more readily than CFCʼs. Consequently, it is of the utmost 

importance that proper system evacuation and leak detection 

procedures be employed. 

 

Copeland recommends a minimum evacuation to 500 microns. 

In addition, a vacuum decay test is strongly recommended to 

assure there is not a large pressure differential between the 

system and vacuum pump. Good evacuation processes include 

frequent vacuum pump oil changes and large diameter, short 

hose connections to both high and low sides of the system 

preferably using bronze braided hose. 

 

Leak detection can be carried out in the conventional manner. 

If HCFC or CFC tracer gas is used, care must be taken to 

completely remove all traces of the gas prior to introducing 

HFCʼs. 

 

Electronic leak detectors are now available that will sense 

HFCʼs. This is considered preferable since it removes the 

possibility of chlorine remaining in the system after leak testing 

with HCFCʼs and/or CFCʼs. There is a view that even small 

quantities of chlorine may act as a catalyst encouraging copper 

plating and/or corrosion and should therefore be avoided.

WARNING: HFC-134a has been shown to be combus- 

 

tible at pressure as low as 5.5 psig (at  

 

350˚F) when mixed with air at concen 

 

trations more than  60% air by volume. At  

 

lower temperature,  higher pressures are  

 

required to support combustion. Therefore, 

 

air should never be mixed with HFC-134a 

 

for leak detection.

Within the last several years, manufacturers have developed 

fluorescent dye leak detection systems for use with refrigerants. 

These dyes mix with the lubricant and, when exposed to an 

ultraviolet light “fluoresce,” indicates the location of leaks. 

Copeland has tested and approved the Rigid “System Safe” dye 

and found it to be compatible with the compressor materials in 

systems.

Evacuation

CAUTION:  Do not use the refrigeration compressor 

 

to evacuate the system. Do not start the 

 

compressor while it is in a vacuum. 

 

A good, deep vacuum pump should be connected to both the 

low and high side evacuation valves with copper tube or high 

vacuum hoses (1/4" ID minimum). If the compressor has service 

valves, they should remain closed. A deep vacuum gauge 

capable of registering pressure in microns should be attached to 

the system for pressure readings.  

 

A shut off valve between the gauge connection and vacuum 

pump should be provided to allow the system pressure to be 

checked after evacuation. Do not turn off vacuum pump when 

connected to an evacuated system before closing shut off valve.  

 

The vacuum pump should be operated until a pressure of 1,500 

microns absolute pressure is reached — at which time the 

vacuum should be broken with the refrigerant to be used in the 

system through a drier until the system pressure rises above  

“0” psig. 

NOTE:  Refrigerant used during evacuation cannot 

be vented. Reclaim all used refrigerant.

 

EPA regulations are constantly being 

updated to ensure your procedure follows 

correct regulations.

 

Repeat this operation a second time.  

 

Open the compressor service valves and evacuate the entire 

system to 500 microns absolute pressure. Raise the pressure to 

2 psig with the refrigerant and remove the vacuum pump.

Summary of Contents for H-IM-FL1A

Page 1: ...riers Sight Glasses 5 Refrigerant Oils 6 Phase Loss Monitor 7 Recommended Refrigerant Piping Practices 7 Refrigeration Pipe Supports 7 Suction Lines 8 Suction Line Risers 8 Liquid Lines 8 Evacuation and Leak Detection 11 Refrigerant Charging Instructions 12 Field Wiring 12 Check Out and Start Up 12 Operational Check Out 13 System Balancing Compressor Superheat 13 System Troubleshooting Guide 14 Pr...

Page 2: ...turerʼs recommendations or if the serial number has been altered defaced or removed MOTOR COMPRESSORS Motor compressors furnished by SELLER are subject to the standard warranty terms set forth above except that motor compressor replacements or exchanges shall be made through the nearest authorized wholesaler of the motor compressor manufacturer not at SELLERʼs factory and no freight shall be allow...

Page 3: ...d Location Requirements for Air Cooled Condensing Units and Remote Condensers Units in Pits The top of the unit should be level with the top of the pit and side distance increased to 2W If the top of the unit is not level with the top of pit discharge cones or stacks must be used to raise discharge air to the top of the pit This is a minimum requirement Decorative Fences Fences must have 50 free a...

Page 4: ...ess Provide adequate space at the compressor end of the unit for servicing Provide adequate space on the connection side to permit service of components Spring Mounted Compressor Compressors are secured rigidly to make sure there is no transit damage Before operating the unit it is necessary to follow these steps a Remove the upper nuts and washers b Discard the shipping spacers c Install the neop...

Page 5: ... drier The sight glass is designed to give a visual indication of moisture content in the system Generally it requires no field service However in cases of extreme acid formation in a system after a compressor burnout the acid may damage the sensing element or etch the glass This would require that the sight glass be replaced along with the liquid line drier after any compressor motor burnout CAUTI...

Page 6: ...introduction of the Polyol ester lubricants Table 3 below summarizes which oils lubricants are approved for use in Copeland compressors Polyol Ester Lubricants Hygroscopicity Ester lubricants POE have the characteristic of quickly absorbing moisture from the ambient surroundings This is shown graphically in Figure 3 where it can be seen that such lubricants absorb moisture faster and in greater qu...

Page 7: ... the base of each suction riser of four 4 feet or more to enhance oil return to the compressor e For desired method of superheat measurement a pressure tap should be installed in each evaporator suction line in the proximity of the expansion valve bulb f When brazing refrigerant lines an inert gas should be passed through the line at low pressure to prevent scaling and oxidation inside the tubing ...

Page 8: ...superheat at the compressor Figure 6 Suction P Traps Slope 1 4 per 10 ft toward compressor Suction Lines NOTE If the suction line must rise to a point higher than the suction connection on the evaporator a suction line trap at the outlet of the evaporator must be provided Horizontal suction lines should slope away from the evaporator toward the compressor at the rate of 1 4 inch per 10 feet for go...

Page 9: ...Tee Straight Through 1 2 2 3 4 4 5 7 8 10 12 14 16 Table 4 Pressure Loss of Liquid Refrigerants in Liquid Line Risers Expressed in Pressure Drop PSIG and Subcooling Loss F Liquid Line Rise in Feet 10ʼ 15ʼ 20ʼ 25ʼ 30ʼ 40ʼ 50ʼ 75ʼ 100ʼ Refrigerant PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F PSIG F R22 4 8 1 6 7 3 2 3 9 7 3 1 12 1 3 8 14 5 4 7 19 4 6 2 24 2 8 0 36 3 12 1 48 4 16 5 R134a 4...

Page 10: ... 1 3 27 26 39 63 86 1 24 134a 64 2 2 57 14 26 40 61 1 91 1 3 8 22 63 5 3 50 27 42 64 93 1 33 R507 404A 55 0 4 98 40 58 95 1 32 1 87 134a 90 9 3 65 20 37 57 87 1 30 1 5 8 22 90 0 4 96 37 59 90 1 33 1 88 R507 404A 78 0 7 07 56 82 1 35 1 86 2 64 134a 158 6 34 34 64 98 1 51 2 24 2 1 8 22 156 8 61 65 1 03 1 57 2 30 3 26 R507 404A 134 12 25 98 1 43 2 35 3 23 4 58 134a 244 9 78 52 99 1 51 2 32 3 47 2 5 8...

Page 11: ...CFCʼs There is a view that even small quantities of chlorine may act as a catalyst encouraging copper plating and or corrosion and should therefore be avoided WARNING HFC 134a has been shown to be combus tible at pressure as low as 5 5 psig at 350 F when mixed with air at concen trations more than 60 air by volume At lower temperature higher pressures are required to support combustion Therefore a...

Page 12: ...ng until system has sufficient refrigerant for proper operation Do not overcharge Remember that bubbles in a sight glass may be caused by a restriction as well as a shortage of refrigerant i Do not leave unit unattended until the system has reached normal operating conditions and the oil charge has been properly adjusted to maintain the oil level at the center of the sight glass CAUTION Extreme car...

Page 13: ...ve at the evaporator should be adjusted Operational Check Out After the system has been charged and has operated for at least two hours at normal operating conditions without any indication of malfunction it should be allowed to operate overnight on automatic controls Then a thorough recheck of the entire system operation should be made as follows a Check compressor discharge and suction pressures...

Page 14: ... system 3 Check for leaks Repair and add charge 4 Low suction pressure 4 See corrective steps for low suction pressure 5 Variable head pressure valve 5 Check valve setting High suction pressure 1 Excessive load 1 Reduce load or add additional equipment 2 Expansion valve overfeeding 2 Check remote bulb Regulate superheat Low suction pressure 1 Lack of refrigerant 1 Check for leaks Repair and add ch...

Page 15: ... and components Verify that all electrical and ground connections are secure tighten as required Check condition of compressor and heater contactors Look for discoloration and pitting Replace as required Check operation and calibration of all timers relays pressure controls and safety controls Clean electrical cabinet Look for signs of moisture dirt debris insects and wildlife Take corrective acti...

Page 16: ...ATE MODULE R1 R4 RELAYS TD7 8 START TIMER FIELD WIRING FACTORY WIRING CB1 CB7 CIRCUIT BREAKERS F1 FUSE CLASS CC CCH CRANKCASE HEATERS C1 C4 COMPRESSOR CONTACTORS C1A1 C4A1 C1 C4 AUXILIARY CONTACTS C5 C12 CONDENSER FAN CONTACTORS FCT FAN CYCLE TEMP CONTROL LSV LIQUID LINE SOLENOID VALVE HPS HIGH PRESSURE SWITCH LPS LOW PRESSURE SWITCH LEGEND w 30 MIN TIME DELAY 25 A M1 M3 C5 25 A C6 25 A M5 M7 C7 2...

Page 17: ...TE MODULE R1 R4 RELAYS TD7 8 START TIMER FIELD WIRING FACTORY WIRING CB1 CB7 CIRCUIT BREAKERS F1 FUSE CLASS CC CCH CRANKCASE HEATERS C1 C4 COMPRESSOR CONTACTORS C1A1 C4A1 C1 C4 AUXILIARY CONTACTS C5 C12 CONDENSER FAN CONTACTORS FCT FAN CYCLE TEMP CONTROL LSV LIQUID LINE SOLENOID VALVE HPS HIGH PRESSURE SWITCH LPS LOW PRESSURE SWITCH LEGEND w 30 MIN TIME DELAY 25 A M1 M3 C5 25 A C6 25 A M5 M7 C7 25...

Page 18: ...18 Control Circuit Wiring Diagram for BACU51 and BACU59 ...

Page 19: ...19 Submittal ...

Page 20: ...20 Submittal ...

Page 21: ...t Serial ________________________________________ Compressor Model ____________________ Compressor Model _________________ Compressor Serial ____________________ Compressor Serial __________________ Electrical _________________ Volts __________________ Phase _______ Voltage at Compressor L1__________ L2 ___________ L3 ___________ Amperage at Compressor L1__________ L2 ___________ L3 ___________ Se...

Page 22: ...22 Notes ...

Page 23: ...23 Notes ...

Page 24: ...PLACE BOULEVARD STONE MOUNTAIN GA 30087 USA 770 465 5600 FAX 770 465 5990 WWW HEATCRAFTRPD COM Since product improvement is a continuing effort we reserve the right to make changes in specifications without notice Visit us online at www heatcraftrpd com ...

Reviews: