15
Self-Contained Spot Merchandiser
3
To restore the normal display, press the
DOWN
button again or wait five seconds.
View Maximum Temperature
1
Press and release the
UP
button.
2
The
Hi
message will be displayed followed by the maximum temperature recorded.
3
To restore the normal display, press the
UP
button again or wait five seconds.
Reset the Maximum and Minimum Temperatures
1
Press and hold the SET button for more than 3 seconds while the maximum or minimum temperature is dis-
played (
rSt
message will be displayed).
2
After confirming the operation, the
rSt
message will start blinking and then the normal temperature will be
displayed.
6.3. Control Settings
The unique settings listed below in Table 6-5 are for the low temperature controller. The low temperature controller is
located inside the control panel on the left side.
Label
Name
Range
Default
Level
Setting
SEt
Setpoint
LS to US
-5.0
---
-20
rtc*
Real time clock menu
-
-
Pr1
-
Hy
Differential
1 to 255°F
2.0
Pr1
5
CCS
Setpoint for continuous cycle
-67 to 302°F
-5
Pr2
-20
* Indicates parameters that are used when the real-time clock feature is included on the controller. The current controller does not
have this feature.
Unique settings listed below in Table 6-6 are for the medium temperature controller. The medium temperature
controller is located inside the control panel on the right side.
Label
Name
Range
Default
Level
Setting
SEt
Setpoint
LS to US
-5.0
---
14
rtc*
Real time clock menu
-
-
Pr1
-
Hy
Differential
1 to 255°F
2.0
Pr1
18
CCS
Setpoint for continuous cycle
-67 to 302°F
-5
Pr2
14
* Indicates parameters that are used when the real-time clock feature is included on the controller. The current controller does not
have this feature.
Table 6-4. Viewing and Resetting Maximum and Minimum Temperatures
Table 6-5. Unique low temperature controller settings
Table 6-6. Unique medium temperature controller settings