22
Installation and Operation Manual
Appendices
There are three appendices related to the Dixell XR75CX Digital Controller. They are:
•
Appendix A: Default Setting Values
•
Appendix B: Parameters
•
Appendix C: Factory Settings
Appendix A: Default Setting Values
Label
Name
Range
Value
Level
SEt
Setpoint
LS to US
[-5.0°C] [23°F]
- - -
HY
Differential
[0.1 to 25.5°C]
[1 to 255°F]
[2.0°C] [2°F]
Pr1
LS
Minimum setpoint
[-50°C to SET]
[-58°F to SET]
[-50.0°C]
[-58°F]
Pr2
US
Maximum setpoint
[SET to 110°C]
[SET to 230°F]
[110.0°C]
[230°F]
Pr2
ot
Thermostat probe calibration
[-12 to 12°C]
[-21 to 21°F]
[0.0°C]
[0°F]
Pr1
P2P
Evaporator probe presence
n=not present; Y=pres.
Y
Pr1
oE
Evaporator probe calibration
[-12 to 12°C]
[-21 to 21°F]
[0.0°C]
[0°F]
Pr2
P3P
Third probe presence
n=not present; Y=pres.
n
Pr2
o3
Third probe calibration
[-12.0 to 12.0°C]
[-21 to 21°F]
[0.0°C]
[0°F]
Pr2
P4P
Fourth probe presence
n=not present; Y=pres.
n
Pr2
o4
Fourth probe calibration
[-12.0 to 12.0°C]
[-21 to 21°F]
[0.0°C]
[0°F]
Pr2
odS
Outputs delay at start up
0 to 255 min
0
Pr2
AC
Anti-short cycle delay
0 to 50 min
1
Pr1
rtr
P1-P2 percentage for regulation
0 to 100 (100=P1, 0=P2)
100
Pr2
CCt
Continuous cycle duration
0.0 to 24h 00min, res. 10min
0.0
Pr2
CCS
Setpoint for continuous cycle
[-50 to 110.0°C]
[-58 to 230°F]
[-5°C]
[23°F]
Pr2
Con
Compressor ON time with faulty probe
0 to 255 min
15
Pr2
CoF
Compressor OFF time with faulty probe
0 to 255 min
30
Pr2
CF
Temperature measurement unit
°C; °F
[°C] [°F]
Pr2
rES
Resolution
in=integer; dE= dec.point
dE
Pr1
Lod
Probe displayed
P1; P2
P1
Pr2
rEd2
X-REP display
P1; P2; P3; P4; SEt; dtr
P1
Pr2
dLY
Display temperature delay
0.0 to 20min 00s, res. 10s
0.0
Pr2
dtr
P1-P2 percentage for display
1 to 99
50
Pr2
tdF
Defrost type
EL=el. heater; in= hot gas
EL
Pr1
dFP
Probe selection for defrost termination
nP; P1; P2; P3; P4
P2
Pr2