25
Self-Contained Spot Merchandiser
FSt
Fans stop temperature
(-50 to 50°C; -58 to 122°F) Setting of temperature, detected
by evaporator probe, above which fans are always OFF.
Fon
Fan ON time
(0 to 15min) With FnC=C_n or C_Y, (fan activated in parallel
with compressor) it sets the evaporator fan ON cycling time
when the compressor is OFF. With Fon=0 and FoF≠0 the fan
is always OFF, with Fon=0 and FoF=0 the fan is always OFF.
FoF
Fan OFF time
(0 to 15min) With FnC=C_n or C_Y, (fan activated in parallel
with compressor) it sets the evaporator fan OFF cycling time
when the compressor is OFF. With Fon=0 and FoF≠0 the fan
is always OFF, with Fon=0and FoF=0 the fan is always OFF.
FAP
Probe selection for fan management
(nP; P1; P2; P3; P4) nP = no probe; P1 =thermostat probe; P2
= evaporator probe; P3 =configurable probe; P4 = Probe on
Hot Key plug.
AUXILIARY THERMOSTAT CONFIGURATION (terms. 1-2) - oA2 = AUS
ACH
Kind of regulation for auxiliary relay
(Ht; CL) Ht = heating; CL = cooling
SAA
Set Point for auxiliary relay
(-50 to 110.0°C; -58 to 230°F) It defines the room temperature
setpoint to switch auxiliary relay.
SHY
Differential for auxiliary output
(0.1 to 25.5°C; 1 to 45°F) Intervention differential for auxiliary
output setpoint. ACH=CL, AUX Cut in is [SAA+SHY]; AUX Cut
out is SAA. ACH=Ht, AUX Cut in is [SAA–SHY]; AUX Cut out
is SAA.
ArP
Probe selection for auxiliary
(nP; P1; P2; P3; P4) nP = no probe, the auxiliary relay is
switched only by the digital input; P1 = Probe 1 (Thermostat
probe); P2 = Probe 2 (evaporator probe); P3 = Probe 3
(display probe); P4 = Probe 4
Sdd
Auxiliary relay OFF during defrost
(n; Y) n = the auxiliary relay operates during defrost; Y = the
auxiliary relay is switched OFF during defrost
ALARMS
ALP
Probe selection for alarm
(nP; P1; P2; P3; P4) nP = no probe, the temperature alarms
are disabled; P1 = Probe 1 (Thermostat probe); P2 = Probe 2
(evaporator probe); P3 = Probe 3 (display probe); P4 = Fourth
probe
ALC
Temperature alarms configuration
(Ab; rE) Ab = absolute temperature, alarm temperature is
given by the ALL or ALU values. rE = temperature alarms are
referred to the setpoint. Temperature alarm is enabled when
the temperature exceeds the [SET+ALU] or [SET-ALL] values.
ALU
MAXIMUM temperature alarm
(ALL to 110°C; ALL to 230°F) When this temperature is
reached the alarm is enabled, after the ALd delay time.
ALL
Minimum temperature alarm
(-50°C to ALU; -58 to ALU) When this temperature is reached
the alarm is enabled, after the ALd delay time.
AFH
Differential for temperature alarm recovery
(0.1 to 25.5°C; 1 to 45°F) Intervention differential for recovery
of temperature alarm
ALd
Temperature alarm delay
(0 to 255 min) Time interval between the detection of an alarm
condition and alarm signaling.
dAo
Exclusion of temperature alarm at start-up
(0.0 to 24h00min, res. 10min) Time interval between the
detection of the temperature alarm condition after instrument
power ON and alarm signaling.
CONDENSER TEMPERATURE ALARM
AP2
Probe selection for temperature alarm of condenser
(nP; P1; P2; P3; P4) nP = no probe; P1 =thermostat probe; P2
= evaporator probe; P3 =configurable probe; P4 = Probe on
Hot Key plug