background image

11

PRO

3

 Top Mount Packaged Refrigeration System | Outdoor

Programming the PJEZC Carel 

Electronic Controller

Reprinted with permission from Carel.

The  Carel  PJEZC  control  is  a  fully  configurable  electronic 

refrigeration  controller.  The  Top  Mount  packaged 

refrigeration  system  uses  the  Carel  controller  on  all  three 

temperature  designated  models.  The  models  differ  by 

a  pre-programmed  parameter  list  that  is  specific  for  

each application.
There  are  two  levels  of  programming  with  the  C  controller. 

The  first  level  can  be  accessed  through  the  keypad.  Set 

Point  (st),  Interval  between  defrost  (do),  Maximum  Defrost 

Duration  (dP),  and  Dripping Time  (dd)  are  examples  of  first 

level parameters. Second level parameters can be accessed by 

entering a password. See “Modifying Parameters”  (page 17).

Installation and Removal

PANEL INSTALLATION FROM THE FRONT USING SCREWS

•  The thickness of the fastening panel must not exceed 3 mm;
•  Remove the front frame and make sure that the two catches 

are in place (these must not protrude from the outline of the 
drilling template). If necessary, unscrew the two screws. Do not 
unscrew excessively, the screws must not be detached from the 
front panel (phase 1);

•  Insert the instrument in the opening in the panel and hold it in 

position by the centre of the front panel (phase 1);

•  Using the screwdriver, tighten the bottom screw 90°, the catch 

must come out of its slot and click onto the panel, then tighten 
until the front panel is secure; Do not over-tighten, when the 
front panel is secured blocks simply make another ½ turn to 
compress the gasket; If the catch does not click onto the panel, 
unscrew the screw, applying pressure at the same time with 
the screwdriver so that the catch moves back. Do not unscrew 
too much, the head of the screw must not be raised from the 
surface of the front panel (phase 2);

•  Repeat the same operation for the top screw (phase 2);
•  Apply the front frame (phase 3).

DISMANTLING USING THE SCREWS FROM THE FRONT

•  Unclip the front frame;
•  Unscrew the bottom screw, at the moment the front panel 

detaches from the panel keep pressure on the screw and 
unscrew a further 90° to make the catch go back into its slot;

•  Repeat for the top screw;
•  Remove the instrument from panel, keeping it horizontal

* Do not over-tighten the screws.

3.

 C

on

tr

ollers

Summary of Contents for PRO TOP MOUNT H-IM-82C

Page 1: ...nit Placement 4 Rigging Mounting Inspection General Safety Information Control Factory Default Settings 5 Standard Installation Procedure 6 Outdoor Unit Installation Instructions 7 2 Freezers Service...

Page 2: ...ox Temp lbs kg oz BTUH PTT047M6B 5 120 208 230 1 60 7 0 15 5 9 350 A 192 87 27 6 700 PTT063M6B 6 860 208 230 1 60 11 5 15 9 5 550 A 207 94 29 8 700 PTT072M6B 7 500 208 230 1 60 9 3 15 7 8 500 A 211 95...

Page 3: ...ood See reference on Page 2 Dimensional Diagrams Figure B Large Cabinet without weather hood See reference on Page 2 25 x 381 2 panel opening required for evaporator section of large cabinet sizes 23...

Page 4: ...ck any panel cam locks to install top mounted equipment The size and shape of the storage will generally determine the type and number of units to be used and their location Top View One System Evapor...

Page 5: ...prior approval is given to do so 6 When unpacking the system care should be taken to prevent damage 7 Avoid removing the shipping base until the unit has been moved to the final destination 8 Complete...

Page 6: ...nstallation to prevent bunching or folding which could affect the gasket to curb sealing or trap rainwater adjacent to the curb 4 Remove the weather hood from the system The compressor compartment cov...

Page 7: ...re 2 Roof membrane placed over curb Figure 3 PTT unit placed on roof of walk in color see rigging instructions Figure 4 Weather hood installed after electrical service connection PTT Models Example Ou...

Page 8: ...functioning properly 8 Clean the evaporator coil surface 9 Clean the drain pan and check the drain pan and drain line for proper drainage Refrigeration Sequence of Operation 1 Power is provided to the...

Page 9: ...Off Off Off If unit shows OFF depress the button and hold for three seconds On Automatic Defrost on start up Off Off Off On If coil temperature is below 65 F If it is above defrost is not initiated D...

Page 10: ...Compressor starts and evaporator fans delay for 2 minutes to freeze coil TABLE 6 Model PTT Medium Temperature Models EZY SETTING 2 SET POINT IS 34 F These models are intended for cooler applications a...

Page 11: ...lling template If necessary unscrew the two screws Do not unscrew excessively the screws must not be detached from the front panel phase 1 Insert the instrument in the opening in the panel and hold it...

Page 12: ...section of each wire 0 5 mm2 Avoid direct contact with internal electronic components Connection errors and connections other than those indicated in this manual may involve danger to the safety of th...

Page 13: ...al timer relating to parameter dI is updated If dI expires in OFF status a defrost is performed when restarting auxiliary relay management only in the following configurations H1 1 2 E0 alarm only H1...

Page 14: ...multifunction input analogue or digital Parameter 4 selects the probe shown on the display all the other display and control modes remain unchanged IMPORTANT the easy compact models can display up to...

Page 15: ...arameters with corresponding values for the control of the refrigeration system Table of Alarms and Signals When an alarm is activiated the display shows the corresponding message that flashes alterna...

Page 16: ...Ad and A0 The alarm is automatically reset when the temperature returns within the set limits see parameter AL HI flashing High temperature alarm The probe has measured a temperature higher than the s...

Page 17: ...until displaying 22 password to access the parameters press the SET button to confirm the password use the UP and DOWN buttons to scroll the parameters The LED corresponding to the category of paramet...

Page 18: ...mperature is too high parameters dt and d defrost probe the manual defrost is not activated and the defrost LED flashes compressor protection times set parameter d9 select d9 1 the high temperature al...

Page 19: ...0 r2 Maximum set point value 0 150 50 c2 Minimum compressor off time 0 100 4 do Type of Defrost 0 4 0 dI Interval between defrost 0 199 6 dt End defrost temperature set point 50 127 65 dP Maximum def...

Page 20: ...for proper superheat 4 Condensing temperature too low 4 Check ambient temperature 50 F to 100 F Compressor 1 Operating beyond design conditions 1 Add equipment so that conditions are within allowable...

Page 21: ...230V Defrost Heaters 4313F 3 3 3 3 3 3 3 3 Outdoor Parts Fan Pressure Control 28917301 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Fan Temperature Control 5521R 1 1 1 1 1 1 1 1 1 1 1 1 Drain Line Heate...

Page 22: ...PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN LINE HEATER TFC TEMPERATURE FA...

Page 23: ...ACITOR HPS HIGH PRESSURE SWITCH PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN...

Page 24: ...URE SWITCH PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN LINE HEATER TFC TEMP...

Page 25: ...Heatcraft Refrigeration Products LLC makes no warranty expressed or implied of fitness for any particular purpose or of any other nature whatsoever with respect to products manufactured or sold by Hea...

Page 26: ...is a continuing effort we reserve the right to make changes in specifications without notice Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd Stone Mountain GA 30087 P 800 321 1881 www h...

Reviews: