 Top Mount Packaged Refrigeration System | Outdoor

Keypads

Preliminary Configurations

Once  the  electrical  connections  have  been  completed,  simply 
power-up the controller to make it operative.
Heatcraft  recommends  that  you  check  the  parameters  listed.

Functions Available from Keypad

ON AND OFF
Switching the instrument ON:
 press UP for more than 3 s (when 

pressing the button, the display shows ON).
Switching the instrument OFF: press UP for more than 3 s. The 

display shows the message “OFF”, alternating with the temperature 

measured by the set probe.
In off status, the following functions are disabled (if featured by the 

model):

•  compressor control / duty setting / continuous cycle;
•  defrost;
•  fan control;
•  alarms : ‘LO’, ‘HI’, ‘IA’, ‘cht’, ‘CHT’;
•  door switch (A4= 7/8 );
•  buzzer (when available)

While the following are enabled:

•  temperature display, alternating with the message “OFF”;
•  parameter display and setting;
•  alarms: “E0”, “E1”, “E2”;
•  the internal timer relating to parameter ‘dI’ is updated. If ‘dI’ 

expires in OFF status, a defrost is performed when restarting;

•  auxiliary relay management, only in the following 

configurations:

•  H1= = 1/2 (“E0” alarm only)
•  H1= 3, A4= 6;

BUT. NO.

NORMAL OPERATION

START UP

pressing 

the button 

alone

pressing 

with other 

buttons

1

more than 

3 s: switch 

ON/OFF

pressed 

together 

with 3 

activates/

deactivates 

the 

continuous 

cycle

2

- 1 s: 

displays/

sets the set 

point

- more 

than 3 s: 

accesses 

the 

parameter 

setting 

menu 
(enter 

password 

22)

- mutes the 

audible 

alarm 

(buzzer)

for 1 s 
RESET 

current EZY 

set

pressed 

together 
(2 and 3) 

activate 

parameter 

reset 

procedure

3

more 

than 3 s: 

activates/

deactivates 

the defrost

pressed 

together 

with 1 

activates/

deactivates 

the 

continuous 

cycle

for 1 s 

displays 

firmware 

version

Control Parameters

st

set point

rd

set point differential

Alarm Parameters

Ad

temperature alarm delay

AL

low temperature alarm threshold/deviation

AH

high temperature alarm threshold/deviation

Defrost Parameters

d0

type of defrost

dl

interval between two defrosts

dt

end defrost temperature

dP

maximum defrost duration

3.

 C

on

tr

ollers

Summary of Contents for PRO TOP MOUNT H-IM-82C

Page 1: ...nit Placement 4 Rigging Mounting Inspection General Safety Information Control Factory Default Settings 5 Standard Installation Procedure 6 Outdoor Unit Installation Instructions 7 2 Freezers Service...

Page 2: ...ox Temp lbs kg oz BTUH PTT047M6B 5 120 208 230 1 60 7 0 15 5 9 350 A 192 87 27 6 700 PTT063M6B 6 860 208 230 1 60 11 5 15 9 5 550 A 207 94 29 8 700 PTT072M6B 7 500 208 230 1 60 9 3 15 7 8 500 A 211 95...

Page 3: ...ood See reference on Page 2 Dimensional Diagrams Figure B Large Cabinet without weather hood See reference on Page 2 25 x 381 2 panel opening required for evaporator section of large cabinet sizes 23...

Page 4: ...ck any panel cam locks to install top mounted equipment The size and shape of the storage will generally determine the type and number of units to be used and their location Top View One System Evapor...

Page 5: ...prior approval is given to do so 6 When unpacking the system care should be taken to prevent damage 7 Avoid removing the shipping base until the unit has been moved to the final destination 8 Complete...

Page 6: ...nstallation to prevent bunching or folding which could affect the gasket to curb sealing or trap rainwater adjacent to the curb 4 Remove the weather hood from the system The compressor compartment cov...

Page 7: ...re 2 Roof membrane placed over curb Figure 3 PTT unit placed on roof of walk in color see rigging instructions Figure 4 Weather hood installed after electrical service connection PTT Models Example Ou...

Page 8: ...functioning properly 8 Clean the evaporator coil surface 9 Clean the drain pan and check the drain pan and drain line for proper drainage Refrigeration Sequence of Operation 1 Power is provided to the...

Page 9: ...Off Off Off If unit shows OFF depress the button and hold for three seconds On Automatic Defrost on start up Off Off Off On If coil temperature is below 65 F If it is above defrost is not initiated D...

Page 10: ...Compressor starts and evaporator fans delay for 2 minutes to freeze coil TABLE 6 Model PTT Medium Temperature Models EZY SETTING 2 SET POINT IS 34 F These models are intended for cooler applications a...

Page 11: ...lling template If necessary unscrew the two screws Do not unscrew excessively the screws must not be detached from the front panel phase 1 Insert the instrument in the opening in the panel and hold it...

Page 12: ...section of each wire 0 5 mm2 Avoid direct contact with internal electronic components Connection errors and connections other than those indicated in this manual may involve danger to the safety of th...

Page 13: ...al timer relating to parameter dI is updated If dI expires in OFF status a defrost is performed when restarting auxiliary relay management only in the following configurations H1 1 2 E0 alarm only H1...

Page 14: ...multifunction input analogue or digital Parameter 4 selects the probe shown on the display all the other display and control modes remain unchanged IMPORTANT the easy compact models can display up to...

Page 15: ...arameters with corresponding values for the control of the refrigeration system Table of Alarms and Signals When an alarm is activiated the display shows the corresponding message that flashes alterna...

Page 16: ...Ad and A0 The alarm is automatically reset when the temperature returns within the set limits see parameter AL HI flashing High temperature alarm The probe has measured a temperature higher than the s...

Page 17: ...until displaying 22 password to access the parameters press the SET button to confirm the password use the UP and DOWN buttons to scroll the parameters The LED corresponding to the category of paramet...

Page 18: ...mperature is too high parameters dt and d defrost probe the manual defrost is not activated and the defrost LED flashes compressor protection times set parameter d9 select d9 1 the high temperature al...

Page 19: ...0 r2 Maximum set point value 0 150 50 c2 Minimum compressor off time 0 100 4 do Type of Defrost 0 4 0 dI Interval between defrost 0 199 6 dt End defrost temperature set point 50 127 65 dP Maximum def...

Page 20: ...for proper superheat 4 Condensing temperature too low 4 Check ambient temperature 50 F to 100 F Compressor 1 Operating beyond design conditions 1 Add equipment so that conditions are within allowable...

Page 21: ...230V Defrost Heaters 4313F 3 3 3 3 3 3 3 3 Outdoor Parts Fan Pressure Control 28917301 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Fan Temperature Control 5521R 1 1 1 1 1 1 1 1 1 1 1 1 Drain Line Heate...

Page 22: ...PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN LINE HEATER TFC TEMPERATURE FA...

Page 23: ...ACITOR HPS HIGH PRESSURE SWITCH PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN...

Page 24: ...URE SWITCH PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN LINE HEATER TFC TEMP...

Page 25: ...Heatcraft Refrigeration Products LLC makes no warranty expressed or implied of fitness for any particular purpose or of any other nature whatsoever with respect to products manufactured or sold by Hea...

Page 26: ...is a continuing effort we reserve the right to make changes in specifications without notice Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd Stone Mountain GA 30087 P 800 321 1881 www h...

Reviews: