background image

20

Installation and Operations Manual

4.

 S

er

vic
e I

nf

orma

tion

Table 5.  

 System Troubleshooting Chart

    PROBLEM 

                   POSSIBLE CAUSES 

   

POSSIBLE CORRECTIVE STEPS

  Compressor 

1.  Main switch open. 

1.  Close switch.

  will not run 

2.  Fuse blown. 

2.  Check electrical circuits and motor winding for shorts or grounds. 

   

 

 

 

Investigate for possible overloading. Replace fuse after fault is corrected.

   

3.  Thermal overloads tripped. 

3.  Overloads are automatically reset. Check unit closely when unit comes  

 

   

 

 

 

back on line.

   

4.  Defective contactor or coil. 

4.  Repair or replace.

   

5.  System shut down by safety devices. 

5.  Determine type and cause of shutdown and correct it before resetting  

 

   

 

 

 

safety switch.

   

6.  No cooling required. 

6.  None. Wait until calls for cooling.

   

7.  Motor electrical trouble. 

7.  Check motor for open windings, short circuit or burn out.

   

8.  Loose wiring. 

8.  Check all wire junctions. Tighten all terminal screws.

  Compressor 

1.  Flooding of refrigerant into crankcase. 

1.  Check setting of expansion valves. 

  noisy or vibrating 

2.  Worn compressor. 

2.  Replace.

  High 

1.  Non-condensables in system. 

1.  Remove the non-condensables.

  discharge 

2.  Fan not running. 

2.  Check electrical circuit. Replace if motor fails.

  pressure 

3.  Dirty condenser coil. 

3.  Clean.

   

4.  System overcharged with refrigerant. 

4.  Reclaim refrigerant and recharge proper amount.

  Low discharge 

1.  Insufficient refrigerant in system. 

1.  Check for leaks. Repair and add charge. 

  pressure 

2.  Low suction pressure. 

2.  See corrective steps for low suction pressure.

  High suction 

1.  Excessive load. 

1.  Reduce load or add additional equipment.

  pressure 

2.  Expansion valve overfeeding. 

2.  Check remote bulb. Regulate superheat.

  Low 

1.  Lack of refrigerant. 

1.  Check for leaks. Repair and add charge (see refrigerant charge chart pg 2).

  suction 

2.  Evaporator dirty or iced. 

2.  Clean.

  pressure 

3.  Expansion valve malfunctioning. 

3.  Check and reset for proper superheat.

   

4.  Condensing temperature too low. 

4.  Check ambient temperature 50°F to 100°F.

  Compressor 

1.  Operating beyond design conditions. 

1.  Add equipment so that conditions are within allowable limits.

  thermal protector 

2.  Dirty condenser coil. 

2.  Clean coil.

  switch open 

3.  Overcharged system. 

3.  Reduce charge (see refrigerant charge chart, pg 2).

  Fan(s) will 

1.  Main switch open. 

1.  Close switch.

  not operate 

2.  Blown fuses. 

2.  Replace fuses. Check for short circuits or overload conditions.

   

3.  Defective motor. 

3.  Replace motor.

   

4.  Defective defrost control. 

4.  Replace defective component.

   

5.  Unit in defrost cycle. 

5.  Wait for completion of cycle.

   

6.  Coil does not get cold enough to reset thermostat 

6.  Adjust fan delay setting of control.

  Room 

1.  Control cut out set too high. 

1.  Adjust control.

  temperature 

2.  Superheat too high. 

2.  Adjust thermal expansion valve.

  too high 

3.  System low on refrigerant. 

3.  Add refrigerant. See refrigerant charge chart pg. 2.

   

4.  Coil iced-up. 

4.  Manually defrost coil. Check defrost controls for malfunction.

  Ice accumulating 

1.  Defrost duration is too long. 

1.  Adjust defrost termination temperature on control.

  on ceiling around 

2.  Fan delay not delaying fans after defrost period. 

2.  Adjust fan delay setting or replace bad sensor.

  evaporator and/or 

3.  Defective defrost control or sensor. 

3.  Replace defective control or sensor.

  on fan guards' 

4.  Too many defrosts. 

4.  Adjust number of defrosts.

  venturi or blades 

  Coil not clearing 

1.  Coil temperature not getting above freezing 

1.  Check heater operation.

  of frost during 

 

point during defrost.

  defrost cycle. 

2.  Not enough defrost cycles per day. 

2.  Adjust control for more defrost cycles.

   

3.  Defrost cycle too short. 

3.  Adjust defrost control, defrost duration setting.

   

4.  Defective defrost control or sensor. 

4.  Replace defective component.

  Ice accumulating 

1.  Defective heater. 

1.  Replace heater.

  in drain pan 

2.  Unit not installed properly (out of level) 

2.  Check and adjust if necessary.

   

3.  Drain line plugged. 

3.  Clean drain line.

   

4.  Defective control. 

4.  Replace defective component.

Summary of Contents for PRO TOP MOUNT H-IM-82C

Page 1: ...nit Placement 4 Rigging Mounting Inspection General Safety Information Control Factory Default Settings 5 Standard Installation Procedure 6 Outdoor Unit Installation Instructions 7 2 Freezers Service...

Page 2: ...ox Temp lbs kg oz BTUH PTT047M6B 5 120 208 230 1 60 7 0 15 5 9 350 A 192 87 27 6 700 PTT063M6B 6 860 208 230 1 60 11 5 15 9 5 550 A 207 94 29 8 700 PTT072M6B 7 500 208 230 1 60 9 3 15 7 8 500 A 211 95...

Page 3: ...ood See reference on Page 2 Dimensional Diagrams Figure B Large Cabinet without weather hood See reference on Page 2 25 x 381 2 panel opening required for evaporator section of large cabinet sizes 23...

Page 4: ...ck any panel cam locks to install top mounted equipment The size and shape of the storage will generally determine the type and number of units to be used and their location Top View One System Evapor...

Page 5: ...prior approval is given to do so 6 When unpacking the system care should be taken to prevent damage 7 Avoid removing the shipping base until the unit has been moved to the final destination 8 Complete...

Page 6: ...nstallation to prevent bunching or folding which could affect the gasket to curb sealing or trap rainwater adjacent to the curb 4 Remove the weather hood from the system The compressor compartment cov...

Page 7: ...re 2 Roof membrane placed over curb Figure 3 PTT unit placed on roof of walk in color see rigging instructions Figure 4 Weather hood installed after electrical service connection PTT Models Example Ou...

Page 8: ...functioning properly 8 Clean the evaporator coil surface 9 Clean the drain pan and check the drain pan and drain line for proper drainage Refrigeration Sequence of Operation 1 Power is provided to the...

Page 9: ...Off Off Off If unit shows OFF depress the button and hold for three seconds On Automatic Defrost on start up Off Off Off On If coil temperature is below 65 F If it is above defrost is not initiated D...

Page 10: ...Compressor starts and evaporator fans delay for 2 minutes to freeze coil TABLE 6 Model PTT Medium Temperature Models EZY SETTING 2 SET POINT IS 34 F These models are intended for cooler applications a...

Page 11: ...lling template If necessary unscrew the two screws Do not unscrew excessively the screws must not be detached from the front panel phase 1 Insert the instrument in the opening in the panel and hold it...

Page 12: ...section of each wire 0 5 mm2 Avoid direct contact with internal electronic components Connection errors and connections other than those indicated in this manual may involve danger to the safety of th...

Page 13: ...al timer relating to parameter dI is updated If dI expires in OFF status a defrost is performed when restarting auxiliary relay management only in the following configurations H1 1 2 E0 alarm only H1...

Page 14: ...multifunction input analogue or digital Parameter 4 selects the probe shown on the display all the other display and control modes remain unchanged IMPORTANT the easy compact models can display up to...

Page 15: ...arameters with corresponding values for the control of the refrigeration system Table of Alarms and Signals When an alarm is activiated the display shows the corresponding message that flashes alterna...

Page 16: ...Ad and A0 The alarm is automatically reset when the temperature returns within the set limits see parameter AL HI flashing High temperature alarm The probe has measured a temperature higher than the s...

Page 17: ...until displaying 22 password to access the parameters press the SET button to confirm the password use the UP and DOWN buttons to scroll the parameters The LED corresponding to the category of paramet...

Page 18: ...mperature is too high parameters dt and d defrost probe the manual defrost is not activated and the defrost LED flashes compressor protection times set parameter d9 select d9 1 the high temperature al...

Page 19: ...0 r2 Maximum set point value 0 150 50 c2 Minimum compressor off time 0 100 4 do Type of Defrost 0 4 0 dI Interval between defrost 0 199 6 dt End defrost temperature set point 50 127 65 dP Maximum def...

Page 20: ...for proper superheat 4 Condensing temperature too low 4 Check ambient temperature 50 F to 100 F Compressor 1 Operating beyond design conditions 1 Add equipment so that conditions are within allowable...

Page 21: ...230V Defrost Heaters 4313F 3 3 3 3 3 3 3 3 Outdoor Parts Fan Pressure Control 28917301 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Fan Temperature Control 5521R 1 1 1 1 1 1 1 1 1 1 1 1 Drain Line Heate...

Page 22: ...PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN LINE HEATER TFC TEMPERATURE FA...

Page 23: ...ACITOR HPS HIGH PRESSURE SWITCH PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN...

Page 24: ...URE SWITCH PRIMARY SINGLE PHASE PROTECTION PROVIDED PRIMARY SINGLE PHASE PROTECTION PROVIDED CCH CRANKCASE HEATER PFC PRESSURE FAN CYCLE SWITCH DLT DRAIN LINE THERMOSTAT DLH DRAIN LINE HEATER TFC TEMP...

Page 25: ...Heatcraft Refrigeration Products LLC makes no warranty expressed or implied of fitness for any particular purpose or of any other nature whatsoever with respect to products manufactured or sold by Hea...

Page 26: ...is a continuing effort we reserve the right to make changes in specifications without notice Heatcraft Refrigeration Products LLC 2175 West Park Place Blvd Stone Mountain GA 30087 P 800 321 1881 www h...

Reviews: